Краткое содержание страницы № 1
Краткое содержание страницы № 2
TABLE OF CONTENTS WARNING: Improper installation, Specifications ............................................................... Page 3 adjustment, alteration, service or maintenance can cause Rules for safe operation ............................................. Page 5 injury or property damage. Refer to this manual. For Locating the Heater .................................................... Page 5 assistance or additional information consult a qualified Combustion Air Requirements ...........
Краткое содержание страницы № 3
Principle of Operation: 425 EF LP and 425 EF NG Specifications When a hot water faucet is opened, the flow of water through 425EF NG 425 EF LP the heater causes the gas valve to open. At the same time a microswitch is activated which sends a spark to the pilot. max. 130 000 Btu/hr 125 000 Btu/hr Gas input The flame sensor confirms that the pilot has been lighted min. 28 000 Btu/hr 28 000 Btu/hr and allows the first two burners to ignite. The flame sensor confirms correct activation and all burne
Краткое содержание страницы № 4
Краткое содержание страницы № 5
The heater may still operate even when improperly vented. GENERAL RULES TO FOLLOW It will, however, be less efficient and could eventually damage FOR SAFE OPERATION the heater. It could even result in human sickness or death due to oxygen deprivation and carbon monoxide poisoning. 1. You should follow these instructions when you install your Before installing the unit, be certain you have the correct heater. In the United States: The installation must conform heater for your type of Gas – Propan
Краткое содержание страницы № 6
Appliances located in confined spaces: The confined space COMBUSTION AIR REQUIREMENTS must be provided with two permanent openings, one The 425 EF water heater holds cold water in its copper commencing within 12 inches of the top and one heat exchanger and brass water valve when not in use. commencing within 12 inches of the bottom of the enclosure. Because of this, any cold air that comes in through the Each opening must have a minimum free area of one square unit’s vent pipe is capable of free
Краткое содержание страницы № 7
The incandescent particle tray (shipped loose in the carton MOUNTING INSTALLATION with the water heater) must be attached at the bottom of the water heater front cover at the time of installation. Use The 425 EF is design certified for mounting on a wall. the screws provided. See figure 3. Secure the two L shaped hooks, which are provided with heater, to a wall surface. Place them 13 ¼” apart as shown in Fig 2. Do not install this appliance on a carpeted wall or over floor covering which is com
Краткое содержание страницы № 8
feet (4.6 m) with two 90-degree elbows. Subtract 5 feet from the total vent length for each additional 90-degree VENTING elbow used. No more than four 90-degree elbows may be used. Any short vertical portion of vent pipe used in the vent system shall be considered part of the allowable 15 WARNING: Do not reduce the vent pipe size and feet (4.6 m) maximum run. Support the vent run at 4 foot do not common vent with any other vented appliance or intervals with overhead hangers. Horizontal sections
Краткое содержание страницы № 9
4”single wall venting only. Use stainless steel (AL29-4C) or galvanized pipe of 26 minimum gauge must be used. Each connection must be properly sealed. Approved Vent Terminal (FXHOOD or other approved terminal) The FXHOOD is design approved with the 425 EF and has a built in back draft flapper to prevent negative air from freezing the 425 EF – see Fig. 5 for restrictions in location of vent terminal. HORIZONTAL SIDE WALL * Maximum 15 feet with 2 elbows. Deduct 5 feet for each additional elbow.
