INSTALLER/CONSUMER
SAFETY INFORMATION
PLEASE READ THIS MANUAL
BEFORE INSTALLING AND
USING APPLIANCE
WARNING!
Chateau™
IF THE INFORMATION IN THIS
MANUAL IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION
Direct Vent Decorative
MAY RESULT CAUSING
PROPERTY DAMAGE, PERSONAL
Gas Appliance
INJURY OR LOSS OF LIFE.
Model: DVT38S2
FOR YOUR SAFETY
Installation and service must
be performed by a qualified
installer, service agency or
the gas supplier.
WHAT TO DO IF YOU SMELL GAS:
• Do n
Краткое содержание страницы № 2
Chateau™ Decorative Gas Appliance Table of Contents Please read the installation & operating instructions before using this appliance. Thank you and congratulations on your purchase of a CFM Corporation fireplace. IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty. Installation & Operating Instructions Important Curing/Burning Instructions ...................
Краткое содержание страницы № 3
Chateau™ Decorative Gas Appliance Installation & Operating Instructions This gas fireplace should be installed by a qualified installer in WARNING: Check with your electronics manufac- accordance with local building codes and with current CSA- turer before installing a television or other electronic B149.1 Installation codes for Gas Burning Appliances and device above this fireplace. Equipment. For USA Installations follow local codes and/or the current National Fuel Gas Code. ANSI Z223.1/NFPA
Краткое содержание страницы № 4
Chateau™ Decorative Gas Appliance Fireplace Dimensions C Finished Wall 24 ¹⁄₂” (622 mm) L 25 ����” for Flush Install 16” (406 mm) 3/4" (19mm) (649mm) I.D. Minimum Clearance to Combustibles 24���" Standard Framing C L (622mm) 10���" (267mm) Noncombustible Facing Material 3/4" NOTE: Noncombustible insula- 51���" (1299mm)* (19mm) tion may be placed behind the C Glass L facing material. 25 ����” (649mm) 9 ���" (235mm) 49���" Sides and Top (1245mm) of Surround 12 ���" (311mm) 55" 33 ���" (1399m
Краткое содержание страницы № 5
Chateau™ Decorative Gas Appliance Clearance to Combustibles Top of Unit to Ceiling ................................ 36” (914 mm) Front of Unit to Combustibles (both sides) ... 36” (914 mm) Appliance Top Standoffs .............................................. 0” (0 mm) Bottom ......................................................... 0” (0 mm) Side Standoffs ............................................. 0” (0 mm) � Back Standoffs ............................................ 0” (0 mm) � � Vent
Краткое содержание страницы № 6
Chateau™ Decorative Gas Appliance other noncombustible face finish material desired Framing and Finishing when setting the depth of the framing. NOTE: The valve box assembly must be installed in 4. Attach the fireplace nailing flanges to the frame as the same room as the fireplace. shown in Figure 4. 1. Choose the unit location. 5. The gas components are located in the control 2. The unit is shipped with four (4) nailing flanges panel assembly attached to the right side of the unit. mounted nea
Краткое содержание страницы № 7
Chateau™ Decorative Gas Appliance DVT38S2 Certified To ANSI Z21.50b-2005 / CSA 2.22b-2005 Vented Gas Fireplace High Elevations �� ��� � ��� ���� Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level. ������ ������� FP1362 For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the Fig. 7 Valve box framing. current ANSI Z223.1/NFPA 54 and/or local codes If marble, tile or any othe
Краткое содержание страницы № 8
H I O P TP TH THTP F F O O L Chateau™ Decorative Gas Appliance Always check for gas leaks with a mild Electrical Junction Box (E Units Only) soap and water solution applied with a brush no larger than 1” (25mm). Never ap- The fireplace, when installed, must be elec- ply soap and water solution with a spray trically connected and grounded in accord- bottle. Do not use an open flame for leak ance with local codes or, in the absence testing. of local
Краткое содержание страницы № 9
LO Chateau™ Decorative Gas Appliance General Venting Your fireplace is approved to be vented either through the side wall, or vertical through the roof. • Only CFM Corporation venting components spe- cifically approved and labelled for this fireplace PILOT may be used. • Venting terminals shall not be recessed into a wall or HONEYWELL IGNITION MODULE siding. 24V MV MV/VP PV GRD 24V SENSE SPARK • Horizontal venting must be installed on a level plane 1 2
Краткое содержание страницы № 10
V Operable Chateau™ Decorative Gas Appliance General Venting Information - Termination Location INSIDE CORNER DETAIL G V N H N A D E L C B ����� B V B V ������ V Fixed Operable Closed F V B M V B J X B I X V K A CFM145a VENT TERMINATION X AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED CFM145 V 1 2 Canadian Installations US Installations A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm) CFM145a deck, or balcony DV Termin Location 5/01/01 Rev. 12/05/01 B = Clearance
Краткое содержание страницы № 11
