FieldServer Data Aire (DAP) FS-8704-49 user manual

User manual for the device FieldServer Data Aire (DAP) FS-8704-49

Device: FieldServer Data Aire (DAP) FS-8704-49
Category: Computer Drive
Manufacturer: FieldServer
Size: 0.49 MB
Added : 6/13/2013
Number of pages: 48
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for FieldServer Data Aire (DAP) FS-8704-49. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with FieldServer Data Aire (DAP) FS-8704-49.

For your convenience

If looking through the FieldServer Data Aire (DAP) FS-8704-49 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual FieldServer Data Aire (DAP) FS-8704-49 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual FieldServer Data Aire (DAP) FS-8704-49 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
FieldServer Data Aire (DAP) FS-8704-49 User manual - Online PDF
Advertisement
« Page 1 of 48 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual FieldServer Data Aire (DAP) FS-8704-49 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to FieldServer Data Aire (DAP) FS-8704-49. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1


A Sierra Monitor Company

Driver Manual
(Supplement to the FieldServer Instruction Manual)

FS-8704-49 Data Aire (DAP)
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version: 1.07
Document Revision: 9

Summary of the content on the page No. 2

FS-8700-49_Data_Aire_DAP Table of Contents TABLE OF CONTENTS 1. Data Aire Description..................................................................................................... 4 1.1. Performance Issues - DARTIII only............................................................................ 4 1.2. Data Alarm Network Module Network LED Operation ................................................ 4 2. Driver Scope of Supply...................................................

Summary of the content on the page No. 3

FS-8700-49_Data_Aire_DAP Table of Contents Appendix E. Writing data to DAP Devices ........................................................................40 Appendix E.1. Background..................................................................................................40 Appendix E.2. Associated Map Descriptors.........................................................................40 Appendix E.3. Starting/Stopping DAP devices ............................................

Summary of the content on the page No. 4

FS-8700-49_Data_Aire_DAP Page 4 of 48 1. Data Aire Description The Data Aire Driver is capable of direct connection to a network of Data Aire DAP devices. The FieldServer is connected in a RS-485 loop topology. Two FieldServer ports are required per loop. The driver is an active client. All data is obtained by poll & response. Connection to a DART is not supported by this driver. The driver may be configured very simply (See Section 4.4). A number of advanced configu

Summary of the content on the page No. 5

FS-8700-49_Data_Aire_DAP Page 5 of 48 2. Driver Scope of Supply 2.1. Supplied by FieldServer Technologies for this driver FieldServer Technologies Description PART # RS-485 connection adapter FS-8700-49 Driver Manual. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Summary of the content on the page No. 6

Gnd _ + FG Gnd _ + FG _ 5V 500mA + 12V 5 00mA _ 12V 5 00mA + 5V 1 .5A 0V Gnd _ + FG Gnd _ + FS-8700-49_Data_Aire_DAP Page 6 of 48 3. Hardware Connections The FieldServer is connected to the DAP devices as shown in connection drawing. Configure the DAP devices according to manufacturer’s instructions Dap/Chiller/Dap80 Dap/Chiller/Dap80 TO OTHER DEVICES RS485 CONFIG PC 9600 N81 (RUISYS) MODEL 8051 Power Net 1 Net 2 P8 P7 P6 P5 P4 P3 P2 P1 RS 232 Et hernet R2 R1 GROUND 5

Summary of the content on the page No. 7

FS-8700-49_Data_Aire_DAP Page 7 of 48 4. Configuring the FieldServer as a Data Aire Client For a detailed discussion on FieldServer configuration, please refer to the FieldServer instruction manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the

Summary of the content on the page No. 8

FS-8700-49_Data_Aire_DAP Page 8 of 48 4.2. Client Side Connection Descriptions Connections Column Title Function Legal Values 1 This is the FieldServer port P1-P8, R1-R2 Port connected to the DART’s RS- (P1-P8) requires 232/485 232 port. converter. The return loop from the DAP 1 P1-P8, R1-R2 devices is connected to this Secondary_Port* (R1-R2) requires 232/485 port. (Loop connected to Tx+ converter. & Tx- terminals. 2 2400/9600 (Vendor Baud* Specify baud rate Limitatio

