FieldServer Profibus FS-8700-113 user manual

User manual for the device FieldServer Profibus FS-8700-113

Device: FieldServer Profibus FS-8700-113
Category: Computer Drive
Manufacturer: FieldServer
Size: 0.2 MB
Added : 10/27/2013
Number of pages: 14
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for FieldServer Profibus FS-8700-113. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with FieldServer Profibus FS-8700-113.

For your convenience

If looking through the FieldServer Profibus FS-8700-113 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual FieldServer Profibus FS-8700-113 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual FieldServer Profibus FS-8700-113 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
FieldServer Profibus FS-8700-113 User manual - Online PDF
Advertisement
« Page 1 of 14 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual FieldServer Profibus FS-8700-113 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to FieldServer Profibus FS-8700-113. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1




A Sierra Monitor Company

Driver Manual
(Supplement to the FieldServer Instruction Manual)

FS-8700-113 Profibus X30 DP Slave
Driver


APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version: 1.00
Document Revision: 11

Summary of the content on the page No. 2

FS-8700-113_Profibus_X30_DP_Slave Driver Manual Table of Contents TABLE OF CONTENTS 1. PROFIBUS X30 DP SLAVE DESCRIPTION................................................................... 3 2. DRIVER SCOPE OF SUPPLY......................................................................................... 4 2.1. Supplied by FieldServer Technologies for this driver.................................................. 4 rd 2.2. Provided by the Supplier of 3 Party Equipment ....................

Summary of the content on the page No. 3

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 3 of 14 1. Profibus X30 DP Slave Description The FieldServer Profibus DP Slave driver can be used to emulate a single Slave station on a Profibus network. DP Masters can open a connection of up to 244 Bytes of Input and 244 Bytes of Output data, but not exceeding a combined total of 416 Bytes to the FieldServer. The FieldServer can be added to the Profibus network with the use of the supplied GSD file for the ANYBUS card. Conne

Summary of the content on the page No. 4

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 4 of 14 2. Driver Scope of Supply 2.1. Supplied by FieldServer Technologies for this driver FieldServer Technologies Description PART # FS-8700-113 Driver Manual. X30-Profibus_DP_Slave Profibus X30 DP Slave Card rd 2.2. Provided by the Supplier of 3 Party Equipment rd 2.2.1. Required 3 Party Software Profibus Network Configuration Tool rd 2.2.2. Required 3 Party Configuration Connection to a properly terminated Profibus net

Summary of the content on the page No. 5

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 5 of 14 3. Hardware Connections The FieldServer is connected to the Profibus network as shown in the connection drawing below. Network termination switches Profibus DB9 connector Profibus Address switches Profibus Status LEDs Profibus connector pinouts Pin Name Description Housing Shield Connected to PE 1 Not connected - 2 Not connected - 3 B-Line Positive RxD/TxD according to RS 485 specification 4 RTS Request To Send* 5 GND BUS Iso

Summary of the content on the page No. 6

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 6 of 14 4. Configuring the FieldServer as a Profibus DP Server For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” filesprovided with the FieldServer). This section documents and describes the parameters necessary for con

Summary of the content on the page No. 7

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 7 of 14 1 4.2. Server Side Connection Descriptors Section Title Connections Column Title Function Legal Values Adapter Adapter Name Prof_DP_MS Example // Server Side Connections Connections Adapter Prof_DP_MS 4.3. Server Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Protocol Specify protocol used Anybus_Prof_DP_S Exa

Summary of the content on the page No. 8

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 8 of 14 4.4. Server Side Map Descriptors 4.4.1. FieldServer Specific Map Descriptor Parameters Column Title Function Legal Values Up to 32 alphanumeric Map_Descriptor_Name Name of this Map Descriptor characters Name of Data Array where One of the Data Array names Data_Array_Name data is to be stored in the from “Data Array” section FieldServer above Starting location in Data 0 to maximum specified in Data_Array_Offset Array “Da