Chateau™ Decorative Gas Appliance Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors. Inside Corner Alcove Applications* Outside Corner D C C F = Combustible G = 6" (152 mm) Combustible V G 6" (152 mm) Noncombustible V E 2" (51 mm) Noncombustible O V F 2" (51 mm) Balcony - Balcony - with no side wall with perpendicular side wall E = Min. 6” (152 mm) for non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls O = 8’ (2.4 m)
Краткое содержание страницы № 12
Chateau™ Decorative Gas Appliance installed before any offset. A maximum of 20’ (6.1 m) proper sealing. Be sure to always attach straps on up- horizontal and three (3) 90° elbows may be installed per elbow to a structural framing member. with a minimum of 12’ (3.66 m) vertical section above For vertical installations, continue installing the pipe as the flue collar of the unit. Refer to Page 13, Figure 15 required until pipe is installed up through the ceiling. At for more information. thi
Краткое содержание страницы № 13
Chateau™ Decorative Gas Appliance 18” (45 cm). This does not apply if the 45° elbows Sidewall Applications are installed on the vertical part of the vent system. Since it is very important that the vent- For each 90° elbow installed in the horizontal run, ing system maintain its balance between the length of the horizontal run MUST be reduced by the combustion air intake and the flue 36” (914 mm). gas exhaust, certain limitations as to vent • The maximum number of elbow degrees in a system
Краткое содержание страницы № 14
Chateau™ Decorative Gas Appliance STEP 3 Sidewall Installation Slide the zero clearance sleeve through the wall and STEP 1 install the firestop on the inside surface of the wall. Locate vent opening on the wall. It may be necessary Secure with four (4) #8 sheet metal screws. to first position the fireplace and measure to obtain hole STEP 4 location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 19) Place fireplace into position. (Fig. 21) Measure the
Краткое содержание страницы № 15
Chateau™ Decorative Gas Appliance Sealing firestop gaps with high temperature sealant will restrict cold air being drawn in around fire- place. STEP 8 Guide the vent terminations 8” and 11” collars into their respective vent pipes. Double check that the vent pipes overlap the collars by 2” (51 mm). Secure the termina- tion to the wall with screws provided and caulk around the wall plate to weatherproof. (Fig. 24) As an alterna- tive to screwing the termination directly to the wall you may als
Краткое содержание страницы № 16
Chateau™ Decorative Gas Appliance the wall plate to weatherproof. (Fig. 25) As an alterna- Zero clearance sleeve is only required for tive to screwing the termination directly to the wall you combustible walls. may also use expanding plugs or an approved exterior construction adhesive. STEP 3 Slide the zero clearance sleeve through the wall and Installing the 38S2VDK Door install the firestop on the inside surface of the wall. When installing the DVT38S2 on an outside wall, the Secure with
Краткое содержание страницы № 17
Chateau™ Decorative Gas Appliance 2. Install the two (2) brackets, using the sheet metal Vertical Through-the-Roof screws, at the bottom right and left corners of the Applications unit. (Fig. 27) Use of Restrictor Plate for Vertical Venting Application The primary purpose for the vent restrictor is to regain flame height under certain venting conditions as outlined below. NOTE: The joints of the inner pipe (flue pipe) must be taped with 550°F or higher temperature metal adhesive tape that
Краткое содержание страницы № 18
Chateau™ Decorative Gas Appliance For vertical venting configurations that include a For LP gas venting straight vertical with 20’ (6 m) or minimum vertical rise of 12’ (3.7 m) and a maximum more, adjust the primary air to the burner housing as horizontal offset of 10’ (3 m) the 4 ¹⁄₂” restrictor plate well as the fresh air to the unit by doing the following: supplied with this unit should be used on LP unit only. 1. Remove glass, logs, glowing embers (if installed). (Fig. 31) Refer to Pag
Краткое содержание страницы № 19
Chateau™ Decorative Gas Appliance • A 2’ (610 mm) vertical section must be installed Vertical Through-the-Roof Installation before any offset. A maximum of 20’ (6.1 m) horizon- 1. Locate your fireplace. tal and three (3) 90° elbows may be installed with a minimum of 12’ (3.66 m) vertical section above the 2. Plumb to center of the (8”) flue collar from ceiling above and mark position. flue collar of the unit. (Fig. 32) 3. Cut opening equal to 14 ¹⁄₂” x 14 ¹⁄₂” (368 x 368 mm). • Up to two (2)
Краткое содержание страницы № 20
Chateau™ Decorative Gas Appliance Attic Insulation Min. Shield Nails (4 Re- 2' (610mm) quired) Attic Joist Base Flanges Ceiling FP263 Fig. 35 Attic shield installation. CFM190 Support Structure Elbow Strap FP263 Fig. 37 Minimum termination to roof clearance. MBUF 5/9/96 CFM190 If an attic is above ceiling level an AIS-SK TTR Ternim. 2' (Attic Insulation Shield) must be installed. Elbow Strap 1/25/02 sta (must be tight) The enlarged ends of the vent section always face downward. Ceilin