Summary of the content on the page No. 9

FS-8700-49_Data_Aire_DAP Page 9 of 48 4.3. Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters Modbus station address of Node_ID 1-259 physical server node Protocol Specify protocol used DAP Specify which port the device is 3 Connection P1-P8, R1-R2 connected to the FieldServer Example // Client Side Nodes Nodes Node_Name Node_ID Protocol Connection Unit1, 1,

Summary of the content on the page No. 10

FS-8700-49_Data_Aire_DAP Page 10 of 48 4.4.2. Driver Related Map Descriptor Parameters Column Title Function Legal Values One of the node names Name of Node to fetch data Node_Name specified in “Client Node from Descriptor” above Data_Type Data type Register, Coil, AI, DI Length Length of Map Descriptor 1 Not required for client Address Starting address of read block configuration - used in simulation configuration only. Only required when the function is a Read (rdbc).

Summary of the content on the page No. 11

FS-8700-49_Data_Aire_DAP Page 11 of 48 4.4.4. Map Descriptor Example 1 - Everything The FieldServer listens passively for all possible data from the device called ‘unit1’ and stores the data in an array called ‘DA_01’. The data that is obtained from ‘unit1’ is dependent on the type of device. Irrespective of the device type the arrangement of data, stored in DA_01, is fixed. If a data field cannot be obtained from ‘unit1’ then the array is left with a zero value for that data fi

Summary of the content on the page No. 12

FS-8700-49_Data_Aire_DAP Page 12 of 48 4.4.6. Map Descriptor: Example 3 – Writing multiple points using one message. Additional information is provided in Appendix B // Client Side Map Descriptors Map Descriptors Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, Address, Length, DA_Field, DA_Assoc, Scan_Interval Write_Map Descriptor_1, DA_SETPOINTS, 0, WRBC, Unit1, 0, 1, nom_h_setpt, 2, 120s Write_Map Descriptor_1, DA_SETPOINTS,

Summary of the content on the page No. 13

FS-8700-49_Data_Aire_DAP Page 13 of 48 Appendix A. Data Tables Appendix A.1. Data Table 1: Array Locations of ‘Everything’ In the following table the array location indicates the offset in the Data Array at which a data field can be found. (This offset is relative to the offset specified in the Map Descriptor) The columns headed 2, 3 … indicate the unit types for which the data fields are available. For example: The field ‘d_temp’ can be read from unit types 2, 5,6,7,9 but not f

Summary of the content on the page No. 14

FS-8700-49_Data_Aire_DAP Page 14 of 48 Array Num Method Data Field 2 3 4 5 6 7 8 9 14 15 Message Type Location Elements bitErrors - see Appendix 73 3 56 x x x x x Dap-Stat E.4 for more information 185 1 1 runtime_c1 x x x x x Dap-Xtra 186 1 1 runtime_c2 x x x x x Dap-Xtra 187 1 1 runtime_c3 x x x x x Dap-Xtra 188 1 1 runtime_c4 x x x x x Dap-Xtra 189 1 1 runtime_ht1 x x x x x Dap-Xtra 190 1 1 runtime_ht2 x x x x x Dap-Xtra 191 1 1

Summary of the content on the page No. 15

FS-8700-49_Data_Aire_DAP Page 15 of 48 Array Num Method Data Field 2 3 4 5 6 7 8 9 14 15 Message Type Location Elements 498 1 1 loc_h_deadband X X X Dap-Menu 499 1 1 loc_h_setpt X X X Dap-Menu 500 2 1 loc_t_dband X X X Dap-Menu 501 2 1 loc_t_setpt X X X Dap-Menu 502 1 1 lo_cal X X X Dap-Menu 503 1 1 lo_h_lim X X X Dap-Menu 504 2 1 lo_t_lim X X X Dap-Menu 505 1 1 main_int X X X Dap-Menu 506 1 1 passwd_a X X X Dap

Summary of the content on the page No. 16

FS-8700-49_Data_Aire_DAP Page 16 of 48 Array Num Method Data Field 2 3 4 5 6 7 8 9 14 15 Message Type Location Elements 854 4 1 adjust_rate x x x Chiller-Menu 855 4 1 auto_ack X X X Chiller-Menu 856 2 1 aux_setpt X X X Chiller-Menu 857 4 1 backup_mods X X X Chiller-Menu 858 2 1 backup_setpt X X X Chiller-Menu 859 4 1 cmota X X X Chiller-Menu 860 4 1 comp_type X X X Chiller-Menu 861 4 1 ptc

