FILE NO. A08-007
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
INDOOR UNIT
RAV-SM404SDT-E
RAV-SM454SDT-E
RAV-SM564SDT-E
OUTDOOR UNIT
RAV-SP404AT-E RAV-SP454AT-E
RAV-SP404ATZ-E RAV-SP454ATZ-E
RAV-SP404ATZG-E RAV-SP454ATZG-E
RAV-SP564AT-E RAV-SP804AT-E
RAV-SP564ATZ-E RAV-SP804ATZ-E
RAV-SP564ATZG-E RAV-SP804ATZG-E
R410A
PRINTED IN JAPAN, Jan., 2009 ToMo
Краткое содержание страницы № 2
Adoption of New Refrigerant This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer. WARNING Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the service person, and not for the customer. CONTENTS SAFETY CAU
Краткое содержание страницы № 3
7. REFRIGERANT R410A ............................................................................ 33 7-1. Safety During Installation/Servicing ............................................................... 33 7-2. Refrigerant Piping Installation....................................................................... 33 7-3. Tools .................................................................................................................. 37 7-4. Recharging of Refrigerant..................
Краткое содержание страницы № 4
SAFETY CAUTION The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them. [Explanation of indications] Indication Explanation Indicates contents assumed that an imminent danger causing a death or serious injury of DANGER the repair engineers and the third parties when an incorrect work ha
Краткое содержание страницы № 5
WARNING Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs. If the earth wire is not correctly connected, contact an electric engineer for rework. Check earth wires. Do not modify the products. Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury. Prohibition of modification. For spare parts, use those specified (∗ ∗ ∗ ∗ ∗). If unspecifi
Краткое содержание страницы № 6
WARNING After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2MΩ or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s Insulator check side. When the refrigerant gas leaks during work, execute ventilation. If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant an
Краткое содержание страницы № 7
New Refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner w
Краткое содержание страницы № 8
4. Tools 1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) 2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) 3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below show
Краткое содержание страницы № 9
1. SPECIFICATIONS 1-1. Indoor Unit 1-1-1. 4-Way Air Discharge Cassette Type Indoor unit RAV-SM564UT-E RAV-SM804UT-E Model Outdoor unit RAV-SP564AT(Z)(ZG)-E RAV-SP804AT(Z)(ZG)-E Cooling capacity (kW) 5.3 7.1 Heating capacity (kW) 5.6 8.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 6.82 – 6.25 8.72 – 7.99 Power consumption (kW) 1.47 1.86 Cooling Power factor (%) 98 97 EER 3.61 3.82 Energy efficiency class ∗ AA Electrical Running current (A) 5.61 – 5.14 8.95 – 8.2
Краткое содержание страницы № 10
1-1-2. Concealed Duct Type Indoor unit RAV-SM562BT-E RAV-SM802BT-E Model Outdoor unit RAV-SP564AT(Z)(ZG)-E RAV-SP804AT(Z)(ZG)-E Cooling capacity (kW) 5.0 7.1 Heating capacity (kW) 5.6 8.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 7.24 – 6.63 10.36 – 9.49 Power consumption (kW) 1.56 2.21 Cooling Power factor (%) 98 97 EER 3.21 3.21 Energy efficiency class* AA Electrical Running current (A) 7.19 – 6.59 10.36 – 9.49 characteristics Power consumption (kW) 1.55 2.2
Краткое содержание страницы № 11
1-1-3. Under Ceiling Type Indoor unit RAV-SM562CT-E RAV-SM802CT-E Model Outdoor unit RAV-SP564AT(Z)(ZG)-E RAV-SP804AT(Z)(ZG)-E Cooling capacity (kW) 5.0 7.1 Heating capacity (kW) 5.6 8.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 7.24 – 6.63 10.36 – 9.49 Power consumption (kW) 1.56 2.21 Cooling Power factor (%) 98 97 EER 3.21 3.21 Energy efficiency class ∗ AA Electrical Running current (A) 6.82 – 6.25 10.12 – 9.28 characteristics Power consumption (kW) 1.47 2.1
Краткое содержание страницы № 12