Краткое содержание страницы № 10
SOFFIT 7’ MINIMUM ABOVE PUBLIC WALKWAY The approved vent terminal must be installed so that flue gases will not jeopardize people, overheat combustible structures or enter into buildings, and so that proper clearances are maintained (See Fig 5). a) The vent terminal shall not be less than 7 feet above a public walkway. b) The vent terminal shall terminate at least 3 feet above any (mechanical) air inlet within 10 feet. c) The vent terminal shall not be within a 6-foot radius from a gas meter or
Краткое содержание страницы № 11
GAS LINE SIZING -It is strongly recommended that the Natural Gas pipe GAS CONNECTIONS be Black Iron pipe the entire distance from the outside meter to the inlet of the 425 EF regulator. 1/2” Black Iron pipe up to 10 feet, 3/4” Black Iron pipe up to 40 feet and 1” Black Iron pipe up to 125 feet distances. Flex line tubing NOTE: The 425 EF is supplied with a gas pressure is NOT recommended, but if used then oversize it. regulator that must be installed on the heater before -It is strongly recommen
Краткое содержание страницы № 12
GAS PIPING, CONNECTIONS Before connecting the gas supply, check the rating plate on the right side of the front cover to be sure that the heater is rated for the same gas to which it will be connected. In the United States: The installation must conform with local codes or, in the absence of local codes, the National Fuel Gas Code ANSI Z223.1/NFPA 54. In Canada: The Installation should conform with CGA B149 INSTALLATION CODES and /or local installation codes. GAS LINE SIZING FOR NATURAL GAS Foll
Краткое содержание страницы № 13
Connecting the pressure relief valve (PRV) WATER CONNECTIONS The listed pressure relief valve supplied with the heater must be installed at the time of installation. Should a discharge line be added to the PRV no valve is to be placed between the PRV and the heater. No reducing coupling or other Install the heater centrally in the building if possible and restriction may be installed in the discharge line. The make hot water piping runs as short as possible When facing discharge line must be ins
Краткое содержание страницы № 14
Краткое содержание страницы № 15
OPERATING INSTRUCTIONS 6. Turn the hot water faucet on to the minimum flow required to activate the heater. The automatic ignition system first Before operating the heater, make sure that the system is ignites the safety pilot burner which then ignites the main filled with water. burner in about 4 seconds. The power exhaust will then activate. Open the cold water inlet supply to the heater fully. 7. The pilot flame will extinguish 10-30 seconds after the Open a hot water faucet to permit the wat
Краткое содержание страницы № 16
140° and 95°F at various flow rates between 2.0 and 4.0 Water Valve (Part # 8707002802): The water valve on gallons per minute. The position you select on the this heater should be serviced periodically. Lubricate temperature selector dial will depend on the temperature of component #36 on page 21 with a small amount of silicon, the incoming water (50°F is average in the U.S.). In warm faucet or lithium grease every two years to keep its o rings weather regions where the incoming cold water is
Краткое содержание страницы № 17
3. Water flow is not sufficient to activate heater. Water flow rate at faucet is below minimum flow needed to activate heater. When temperature adjustment knob is turned all the way clockwise, the model 425 EF requires 1/2 gallon per minute flow to activate the heater. As a reference, this is a flow which would fill a quart jar in 30 seconds. If the temperature adjustment knob is turned fully counterclockwise, a flow rate of 1.1 gallons/minute is required to activate the heater. 4. Bad fuse Chec
Краткое содержание страницы № 18
PILOT SPARKS CONTINUOUSLY WITH NO WATER Mineral deposits can eventually (3-5 years in hard water RUNNING areas) corrode the water valve parts to a point where they will need replacing. Any sign of moisture at the bleed hole 1. Microswitch needs adjustment is a sign that the water valve needs to be replaced If no water is running, but pilot electrode continuously sparks, immediately. the microswitch screw to the water valve needs adjustment. See Figure 14. 10. Poor circuit connections at the ECO
Краткое содержание страницы № 19
WATER IS TOO HOT HOT WATER TEMPERATURE FLUCTUATES / UNIT DEACTIVATED 1. Temperature Selection too high 1. Unbalanced pressure in waterlines Turn the temperature adjustment knob counter-clockwise The added restriction caused by the 425 EF in the hot water (to the left) to lower the maximum water temperature. system can result in uneven pressures between the cold Note: This will increase the activation flow rate. and the hot. In such cases when mixing cold water at the 2. Inlet water temperature i
Краткое содержание страницы № 20
Fig. 15 - Diagram of 425 EF 13 1 3 2 4 5 6 9 10 7 8 11 14 12 6 720 606 601-12.1AL 1. Heat exchanger 7. electric control box 8. Power cord 2. Pilot assembly 9. on/off switch 3. Burner manifold gas 10. Temperature adjustment selector pressure test nipple 4. Main gas burner 11. Microswitch 5. Pilot gas tubing 12. Gas inlet gas pressure test nipple 13. Exhaust Fan 6. Gas valve 14. Flexible hot outlet 20 6 720 607 017