Summary of the content on the page No. 17

FS-8700-49_Data_Aire_DAP Page 17 of 48 Array Num Method Data Field 2 3 4 5 6 7 8 9 14 15 Message Type Location Elements 907 4 1 alrm_select_4 X X X X Dap80-Menu 908 4 1 ant-enable X X X X Dap80-Menu 909 4 1 autoflush_time X X X X Dap80-Menu 910 4 1 auto_ack X X X X Dap80-Menu 911 4 1 comp_config X X X X Dap80-Menu 912 4 1 control_type X X X X Dap80-Menu 913 4 1 c_mode X X X X Dap80-Menu 914 4 1 da_volts X X X X Dap80-Me

Summary of the content on the page No. 18

FS-8700-49_Data_Aire_DAP Page 18 of 48 Array Num Method Data Field 2 3 4 5 6 7 8 9 14 15 Message Type Location Elements 1086 4 1 voice X X X X Dap80-Menu 1100 1 1 sensor_1_name x x Dap80-Analog 1101 1 1 sensor_1_units x x Dap80-Analog 1102 1 1 sensor_1_type x x Dap80-Analog 1103 1 1 sensor_1_min_val x x Dap80-Analog 1104 1 1 sensor_1_max_val x x Dap80-Analog 1105 1 1 sensor_1_cal x x Dap80-Analog 1106 1 1 sensor_2_

Summary of the content on the page No. 19

FS-8700-49_Data_Aire_DAP Page 19 of 48 FieldServer FieldServer Data Message D/A Control Panel Array Point Description Field Type Type Location Lowest Humidity in the 60 LoHum DAP Stat All last 24 hrs 61 Chilled_water Water Valve setting DAP Stat All 62 Compressor_config Compressor configuration DAP Stat All 63 heat_strip_config Heating configuration DAP Stat All 64 hum_config Humidifier configuration DAP Stat All Utilization Percentage of 65 csUtilPct DAP Stat All coolin

Summary of the content on the page No. 20

FS-8700-49_Data_Aire_DAP Page 20 of 48 FieldServer FieldServer Data Message D/A Control Panel Array Point Description Field Type Type Location 474 adj_rate Adjustment rate DAP Menu DAP049,048,046 optional alarm 1 delay 478 alrm_delay_1 DAP Menu DAP049,048,046 setting optional alarm 2 delay 479 alrm_delay_2 DAP Menu DAP049,048,046 setting optional alarm 3 delay 480 alrm_delay_3 DAP Menu DAP049,048,046 setting Enable optional alarm 1 481 alrm_enable_1 DAP Menu DAP049,048


Alternative user manuals
# User manual Category Download
1 FieldServer FS-8700-01 User manual Computer Drive 0
2 FieldServer FS-8700-114 X30 User manual Computer Drive 0
3 FieldServer FS-8700-64 User manual Computer Drive 0
4 FieldServer Carrier DataPort FS-8700-86 User manual Computer Drive 2
5 FieldServer FS-8700-80 User manual Computer Drive 1
6 FieldServer FS-8700-103 User manual Computer Drive 1
7 FieldServer Dart FS-8700-78 User manual Computer Drive 1
8 FieldServer Gamewell FS-8700-83 User manual Computer Drive 2
9 FieldServer FS-8700-105 User manual Computer Drive 1
10 FieldServer A Sierra Monitor Company X30 User manual Computer Drive 2
11 FieldServer FS-8700-73 User manual Computer Drive 1
12 FieldServer FS-8700-03 DF1 User manual Computer Drive 1
13 FieldServer Gardner Denver FS-8700-60 User manual Computer Drive 11
14 FieldServer Canatal Satchnet Driver FS-8700-59 User manual Computer Drive 3
15 FieldServer ControlNet FS-8700-104 User manual Computer Drive 1
16 Sony MSH-128S2 User manual Computer Drive 2
17 Sony 2GB Flash Drive USM2GLX User manual Computer Drive 0
18 Sony SAITE1300-F User manual Computer Drive 0
19 Sony CRX - 160E User manual Computer Drive 0
20 Sony 2GN User manual Computer Drive 0