IPGSM-DP Commercial Fire Communicator
RADIO TROUBLE
IPGSM-DP
IPGSM-DP
Commercial Fire Communicator
Commercial Fire Communicator
I In ns st ta alllla at tiio on n a an nd d S Se et tu up p G Gu uiid de e
800-08074 1/11 Rev. A
Краткое содержание страницы № 2
Contents General Information .......................................................................................................................1 Package Contents .......................................................................................................................1 Compatible Fire Panels ..............................................................................................................1 Operation..............................................................
Краткое содержание страницы № 3
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide General Information The IPGSM-DP Commercial Fire Communicator (henceforth referred to as IPGSM-DP) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the Internet as its primary reporting path, and uses a GSM cellular reporting path as a backup. In addition, this communicator utilizes a sophisticated power module (PowerBoost1) that monitors and reports
Краткое содержание страницы № 4
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide STEP 1 – Activate the SIM and Setup the Customer Account The communicator requires a subscriber account (customer account) to be setup with AlarmNet Direct. This is accomplished by registering the communicator's iGSM communications module with AlarmNet. Registering, enables the fire panel to send reports. To setup the customer account you will need to contact the central monitoring station to get account information,
Краткое содержание страницы № 5
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide STEP 3 – Determine the Signal Strength and Select a Location IMPORTANT - Do Not mount this device outdoors. RF Exposure Warning - The antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be collocated or operating in con- junction with any other antenna or transmitter. When choosing a suitable mounting location, understand that signal st
Краткое содержание страницы № 6
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide 3. Install the two plastic mounting rails for the LED Display board. They simply snap into the back plate holes. 4. Connect the LED Display board to its connector, then slide the board into the mounting rails. (Yellow LED and Buzzer are on top.) 5. Carefully remove the packaging material that surrounds the PowerBoost1. 6. Mount the PowerBoost1 on the three unused standoffs. Use the plastic screw (prevents shorting)
Краткое содержание страницы № 7
IBS GPRS M1 M0 RSSI Data Out IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide ANTENNA WALL OUTLET BOX (K14358) TRANSFORMER (N8167) NUT, WASHER ANTENNA MOUNTING ADAPTER CABINET DOOR ON 15 2 3 4 RED GREEN Dialer Capture Module FOR EXTERNAL ANTENNA 50 OHM MMCX ONLY 7720P PROGRAMMER PORT NOT FOR TELEPHONE SERVICE USE! PRIMARY POWER: 9 - 16.5 VAC BATTERY CURRENT: 900mA PEAK, 70mA STANDBY TO Facility BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP FCC:XXXXXXXXXX IC: YYYYYYYYYY Gr
Краткое содержание страницы № 8
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide STEP 5 – Program the Communications Module You must use the 7720P Programming tool to program the IPGSM-DP. When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [Space] key to scroll through a list of options. (no display) 1. Connect the 77
Краткое содержание страницы № 9
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded. Note: If critical configuration changes were made, such as the
Краткое содержание страницы № 10
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide IPGSM-DP Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DP, and Telco 2 is used by the IPGSM-DP to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if there are no faults in the iGSM Communications module. Fault Condition Indication to Fire Panel PowerBoost1 fault Telco 2 is cut. iGSM Communic
Краткое содержание страницы № 11
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide Violet Note: If a wire pulled out of the LED Board Connector LED Board Black refer to the diagram on right and reinsert wire, ensuring Connector White the connector pin is locked in. Wires NC Red NC Brown Yellow Gray PowerBoost1 Module Information LED Indicator STATUS AC AC power available. (green) ACTIVE Cyclical flashing – normal communications. (green) Repetition of 3 flashes – loss of communication
Краткое содержание страницы № 12
IBS GPRS M1 M0 RSSI IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide iGSM Communications Module Information ON – NOT registered with AlarmNet. GRN OFF – Registered with AlarmNet. FAST BLINK – Download session with Compass in progress. PRIMARY POWER: 9 - 16.5 VAC SLOW BLINK – In unison with yellow LED, CURRENT: 900mA PEAK, 70mA STANDBY 7720P BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP Programmer registration in progress. Port
Краткое содержание страницы № 13
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide RF Specifications Transmission Transmit Receive Receive Number Channel Duplex Frequency Power Frequency of Separation Band Sensitivity Spacing Channels (MHz) (dBm) (MHz) (kHz) (dBm) (MHz) GSM 850 824-849 33 869-894 -107 124 200 45 GSM 900 890-915 33 935-960 -107 124 200 45 GSM 1800 1710-1785 30 1805-1880 -106 374 200 95 GSM 1900 1850-1910 30 1930-1990 -105.5 299 200 80 IPGSM-DP Specifications ITEM SPEC
Краткое содержание страницы № 14
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide NOTES – 12 –
Краткое содержание страницы № 15
IBS GPRS M1 M0 RSSI Wiring Diagram The wiring diagram below is depicted for point-to-point electrical connection checks used for troubleshooting or component replacement. It is not intended to show the physical routing of wires. When replacing a wire or component, ensure the wire is routed in the same manner as the original factory wire. WALL OUTLET TRANSFORMER BOX (K14358) ANTENNA (N8167) (Buzzer) OPTIONAL CABINET WHT (LO BATT) TAMPER SWITCH CABINET DOOR LED Display RADIO PowerBoost1 Bu
Краткое содержание страницы № 16
FCC STATEMENT Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio