FieldServer FS-8704-01 user manual

User manual for the device FieldServer FS-8704-01

Device: FieldServer FS-8704-01
Category: Computer Drive
Manufacturer: FieldServer
Size: 0.12 MB
Added : 6/13/2013
Number of pages: 12
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for FieldServer FS-8704-01. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with FieldServer FS-8704-01.

For your convenience

If looking through the FieldServer FS-8704-01 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual FieldServer FS-8704-01 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual FieldServer FS-8704-01 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
FieldServer FS-8704-01 User manual - Online PDF
Advertisement
« Page 1 of 12 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual FieldServer FS-8704-01 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to FieldServer FS-8704-01. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1





A Sierra Monitor Company

Driver Manual
(Supplement to the FieldServer Instruction Manual)

FS-8704-01 SMC TCP/IP

APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version: 1.01
Document Revision: 0

Summary of the content on the page No. 2

FS-8704-01 SMC TCP/IP Driver Manual Table of Contents TABLE OF CONTENTS 1. SMC TCP/IP DESCRIPTION .............................................................................................3 2. DRIVER SCOPE OF SUPPLY...........................................................................................4 2.1. Supplied by FieldServer Technologies for this driver ...................................................4 rd 2.2. Provided by the Supplier of 3 Party Equipment............

Summary of the content on the page No. 3

FS-8704-01 SMC TCP/IP Driver Manual Page 3 of 12 1. SMC TCP/IP Description The SMC TCP/IP driver allows the FieldServer to transfer data to and from other FieldServers over Ethernet using SMC TCP/IP protocol. The FieldServer can emulate either a Server or Client. The SMC TCP/IP driver can be used for inter-bridge (FieldServer to FieldServer) communications to perform tasks like mirroring data arrays between FieldServers. Max Nodes Supported FieldServer Mode Nodes Comments

Summary of the content on the page No. 4

FS-8704-01 SMC TCP/IP Driver Manual Page 4 of 12 2. Driver Scope of Supply 2.1. Supplied by FieldServer Technologies for this driver FieldServer Technologies Description PART # FS-8915-10 UTP cable (7 foot) for Ethernet connection FS-8704-01 SMC TCP/IP Driver Manual. rd 2.2. Provided by the Supplier of 3 Party Equipment rd 2.2.1. Required 3 Party Hardware Part # Description ∗ Ethernet 10/100 BaseT hub rd 2.2.2. Required 3 Party Software None. rd 2.2.3. Required 3 Pa

Summary of the content on the page No. 5

FS-8704-01 SMC TCP/IP Driver Manual Page 5 of 12 3. Hardware Connections The FieldServer is connected to the Ethernet network as shown in the connection drawing. Ethernet Hub or Switch N1 N1 FieldServer 1 FieldServer 2 3.1. Hardware Connection Tips / Hints Please use the appropriate category Ethernet cable, i.e. At least CAT5 for a 100Mb/s connection. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-229

Summary of the content on the page No. 6

FS-8704-01 SMC TCP/IP Driver Manual Page 6 of 12 4. Configuring the FieldServer as a SMC TCP/IP Client For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for conf

Summary of the content on the page No. 7

FS-8704-01 SMC TCP/IP Driver Manual Page 7 of 12 4.2. Client Side Connection Descriptions Section Title Connections Column Title Function Legal Values Adapter Adapter Name N1 Protocol Specify protocol used SMT Example // Client Side Connections Connections Adapter, Protocol N1, SMT 4.3. Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters Station address of

Summary of the content on the page No. 8

FS-8704-01 SMC TCP/IP Driver Manual Page 8 of 12 4.4. Client Side Map Descriptors 4.4.1. FieldServer Related Map Descriptor Parameters Column Title Function Legal Values Name of this Map Up to 32 alphanumeric Map_Descriptor_Name Descriptor characters Name of Data Array One of the Data Array where data is to be Data_Array_Name names from “Data Array” stored in the section above FieldServer Starting location in Data 0 to maximum specified in Data_Array_Offset Array “Data A

Summary of the content on the page No. 9

FS-8704-01 SMC TCP/IP Driver Manual Page 9 of 12 4.5. Map Descriptor Example. // Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Data_Type, Target_DA_Name, Target_DA_Offset, Length CMD_01, DA_AI_01, 0, RDBC, Node_1, Register, Reg_Values, 0, 100 The name of the Data Array in the remote FieldServer from which data is to be read.. FieldServer Technologies 1991 Tarob Court Milpita

Summary of the content on the page No. 10

FS-8704-01 SMC TCP/IP Manual Page 10 of 12 5. Configuring the FieldServer as a SMC TCP/IP Server For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configur

Summary of the content on the page No. 11

FS-8704-01 SMC TCP/IP Manual Page 11 of 12 5.2. Server Side Node Descriptors Section Title Nodes Column Title Function Legal Values Up to 32 alphanumeric Node_Name Provide name for node characters Modbus station address of physical Node_ID 1-65535 server node Protocol Specify protocol used SMT Specifies time FieldServer will reserve server side connection Server_Hold_Timeout* while waiting for the Client side to >1.0s update data in Data_Array (if necessary) Example

Summary of the content on the page No. 12

FS-8704-01 SMC TCP/IP Manual Page 12 of 12 THIS PAGE INTENTIONALLY LEFT BLANK FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com


Alternative user manuals
# User manual Category Download
1 FieldServer FS-8700-01 User manual Computer Drive 0
2 FieldServer FS-8700-114 X30 User manual Computer Drive 0
3 FieldServer FS-8700-64 User manual Computer Drive 0
4 FieldServer Carrier DataPort FS-8700-86 User manual Computer Drive 2
5 FieldServer FS-8700-80 User manual Computer Drive 1
6 FieldServer FS-8700-103 User manual Computer Drive 1
7 FieldServer Dart FS-8700-78 User manual Computer Drive 1
8 FieldServer Gamewell FS-8700-83 User manual Computer Drive 2
9 FieldServer Data Aire (DAP) FS-8704-49 User manual Computer Drive 15
10 FieldServer FS-8700-105 User manual Computer Drive 1
11 FieldServer A Sierra Monitor Company X30 User manual Computer Drive 2
12 FieldServer FS-8700-73 User manual Computer Drive 1
13 FieldServer FS-8700-03 DF1 User manual Computer Drive 1
14 FieldServer Gardner Denver FS-8700-60 User manual Computer Drive 11