Краткое содержание страницы № 1
530.26-TG3YI (1294)
®
SINGLE PACKAGE
GAS / ELECTRIC UNITS AND
SINGLE PACKAGE AIR CONDITIONERS
D3CE / D3CG 180 & 240
(WORLD 50 HZ)
SUNLINE 2000
DCG
Shown
DESCRIPTION
Sunline 2000 units are highly efficient, convertible rooftops. All
With horizontal ductwork, it should be mounted on the return
models have dual refrigerant circuits for efficient part load
air duct.
operation. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
All supply
Краткое содержание страницы № 2
530.26-TG3YI On units built prior to January 1995 an accessory field harness FIELD-INSTALLED ACCESSORIES must be installled. SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS Power exhaust is not available as a field installed option. Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing BAROMETRIC RELIEF DAMPER - This damper accessory up to 100% outdoor air with nominal 1% leakage type dampers. can be used to relieve internal air pres
Краткое содержание страницы № 3
530.26-TG3YI ® SUNLINE 2000 (OPTION / ACCESS.) DCE UNITS ALUMINIZED STEEL THROWAWAY D*CG UNITS (OPTION / ACCESSORY) FEMALE MODEL DCG (Gas Heating) RATINGS CAPACITY RATINGS - Cooling / Electric Heating 1 Electric Heat4 Rating Total Output, Total Input, 2 3 Sensible Output, Latent Output, Model COP EER Nominal Capacity, Point Mbh / kW kW Mbh / kW Mbh / kW kW T1 159 / 46.6 18.2 2.60 8.80 132 / 38.7 26.9 / 7.9 D3CE180 T2 142 / 41.7 20.0 2.10 7.15 141 / 41.2 1.6 / 0.5 18, 36, 54, 72 T3 152 / 44.6 1
Краткое содержание страницы № 4
530.26-TG3YI 3 COOLING CAPACITIES (m /s Air Flow) - 180 UNITS 1 Sensible Capacity , kW Air On Total Power 1 2 Evaporator Coil Cap. Input Entering Dry Bulb Temp., °C 3 kW kW m /s 32 30 28 26 24 22 WB °C @27°C Air Temperature on Condenser Coil 23 66.4 14.7 51 44 37 30 23 - 21 62.3 14.4 59524437 3023 3.40 19 58.2 14.0 58585245 3831 17 56.7 14.0 57575649 4134 15 55.2 13.9 55555552 4537 23 61.5 14.5 46 40 34 27 21 - 21 57.7 14.2 53464034 2822 2.80 19 53.9 13.9 54534741 3528 17 52.5 13.8 52525144 3832
Краткое содержание страницы № 5
530.26-TG3YI COOLING CAPACITIES (CFM Air Flow) - 180 UNITS 1 Sensible Capacity , MBH Air On Total Power 1 2 Evaporator Coil Cap. Input Entering Dry Bulb Temp., °F MBH kW CFM WB °F 90 86 82 79 75 72 @80°F Air Temperature on Condenser Coil1 73 227 14.7 175 151 126 102 78 - 70 213 14.4 200 176 152 127 103 79 7200 66 199 14.0 199 199 177 153 128 104 63 193 14.0 193 193 190 166 142 117 59 188 13.9 188 188 188 176 152 128 73 210 14.5 157 136 115 93 72 - 70 197 14.2 180 159 138 116 95 74 5930 66 184 13
Краткое содержание страницы № 6
530.26-TG3YI 3 COOLING CAPACITIES (m /s Air Flow) - 240 UNITS 1 Sensible Capacity , kW Air On Total Power 1 2 Evaporator Coil Cap. Input Entering Dry Bulb Temp., °C 3 kW kW m /s 32 30 28 26 24 22 WB °C @27°C Air Temperature on Condenser Coil 23 80.4 19.0 74 65 55 46 37 - 21 77.6 18.8 78706152 4333 4.40 19 74.8 18.6 75756757 4839 17 72.4 18.4 72727162 5344 15 70.0 18.1 70707065 5647 23 76.9 18.8 68 60 52 44 36 - 21 74.3 18.6 73655749 4133 3.80 19 71.6 18.4 72706254 4638 17 69.3 18.2 69696759 5143
Краткое содержание страницы № 7
530.26-TG3YI COOLING CAPACITIES (CFM Air Flow) - 240 UNITS 1 Sensible Capacity , MBH Air On Total Power 1 2 Evaporator Coil Cap. Input Entering Dry Bulb Temp., °F MBH kW CFM WB °F 90 86 82 79 75 72 @80°F Air Temperature on Condenser Coil 73 274 19.0 252 221 189 158 127 - 70 265 18.8 265 240 208 177 146 114 9320 66 255 18.6 255 255 227 196 164 133 63 247 18.4 247 247 243 211 180 149 59 239 18.1 239 239 239 223 192 161 73 263 18.8 232 205 177 150 123 - 70 253 18.6 250 222 195 168 141 113 8050 66 2
Краткое содержание страницы № 8
530.26-TG3YI BLOWER PERFORMANCE (D*CE180 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONS 3 STANDARD DRIVE (m /s) AIRFLOW MOTOR BLOWER 3 3 3 3 3 PULLEY 2.10 m /s 2.45 m /s 2.80 m /s 3.10 m /s 3.40 m /s SPEED, (TURNS ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input RPM OPEN)* (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) 845 6.0 173 1.8 2.2 138 2.2 2.6 83 2.6 3.1 18 3.0 3.5 - - - 885 5.