Summary of the content on the page No. 9

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 9 of 14 4.4.3. Map Descriptor Example. // Server side Map Descriptor Map Descriptor Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Profibus_Data_Type, Address, Length, Scan_Interval Get_Data, Input_Data, 0, RDBC, Prof_5, WORD, 0, 100, 1s Put_Data, Output_Data, 0. WRBC, Prof_5, WORD, 0, 100, 1s Read function Map Write function Map Descriptor gets data Note that each address Des

Summary of the content on the page No. 10

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 10 of 14 Appendix A. Advanced Topics Appendix A.1. X30 Profibus LED indicators LED 1 – Not used LED 2 – Slave Online Status Color Frequency Description Green - Slave is online on the Profibus network Off - Slave is not online on the Profibus network LED 3 – Slave Offline Status Color Frequency Description Red - Slave is offline on the Profibus network Off - Slave is not offline on the Profibus network LED 4 – Fieldbu

Summary of the content on the page No. 11

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 11 of 14 Appendix A.2. Setting the FieldServer’s Profibus Station Address The Station Address can be set in the FieldServer’s CSV file using the System_Station_Address, (refer to Section 4.1), or it can be set with the two rotary switches as indicated on the connection diagram. The left switch selects the left decimal digit and the right switch the right decimal digit of the Station Address. Note that the software setting with the Sy

Summary of the content on the page No. 12

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 12 of 14 Appendix B. Troubleshooting Appendix B.1. FieldServer as a Profibus Slave If no communication is being experienced between a Profibus Master and a FieldServer Profibus Slave, check for the following most common issues: • The Node_ID must match the System_Station_Address in the configuration o Having these two parameters match in the configuration tells the FieldServer that the buffer referenced in the Node_ID refers to the bu

Summary of the content on the page No. 13

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 13 of 14 • The Data Type/Offset/Length combination may be incorrectly set up o In the FieldServer configuration, the Offset Parameter refers to the buffer offset in bytes (starting at 0), regardless of data type. o The Length parameter always refers to length in items, which means Float data will be the number of float values, Word data will be the number of words, etc. FieldServer Technologies 1991 Tarob Court Milpitas, Califor

Summary of the content on the page No. 14

FS-8700-113 X30 Profibus DP Slave Driver Manual Page 14 of 14 THIS PAGE INTENTIONALLY LEFT BLANK FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com


Alternative user manuals
# User manual Category Download
1 FieldServer FS-8700-01 User manual Computer Drive 0
2 FieldServer FS-8700-114 X30 User manual Computer Drive 0
3 FieldServer FS-8700-64 User manual Computer Drive 0
4 FieldServer Carrier DataPort FS-8700-86 User manual Computer Drive 2
5 FieldServer FS-8700-80 User manual Computer Drive 1
6 FieldServer FS-8700-103 User manual Computer Drive 1
7 FieldServer Dart FS-8700-78 User manual Computer Drive 1
8 FieldServer Gamewell FS-8700-83 User manual Computer Drive 2
9 FieldServer Data Aire (DAP) FS-8704-49 User manual Computer Drive 15
10 FieldServer FS-8700-105 User manual Computer Drive 1
11 FieldServer A Sierra Monitor Company X30 User manual Computer Drive 2
12 FieldServer FS-8700-73 User manual Computer Drive 1
13 FieldServer FS-8700-03 DF1 User manual Computer Drive 1
14 FieldServer Gardner Denver FS-8700-60 User manual Computer Drive 11
15 FieldServer Canatal Satchnet Driver FS-8700-59 User manual Computer Drive 3
16 Sony MSH-128S2 User manual Computer Drive 2
17 Sony 2GB Flash Drive USM2GLX User manual Computer Drive 0
18 Sony SAITE1300-F User manual Computer Drive 0
19 Sony CRX - 160E User manual Computer Drive 0
20 Sony 2GN User manual Computer Drive 0