Summary of the content on the page No. 1 
                    
                         
A Sierra Monitor Company 
 
Driver Manual  
(Supplement to the FieldServer Instruction Manual) 
 
FS-8704-07 AB_CSP 
 
APPLICABILITY & EFFECTIVITY 
Effective for all systems manufactured after May 1, 2001                                                                                                                                                                                                                                                                                                      
                    
                    Summary of the content on the page No. 2 
                    
                        FS-8704-07_AB-CSP Manual        Index  TABLE OF CONTENTS  1. Allen Bradley AB_CSP Description.................................................................................3  2. Hardware/Software............................................................................................................4  2.1. Supplied by FieldServer Technologies for this Driver...................................................4  rd 2.2. Provided by Supplier of 3 Party Equipment................................
                    
                    Summary of the content on the page No. 3 
                    
                        FS-8704-07_AB-CSP Manual       Page 3 of 15  1. Allen Bradley AB_CSP Description  The AB_CSP driver allows the FieldServer to transfer data to and from devices over AB_CSP  Ethernet protocol. The FieldServer can emulate either a Server or Client.     The information that follows describes how to expand upon the factory defaults provided in the  configuration files included with the FieldServer.  FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com  Te
                    
                    Summary of the content on the page No. 4 
                    
                        FS-8704-07_AB-CSP Manual       Page 4 of 15  2. Hardware/Software   2.1. Supplied by FieldServer Technologies for this Driver  FieldServer Technologies PART # DESCRIPTION  FS-8915-10 Ethernet cable (7 foot)   FS-8704-07 Driver Manual  rd 2.2. Provided by Supplier of 3 Party Equipment  PART # DESCRIPTION  1  AB_CSP compatible PLC, e.g. SLC5/05 etc.   2   AB_CSP Client, e.g. Wonderware, Intellution FIX, GE Cimplicity, etc.                                                    1  If FieldServer used a
                    
                    Summary of the content on the page No. 5 
                    
                        FS-8704-07_AB-CSP Manual       Page 5 of 15  3. Hardware Connections  Make sure the device IP_address is configured to be on the same IP network as the  FieldServer. Use a crossover cable if the FieldServer is connected directly to the PLC device.  Use a straight cable if the FieldServer is connected to a hub.    Configure the PLC according to manufacturer’s instructions    PLC Ethernet Interface SITE FS-8915-10 ETHERNET FS-8915-10 (408)-262-2299 FIELDSERVER AB-CSP CONNECTION DIAGRAM BASE NAME: 
                    
                    Summary of the content on the page No. 6 
                    
                        FS-8704-07_AB-CSP Manual       Page 6 of 15  4. Configuring the FieldServer as a AB-CSP Client  For a detailed discussion on FieldServer configuration, please refer to the FieldServer  Configuration Manual. The information that follows describes how to expand upon the factory  defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  provided with the FieldServer).    This section documents and describes the parameters necessary for configuring the Fiel
                    
                    Summary of the content on the page No. 7 
                    
                        FS-8704-07_AB-CSP Manual       Page 7 of 15  4.2. Client Side Connection Descriptors  Section Title  Connections  Column Legal  Function  Title Values  Specify which port the device is connected to the  Adapter N1  FieldServer  Protocol  Specify protocol used AB_CSP    Example    //    Client Side Connections      Connections   Adapter, Protocol     N1, AB_CSP    4.3. Client Side Node Descriptors  Section Title  Nodes  Column Title Function Legal Values  Up to 32 alphanumeric  Node_Name Provide 
                    
                    Summary of the content on the page No. 8 
                    
                        FS-8704-07_AB-CSP Manual       Page 8 of 15  4.4. Client Side Map Descriptors Client Side Map Descriptors  4.4.1. FieldServer Related Map Descriptor Parameters  Column Title Function Legal Values  Name of this Map Up to 32 alphanumeric  Map_Descriptor_Name  Descriptor characters  Name of Data Array  One of the Data Array  where data is to be  Data_Array_Name names from “Data Array”  stored in the  section above  FieldServer  Starting location in Data 0 to maximum specified in  Data_Array_Offset 
                    