Краткое содержание страницы № 9
530.26-TG3YI BLOWER PERFORMANCE (D*CE240 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONS 3 STANDARD DRIVE (m /s) AIRFLOW MOTOR BLOWER 3 3 3 3 3 PULLEY 2.80 m /s 3.30 m /s 3.80 m /s 4.10 m /s 4.40 m /s SPEED, (TURNS ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input RPM OPEN)* (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) 765 6.0 137 2.9 3.3 93 2.9 3.3 23 3.2 3.7 ----- - 795 5.0 176 3.0
Краткое содержание страницы № 10
530.26-TG3YI BLOWER PERFORMANCE (D*CG180 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONS 3 STANDARD DRIVE (m /s) AIRFLOW MOTOR BLOWER 3 3 3 3 3 PULLEY 2.10 m /s 2.45 m /s 2.80 m /s 3.10 m /s 3.40 m /s SPEED, (TURNS ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input RPM OPEN)* (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) 845 6.0 206 1.8 2.2 146 2.0 2.5 80 2.4 2.8 18 2.7 3.2 - - - 885 5.
Краткое содержание страницы № 11
530.26-TG3YI BLOWER PERFORMANCE (D*CG240 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONS 3 STANDARD DRIVE (m /s) AIRFLOW MOTOR BLOWER 3 3 3 3 3 PULLEY 2.80 m /s 3.30 m /s 3.80 m /s 4.10 m /s 4.40 m /s SPEED, (TURNS ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input RPM OPEN)* (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) 765 6.0 202 2.1 2.4 80 2.7 3.1 - ------- 795 5.0 238 2.3 2.6 117 2
Краткое содержание страницы № 12
530.26-TG3YI BLOWER MOTOR AND DRIVE DATA ADJUSTABLE FIXED 1 MOTOR BELT (NOTCHED) 2 MOTOR PULLEY BLOWER PULLEY BLOWER UNIT RANGE PITCH PITCH PITCH SIZE FRAME EFF. BORE DESIG- BORE DESIG- DESIG- (RPM) kW/HP DIA. DIA. LENGTH QTY SIZE (%) (mm/in.) NATION (mm/in.) NATION NATION (mm/in.) (mm / in.) (mm/in.) 109-135 1 180 845-1040 3.0 / 4.0 184T 84 29 / 1 ⁄ 1VP56 188 / 7.4 25 / 1 BK80 1773 / 69.8 BX68 1 8 4.3-5.3 STD. DRIVE 140-165 3 3 240 765-905 5.6 / 7.5 213T 87 35 / 1 ⁄ 1VP68 264 / 10.4 30 / 1 ⁄ B
Краткое содержание страницы № 13
530.26-TG3YI FIELD WIRING - Electric/Electric and Gas/Electric Units LINE VOLTAGE L1 Refer to the TERMINAL ELECTRICAL DATA BLOCK 2TB L2 tables to size the IN UNIT power wiring, the fuses and CONTROL BOX L3 the disconnect switch. NEUTRAL N TERMINAL GRD. LUG 24 VOLT TRANSFORMER ELECTRICAL DATA - Cooling Only Units and Units With Gas Heat SUPPLY AIR TOTAL UNIT OUTDOOR COMPRESSOR BLOWER AMPACITY, FAN MAX. MIN. UNIT POWER 2 MOTOR, (FLA) (AMPS) MOTOR, FUSE WIRE SIZE , SIZE SUPPLY 1 2 RLA LRA (#1 & #
Краткое содержание страницы № 14
