Краткое содержание страницы № 1
Installation,
Start-Up and
Operator’s Manual
Manual de Instalación,
Arranque y Operario
Manuel d'Installation,
Démarrage et Utilisation
Questions? Help is just a moment away!
Preguntas? La ayuda es justa un momento
lejos!
Vous avez des questions? Vous n'avez pas
besoin d'aller loin pour trouver de l'aide!
Call: Home Standby Generator Helpline
Llamada: Línea Directa de Reserva de Hogar
Appelez: Ligne Directe de Secours À la
Maison - 1-800-743-4115 M-F 8-5 CT
Web: www.briggspowerproducts.com
Home
Краткое содержание страницы № 2
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual TABLE OF CONTENTS TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Grounding the Generator . . . . . . . . . . . . . . . . . . . . . 16 IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . 3-4 Utility Control Circuit Connection . . . . . . . . . . . . . 16 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . 5 Remote LED Plate . . . . . . . . . . . . . . .
Краткое содержание страницы № 3
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual SAVE THESE INSTRUCTIONS IMPORTANT SAFETY DANGER Storage batteries give off explosive hydrogen gas INSTRUCTIONS during recharging. Slightest spark will ignite hydrogen and cause The safety alert symbol ( ) is used with a signal word explosion. (DANGER, CAUTION,WARNING), a pictorial and/or a Battery electrolyte fluid contains acid and is safety message to alert you to hazards. DANGER indicates extr
Краткое содержание страницы № 4
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual WARNING CAUTION Generator produces powerful voltage. Excessively high operating speeds increase risk of injury and damage to generator. Failure to properly ground generator can result in electrocution. Excessively low speeds impose a heavy load. Failure to isolate generator from power utility DO NOT tamper with governed speed. Generator supplies can result in death or injury to electric utility
Краткое содержание страницы № 5
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual SAVE THESE CUSTOMER INSTRUCTIONS RESPONSIBILITIES Read and follow the instructions given in this manual, This manual contains important instructions that should be especially the section regarding selecting essential circuits. followed during installation and maintenance of the Follow a regular schedule in maintaining, caring for and generator and battery. using your Home Standby Generator, a
Краткое содержание страницы № 6
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual KNOW YOUR HOME STANDBY GENERATOR Read this operator’s manual and safety rules before operating your generator. Compare the illustrations with your generator to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference. Generator is shown with roof, plastic Air Cleaner Engine Label Oil Fill access door and control panel door Cap/DipStick rem
Краткое содержание страницы № 7
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual KNOW YOUR CONTROL PANEL Compare this Control Panel illustration with your generator to familiarize yourself with the location of these important controls: 15 Amp Fuse Set Exercise Switch Circuit Breaker AUTO/OFF/MANUAL Switch 15 Amp Fuse — Protects the Home Standby Generator “OFF” position turns off generator, prevents generator DC control circuits. If the fuse has melted open or was from starti
Краткое содержание страницы № 8
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual OWNER ORIENTATION WARNING Propane and Natural Gas are extremely This section provides the Home Standby Generator owner flammable and explosive. with the information necessary to achieve the most Fire or explosion can cause severe burns or satisfactory and cost effective installation possible. death. The illustrations are for typical circumstances and are The Home Standby Generator is equipped w
Краткое содержание страницы № 9
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual General Location Guidelines Shipment Contents WARNING The Home Standby Generator is supplied with: Home Standby Generator w/disconnect box Running generator gives off carbon monoxide, Pre-attached mounting pad an odorless, colorless, poison gas. One 24” flexible hook-up hose Breathing carbon monoxide can cause nausea, Installation, start-up and operator’s manual fainting or death. Insta
Краткое содержание страницы № 10
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual Essential Circuits Figure 2 — Wattage Reference Guide Running Consult with owner to clearly identify the circuits in Device Watts building that are "essential". Air Conditioner (12,000 Btu)* 1700 It is important that you understand which circuits the Air Conditioner (24,000 Btu)* 3800 owner wants to include as "Essential Circuits". Depending Air Conditioner (40,000 Btu)* 6000 on the
Краткое содержание страницы № 11