                    Summary of the content on the page No. 9 
                    
                        FS-8704-07_AB-CSP Manual       Page 9 of 15  4.4.3. Map Descriptor Example  //    Client Side Map Descriptors             Map_Descriptors                       Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, File_Type, File_Number, Address, Length, Scan_Interval  CMD_AI_01, DA_AI_01, 0, RDBC, PLC_01, N, 10, 0, 16, 1.0s  CMD_AO_01, DA_AO_01, 0, RDBC, PLC_01, N, 11 0, 16, 1.0s             Map_Descriptors                       Map_Descriptor_Name, Data_Array_Name, Data
                    
                    Summary of the content on the page No. 10 
                    
                        FS-8704-07_AB-CSP Manual       Page 10 of 15  5. Configuring the FieldServer as an AB_CSP Server  5.1. Server Side Connection Descriptors  Section Title  Connections  Column Title Function Legal Values  Specify which port the device  Adapter is connected to the N1  FieldServer  Protocol Specify protocol used AB_CSP  Must be on the same  Virtual IP address of  IP_Address optional subnet as the client or  FieldServer  gateway    Example    //    Server Side Connections        Connections    Adapte
                    
                    Summary of the content on the page No. 11 
                    
                        FS-8704-07_AB-CSP Manual       Page 11 of 15  5.3. Server Side Map Descriptors  5.3.1. FieldServer Related Map Descriptor Parameters  Column Title Function Legal Values  Name of this Map Up to 32 alphanumeric  Map_Descriptor_Name  Descriptor characters  Name of Data Array  One of the Data Array  where data is to be  Data_Array_Name names from “Data Array”  stored in the  section above  FieldServer  Starting location in Data 0 to maximum specified in  Data_Array_Offset  Array “Data Array” section
                    
                    Summary of the content on the page No. 12 
                    
                        FS-8704-07_AB-CSP Manual       Page 12 of 15  5.3.3. Map Descriptor Example  //   Client Side Map descriptors    Map_Descriptors                                                                                                                Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, File_Type, File_Number, Address, Length, Data_Array_Low_Scale, Data_Array_High_Scale, Node_Low_Scale, Node_High_Scale   SMD_AI_01, DA_AI_01, 0, Server, ABE_Srv_11, N, 10, 0, 16, 0, 1
                    
                    Summary of the content on the page No. 13 
                    
                        FS-8704-07_AB-CSP Manual       Page 13 of 15  Appendix A. Troubleshooting  Appendix A.1. Continuous Map Descriptors  RS View has been known to crash if it tries to read a server mapping that is discontinuous.  e.g.    Server map 1:  N21: 0-31   Server map 2:  N21: 32-100  This will crash RS view as the AB_CSP will attempt to map N21: 0-100   If set up as      Server Map 1: N21: 0-100, no problems are experienced  FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.f
                    
                    Summary of the content on the page No. 14 
                    
                        FS-8704-07_AB-CSP Manual       Page 14 of 15  Appendix B. Command Support  The following commands are supported by the FieldServer for the various PLC types:  Typical  PLC_Type File_type FNC Read FNC Write  Command  N 1 Range Read 0 Range Write N7: 3, L5  PLC3 F 1 Range Read 0 Range Write F12: 3, L5  B 1 Range Read 2 Bit Write B3/4: 5, l5  N 1 Range Read 0 Range Write N7: 3 , L5  PLC5 F 1 Range Read 67 Typed Write F12: 3, L5  B 1 Range Read 26 Read Modify Write B3/4: 5, L5  Protected Typed Prote
                    
                    Summary of the content on the page No. 15 
                    
                        FS-8704-07_AB-CSP Manual       Page 15 of 15  Appendix C. Revision History  Driver Doc. Date Resp Format Comment  Ver. Rev. 2/3/04 MF MF 1.00 1 Formatting updated.  Revision table added.    Added connection diagram.  Converted final  5/6/04 Meg Meg 1.00 2 chapters to appendices.  Removed nonsense  text.  6/14/04 JD  1.00 3 Releasing  Changed Appendix numbering to letters and  added borders and shading.  Corrected example  12/27/04 Meg Meg 1.00 4 table formatting.  Removed some commas in  example