530.26-TG3YI ELECTRICAL DATA - Units With Supplemental Electric Heating HEATER OPTION MINIMUM POWER MINIMUM UNIT CIRCUIT MAXIMUM 2 SUPPLY WIRE SIZE OUTPUT 1 SIZE MODEL STAGES AMPS AMPACITY FUSE SIZE 2 (VOLTS) (mm /AWG) kW (AMPS) E018 11.3 1 17.1 47.0 60 10 / 8 E036 22.6 2 34.3 53.6 60 16 / 6 380-3+N-50 E054 33.8 2 51.4 75.0 80 25 / 4 E072 45.1 2 68.6 96.5 100 35 / 2 180 E018 13.5 1 18.7 47.0 60 10 / 8 E036 26.9 2 37.4 57.5 60 16 / 6 415-3+N-50 E054 40.4 2 56.2 80.9 90 25 / 4 E072 53.8 2 74.9 10
Краткое содержание страницы № 15
530.26-TG3YI UNIT DIMENSIONS - D*CE180 & 240 UNITS 1235 (48-5/8") (180) 1337 (52-5/8") (240) 3181 (125-1/4") (180) 3461 (136-1/4") (240) 616 (24-1/4") (180) 895 (35-1/4") (240) RETURN AIR All dimensions are in millimeters and inches, SUPPLY AIR unless otherwise specified. They are subject to change without notice. Certified dimensions will be provided upon request. OUTDOOR AIR (Discharge) CLEARANCES (mm / in.) OUTDOOR AIR Front 914 / 36 (Economizer) 610 / 24 (Less Economizer) Back 1245 / 49 (Wi
Краткое содержание страницы № 16
530.26-TG3YI UNIT DIMENSIONS - D*CG180 & 240 UNITS 1235 (48-5/8") (180) 1337 (52-5/8") (240) 3181 (125-1/4") (180) 3561 (136-1/4") (240) 616 (24-1/4") (180) 895 (35-1/4") (240) RETURN AIR SUPPLY AIR OUTDOOR AIR (Discharge) OUTDOOR AIR (Economizer) CLEARANCES (mm / in. ) 1 Front 914 / 36 All dimensions are in millimeters and inches, 610 / 24 (Less Economizer) Back unless otherwise specified. They are subject to 1245 / 49 (With Economizer) change without notice. Certified dimensions 610 / 24 (Less
Краткое содержание страницы № 17
530.26-TG3YI UNIT DIMENSIONS - D*CE / D*CG180 & 240 UNITS (Cont’d.) DUCT COVERS - Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For downflow duct applications: 1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers. 2. Remove and discard the bottom duct covers. 3. Replace the side supply and return air compartment panels. For sideflo
Краткое содержание страницы № 18
530.26-TG3YI ROOF CURB DIMENSIONS - D*CE / D*CG180 & 240 UNITS 362 (14-1/4") (180) 641 (25-1/4") (240) 2927 (115-1/4") (180) 3207 (126-1/4") (240) * Supply and Return Air (including duct suppport rails) as shown, are typical for downflow duct applications. For location of sideflow duct applications (on back of unit), refer to Unit Dimension details. ROOF CURB BENEFITS UNIT AND CURB APPLICATION 2927 (115-1/4") (180) 3207 (126-1/4") (240) TYPICAL APPLICATIONS 18 Unitary Products Group
Краткое содержание страницы № 19
530.26-TG3YI TYPICAL APPLICATIONS - Cont’d. ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN) Unitary Products Group 19
Краткое содержание страницы № 20
P.O. Box 1592, York, Pennsylvania USA 17405-1592 530.26TG3YI Subject to change without notice. Printed in U.S.A Supersedes: Nothing Copyright by York International Corporation 1994. All Rights Reserved.