Краткое содержание страницы № 1
251934-YTG-J-0910
Description
TECHNICAL GUIDE
®
YORK ZJ Series Sunline Magnum™ /ZR Series
MagnaDRY™/ZF Series Sunline™ units are convertible single
package high efficiency rooftops. All models have independent
refrigeration circuits for efficient part load operation.
Although the units are primarily designed for curb mounting on
a roof, they can also be slab-mounted at ground level or set on
steel beams above a finished roof.
All ZJ/ZR/ZF units are self-contained and assembled on rigid
Краткое содержание страницы № 2
251934-YTG-J-0910 Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . .
Краткое содержание страницы № 3
251934-YTG-J-0910 Component Location (ZJ shown) ® Simplicity Control Board Slide In/ Plug In Internal Economizer (Optional) 110 Volt Convenience Outlet (“Powered” or 2” Disposable Filters “Non-Powered” Optional) (4” Filters Optional) Disconnect Location (Optional Disconnect Switch) Bottom Power and Control Wiring Entry Power Ventor Motor Electric Heater Location (Optional Electric/Electric Units) Location of VFD (Optional) Location of VFD Bypass (Optional) Belt Drive Copper Tube/ Blower Motor T
Краткое содержание страницы № 4
251934-YTG-J-0910 Nomenclature 15-25 Ton Sunline Magnum™ Model Number Nomenclature Z J 180 N24 A 2 A AA 1 0 1 2 4 A Product Category Product Style Z = A/C, Single Pkg., R-410A A = Style A Product Identifier Configuration Options (not required for all units) These four digits will not be assigned until a quote is requested, or an order placed. J = 11.0+ EER A/C SS Drain Pan R = 90.1 w/Reheat CPC Controller, DFS, APS F = 10 thru 11 EER A/C Johnson Controller UNT 1126 (N2 protocol), DFS, APS Nomina
Краткое содержание страницы № 5
251934-YTG-J-0910 the fixed outdoor air intake assembly should be mounted Features and Benefits over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct. Standard Features • System Protection - Suction line freezestats are supplied • High Efficiency - High efficiency units reach as high as on all units to protect against loss of charge and coil frosting 12.4 EER. Gas/electric units have electronic spark ignition when the economizer ope
Краткое содержание страницы № 6
251934-YTG-J-0910 valve, if applicable, and the temperature limit switch on The rainhood is painted to match the basic unit and must gas and electric heat units. The unit control board will be field-assembled before installing. alarm on ignition failures, compressor lockouts and • BAS-Ready Economizer - Includes a slide-in / plug-in repeated limit switch trips. damper assembly with fully modulating spring-return • Nuisance Trip Protection and Strikes - To prevent motor actuator with zero to
Краткое содержание страницы № 7
251934-YTG-J-0910 pressure in the supply duct. A pressure transducer and between heavy gauge steel sheets to form a durable, rigid VAV control board are mounted inside the control box. casing to withstand higher working pressures and impact The drive comes completely wired and pre-programmed forces. The heavy-duty construction provides excellent from the factory. acoustic and thermal insulation and eliminates erosion of insulation material and contamination of the air stream. An optional, f
Краткое содержание страницы № 8
251934-YTG-J-0910 Control Options • Motorized Outdoor Air Intake Damper - Includes a slide-in / plug-in damper assembly with a 2-position, • BAS - Building Automation System Controls spring return motor actuator which opens to some pre-set (available on two-system cooling product only). position whenever the supply air blower is operating and ® Simplicity™ INTELLI-Comfort™ Control - The York will drive fully closed when the blower unit shuts down. Simplicity™ INTELLI-CO sensor to perform D
Краткое содержание страницы № 9
251934-YTG-J-0910 • Phase Monitors - Designed to prevent unit damage. The unit shall have a minimum EER rating of 12.1. The 20 ton unit phase monitor will shut the unit down in an out-of phase shall have a minimum EER rating of 11.6. The 25 ton unit shall condition. have a minimum EER rating of 10.4. ZR units shall be factory-assembled, single packaged, ZR***N Guide Specifications Electric Cooling/Gas Heat, ZR***C/E Electric Cooling/Optional Electric Heat, designed for outdoor mounted insta
Краткое содержание страницы № 10
251934-YTG-J-0910 the service factor. Units shall be designed not to operate above f. Hot gas bypass option shall be factory-installed on service factor. Fan wheel shall be double-inlet type with compressor #1 discharge line to provide cooling in low- forward-curved blades, dynamically balanced to operate load applications. HGBP shall be a standard feature on smoothly throughout the entire range of operation. Airflow VAV models and an optional feature on CV models. design shall be constant air v