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual This rating is applicable to installations served by a Fuel Inlet Dimensions reliable normal utility source.This rating is only applicable Figure 4, below, depicts the location of the fuel piping to variable loads with an average load factor of 80% of connector. the standby rating.The standby rating is only applicable for optional standby power where the generator set Figure 4 — Generator Fuel At
Краткое содержание страницы № 12
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual Piping must be of the correct size to maintain the THE GASEOUS FUEL required supply pressures and volume flow under varying generator load conditions with all gas appliances SYSTEM connected to the fuel system turned on and operating. WARNING Use an approved pipe sealant or joint compound on all Propane and Natural Gas are extremely threaded fittings to reduce the possibility of leakage. flam
Краткое содержание страницы № 13
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual Where the formation of hydrates or ice is known to When the initial test runs are completed, the manometer is occur, piping should be protected against freezing.The removed and the port is plugged.A typical final fuel termination of hard piping should include a sediment trap connection assembly is shown in Figure 6. where condensate is not likely to freeze. Figure 6 — Completed Fuel Connections
Краткое содержание страницы № 14
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual Fuel Pipe Sizing Listed values compensate for a nominal amount of Figures 8 and 9 provide the maximum capacity of pipe in restriction from bends, fittings, etc. If an unusual number of cubic feet of gas per hour for gas pressures of 0.5 psi or fittings, bends, or other restrictions are used, please refer less and a pressure drop of 0.3 in. water column. Specific to federal and local codes. gravit
Краткое содержание страницы № 15
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual Fuel Comparison Chart Fuel Comparison Chart Physical Properties Propane Natural Gas Normal Atmospheric State Gas Gas Boiling Point (in °F): Initial -44 -259 End -44 -259 Heating Value: BTU per gallon (Net LHV*) 83,340 63,310 BTU per Gallon (Gross**) 91,547 Cubic Feet (Gas) 2,516 1,000 Density*** 36.39 57.75 Weight† 4.24 2.65 Octane Number: Research 110+ 110+ Motor 97 * LHV (
Краткое содержание страницы № 16
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual Remote Diagnostic LED Plate WIRE CONNECTIONS The light on the remote LED plate is referred to as the Diagnostic LED.The LED will stay lit indicating the generator Recommended T orque Values is in ready mode and will turn on and off in a series of blinks Torque all wire connections/fasteners to values recommended if certain faults are detected in the Home Standby in Figure 10. Suitable for copper
Краткое содержание страницы № 17
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual NOTE: With the battery installed and utility power Battery Connection available to the Automatic Transfer Switch, the battery The Home Standby Generator is supplied with a 12Volt receives a trickle charge whenever the engine is not DC,AGM type, 33 Amp-Hour, valve regulated battery. It is a running.This process may take up to 72 hours to fully sealed, lead-acid rechargeable battery. It is installe
Краткое содержание страницы № 18
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual 9. Connect an RMS AC voltmeter and a frequency meter FUEL SYSTEM SELECTION to check generator output at load side of circuit breaker.Voltage should be 230-240 Volts, frequency The engine of your Home Standby Generator is factory should be 62.0 - 62.5 Hz. calibrated to run on natural gas (NG). It may also be operated on liquid propane (LP). 10. Check generator output between one generator To confi
Краткое содержание страницы № 19
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual For example, if you press the “Set Exercise” switch on SETTING EXERCISE TIMER Sunday morning at 10:00 AM, the unit will run an exercise cycle the following Sunday at 10:00 AM (+/- 1 hour). The Home Standby Generator is equipped with an exercise timer that will start and exercise the generator once every NOTE: “Set Exercise” will only work if the unit is in the seven days. During this exercise per
Краткое содержание страницы № 20
Briggs & Stratton Power Products Home Standby Generator Installation, Start-Up and Operator’s Manual 2. With generator output supplying load, turn ON SPECIFICATIONS service disconnect or main distribution panel circuit breaker that supplies utility power to automatic Rated Maximum Power (LP*) . . . . . . . . . . . . . . . . . .7.0 kW transfer switch. Rated Maximum Load Current: 3. Automatic transfer switch will transfer loads back to at 240 Volts . . . . . . . . . . . . . . . . . . . . . . . . .