1-1-4. High Wall Type Indoor unit RAV-SM562KRT-E RAV-SM802KRT-E Model Outdoor unit RAV-SP564AT(Z)(ZG)-E RAV-SP804AT(Z)(ZG)-E Cooling capacity (kW) 5.0 6.9 Heating capacity (kW) 5.6 8.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 7.24 – 6.63 11.25 – 10.31 Power consumption (kW) 1.56 2.40 Cooling Power factor (%) 98 97 EER 3.21 2.88 Energy efficiency class ∗ AC Electrical Running current (A) 7.19 – 6.59 11.25 – 10.31 characteristics Power consumption (kW) 1.55 2.4
Краткое содержание страницы № 13
1-1-5. Compact 4-Way Air Discharge Cassette Type (600 × 600) Indoor unit RAV-SM 402MUT-E 452MUT-E 562MUT-E Model Outdoor unit RAV-SP 404AT(Z)(ZG)-E 454AT(Z)(ZG)-E 564AT(Z)(ZG)-E Cooling capacity (kW) 3.6 4.0 5.0 Heating capacity (kW) 4.0 4.5 5.6 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 5.05 – 4.63 5.82 – 5.33 7.24 – 6.63 Power consumption (kW) 1.00 1.19 1.56 Cooling Power factor (%) 90 93 98 EER 3.60 3.36 3.21 Energy efficiency class ∗ AAA Electrical Running
Краткое содержание страницы № 14
Indoor unit 1 RAV-SM402MUT-E Model Indoor unit 2 RAV-SM402MUT-E Outdoor unit RAV-SP804AT(Z)(ZG)-E Cooling capacity (kW) 7.1 Heating capacity (kW) 8.0 Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 10.36 – 9.49 Power consumption (kW) 2.21 Cooling Power factor (%) 97 EER 3.21 Energy efficiency class ∗ A Electrical characteristics Running current (A) 10.12 – 9.28 Power consumption (kW) 2.16 Heating Power factor (%) 97 COP 3.70 Energy efficiency class ∗ A Fa
Краткое содержание страницы № 15
1-1-6. Slim Duct Type Indoor unit RAV-SM 404SDT-E 454SDT-E 564SDT-E Model Outdoor unit RAV-SP 404AT(Z)(ZG)-E 454AT(Z)(ZG)-E 564AT(Z)(ZG)-E Cooling capacity (kW) 3.6 4.0 5.0 Heating capacity (kW) 4.0 4.5 5.6 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 5.20 – 4.77 5.87 – 5.38 7.24 – 6.63 Power consumption (kW) 1.03 1.20 1.56 Cooling Power factor (%) 90 93 98 EER 3.50 3.33 3.21 Energy efficiency class ∗ AAA Electrical Running current (A) 4.94 – 4.53 5.62 – 5.15 6.6
Краткое содержание страницы № 16
Indoor unit 1 RAV-SM404SDT-E Model Indoor unit 2 RAV-SM404SDT-E Outdoor unit RAV-SP804AT(Z)(ZG)-E Cooling capacity (kW) 7.1 Heating capacity (kW) 8.0 Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 10.36 – 9.49 Power consumption (kW) 2.21 Cooling Power factor (%) 97 EER 3.21 Energy efficiency class ∗ A Electrical characteristics Running current (A) 10.12 – 9.28 Power consumption (kW) 2.16 Heating Power factor (%) 97 COP 3.70 Energy efficiency class ∗ A Fa
Краткое содержание страницы № 17
1-2. Outdoor Unit Model name Outdoor unit RAV-SP 404AT(Z)(ZG)-E 454AT(Z)(ZG)-E 564AT(Z)(ZG)-E 804AT(Z)(ZG)-E 1 phase 230V (220 – 240V) 50Hz Power supply (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) 1.1 1.1 1.1 2.0 Pole 44 4 4 Refrigerant charged (kg) 1.0 1.0 1.4 2.1 Refrigerant control Pulse motor valve Standard length (m) 7.5 7.5 7.5 7.5 Min. length (m) 55 5 5 Max. total length (m) 30 30 50 50 Inter connecting Additional refri
Краткое содержание страницы № 18
1-3. Operation Characteristic Curve Operation characteristic curve RAV-SP564AT-E, RAV-SP564ATZ-E, RAV-SP564ATZG-E 10 16 9 14 RAV-SM562BT, CT, KRT, MUT-E, RAV-SM562BT, CT, KRT, MUT-E, RAV-SM562BT, CT, KRT, MUT-E, RAV-SM562BT, CT, KRT, MUT-E, RAV-SM564SDT-E RAV-SM564SDT-E RAV-SM564SDT-E RAV-SM564SDT-E 8 12 7 10 6 5 8 4 6 RAV-SM564UT-E RAV-SM564UT-E RAV-SM564UT-E RAV-SM564UT-E 3 4 Conditions • Conditions 2 Indoor : DB20˚C Indoor : DB27˚C/WB19˚C Outd
Краткое содержание страницы № 19
RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E 14 16 14 12 SP45 SP45 12 SP45 SP45 10 10 8 8 SP40 SP40 6 6 SP40 SP40 4 4 Conditions Conditions Indoor : DB27˚C/WB19˚C Indoor : DB20˚C Outdoor : DB35˚C Outdoor : DB7˚C/WB6˚C 2 2 Air flow : High Air flow : High Pipe length : 7.5m Pipe length : 7.5m 230V 230V 0 0 0 20 40 50 60708090 100 0 2040608090100 120 Compressor speed (rps) Compressor speed (rps) Capacity variation ratio acco
Краткое содержание страницы № 20
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS) 2-1. Indoor Unit RAV-SM404SDT-E, RAV-SM454SDT-E, RAV-SM564SDT-E 845 21 803 (inside) 21 Refrigerant piping 103 Air filter 31 805 59 80 910 33 163 Fresh air inlet Drain-up port (knock-out hole) Hung-up plate – 20 – Ø92 80 168 120 168 19 20 (inside) 21 21 67 511 67 57 645 210 40 359 372 422 502 4-Ø4