Краткое содержание страницы № 11
251934-YTG-J-0910 Electric Heating (ZJ/ZR/ZF***C/E Models) position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not Nickel chromium electric heating elements shall be provided as exceed 2% when dampers are fully closed and operating required by the application with 1 or 2 stage control, as against a pressure differential of 0.5 IWG. A unit-mounted required, from 13.5 KW to 72 KW capacities. The heating potentiometer shall be provided t
Краткое содержание страницы № 12
251934-YTG-J-0910 • Dirty Filter Switch 3 and SOL 2, and energizes SOL 1, engaging circuit # 1, resulting in circuit #1 cooling mode operation. • Double Wall • Phase Monitor When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and engages circuit •Coil Guard #1 and circuit #2 in the cooling mode. • Powered GFI Convenience Outlet • Non-powered GFI Convenience Outlet Indoor blower operation is initiated upon a call for first stage ® cooling, sec
Краткое содержание страницы № 13
251934-YTG-J-0910 Reheat Control Board R Y1 P4 Y2 K1 G W1 K2 W2 OCC K4 C K3 COM ` P6 P5 P3 HGRR HGR HUM DEHUMIDISTAT MODE HARNESS SELECTION CONNECTION JUMPER Reheat Controls - Part 1 Johnson Controls Unitary Products 13
Краткое содержание страницы № 14
251934-YTG-J-0910 UCB RHB UNIT CONTROL REHEAT CONTROL BOARD BOARD HUM HUMIDIFY TERMINAL RHR REHEAT RELAY RHTB REHEAT TERMINAL BLOCK Reheat Controls - Part 2 REHEAT SOLENOID 1 REHEAT REHEAT SOLENOID 3 SOLENOID 2 UCB UNIT CONTROL BOARD RHB REHEAT CONTROL BOARD 14 Johnson Controls Unitary Products
Краткое содержание страницы № 15
251934-YTG-J-0910 Physical Data ZJ180-300 Physical Data Models Component ZJ180 ZJ210 ZJ240 ZJ300 Nominal Tonnage 15 17.5 20 25 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 183500 213700 242000 312000 ARI net capacity (Btu) 178500 206000 235000 295000 EER 12.4 12.1 11.6 10.4 SEER - - - - IPLV 13.9 13.2 12.9 10.6 Nominal CFM 6000 7000 8000 10000 System power (KW) 14.40 17.10 20.10 28.50 Refrigerant type R-410a R-410a R-410a R-410a Refrigerant charge (lb-oz) System 1 12-8 12-8 12-0 1
Краткое содержание страницы № 16
251934-YTG-J-0910 ZJ180-300 Physical Data (Continued) Models Component ZJ180 ZJ210 ZJ240 ZJ300 Nominal Tonnage 15 17.5 20 25 CONDENSER FAN DATA Quantity 4 4 4 4 Fan diameter (Inch) 24 24 30 30 Type Prop Prop Prop Prop Drive type Direct Direct Direct Direct No. speeds 1 1 1 1 Number of motors 2 2 2 2 Motor HP each 1/3 1/3 1/3 1/3 RPM 850 850 870 870 Nominal total CFM 4000 4000 5000 5000 BELT DRIVE EVAP FAN DATA Quantity 1 1 1 1 Fan Size (Inch) 15 X 15 18 X 15 18 X 15 18 X 15 Type Centrifugal Cen
Краткое содержание страницы № 17
251934-YTG-J-0910 ZR180-300 Physical Data Models Component ZR180 ZR240 ZR300 Nominal Tonnage 15 20 25 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 189 243 303 ARI net capacity (Btu) 183 235 288 EER 11.6 12.1 10.5 SEER - - - IPLV 12.4 13.8 11.3 Nominal CFM 6000 8000 10000 System power (KW) 14.40 20.10 28.50 Refrigerant type R-410a R-410a R-410a Refrigerant charge (lb-oz) System 1 22 24 25 System 2 22 24 24-8 ARI HEATING PERFORMANCE Heating model 24 32 24 32 24 32 Heat input (K Btu)
Краткое содержание страницы № 18
251934-YTG-J-0910 ZR180-300 Physical Data (Continued) Models Component ZR180 ZR240 ZR300 Nominal Tonnage 15 20 25 CONDENSER FAN DATA Quantity 4 4 4 Fan diameter (Inch) 24 30 30 Type Prop Prop Prop Drive type Direct Direct Direct No. speeds 1 1 1 Number of motors 4 4 4 Motor HP each 1/3 3/4 3/4 RPM 850 870 870 Nominal total CFM 4000 5000 5000 BELT DRIVE EVAP FAN DATA Quantity 1 1 1 Fan Size (Inch) 15 X 15 18 X 15 18 X 15 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VP65 1VP65 1VP60 1VP
Краткое содержание страницы № 19
251934-YTG-J-0910 ZF180-300 Physical Data Models Component ZF180 ZF210 ZF240 ZF300 Nominal Tonnage 15 17.5 20 25 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (K Btu) 181 208 259 279 ARI net capacity (K Btu) 174 203 250 270 EER 11.0 11.0 10.0 10.0 SEER - - - - IPLV 12.9 12.77 11.5 11 Nominal CFM 6000 7000 8000 10000 System power (KW) 15.8 18.5 25.0 27.0 Refrigerant type R-410a R-410a R-410a R-410a Refrigerant charge (lb-oz) System 1 20-8 23-8 22 22 System 2 20-8 23-8 23 23-4 ARI HEATING
Краткое содержание страницы № 20
251934-YTG-J-0910 ZF180-300 Physical Data (Continued) Models Component ZF180 ZF210 ZF240 ZF300 Nominal Tonnage 15 17.5 20 25 CONDENSER FAN DATA Quantity 2 2 2 2 Fan diameter (Inch) 24 24 30 30 Type Prop Prop Prop Prop Drive type Direct Direct Direct Direct No. speeds 1 1 1 1 Number of motors 2 2 2 2 Motor HP each 1.25 1.25 1.25 1.25 RPM 1140 1140 1140 1140 Nominal total CFM 5765 7000 7000 7000 BELT DRIVE EVAP FAN DATA Quantity 1 1 1 1 Fan Size (Inch) 15 X 15 18 X 15 18 X 15 18 X 15 Type Centrif