PACKAGE HEAT PUMP UNITS
FORM NO. P11-763 REV. 1
Supersedes Form No. P11-763
RJNA- HIGH EFFICIENCY SERIES
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
*Unit shown with
optional louver
panels installed.
ISO 9001:2000
“CERTIFIED UNDER THE
A.R.I. CERTIFICATION
PROGRAM—A.R.I.
STANDARD 240”
Краткое содержание страницы № 2
TABLE OF CONTENTS Introduction ..................................................................................................3-4 Model Identification Options............................................................................5-6 General Data RJNA- Series ..........................................................................................7-13 General Data Notes ........................................................................................14 Performance Data RJNA- Serie
Краткое содержание страницы № 3
INTRODUCTION These quality features are included in the Rheem Outdoor Package Heat Pumps Control Box Access Compressor Access Blower Access Optional Electric Heater Kit Evaporator Coil/Filter Access 3
Краткое содержание страницы № 4
INTRODUCTION INTRODUCTION ENGINEERING FEATURES RJNA- Series Package Heat Pumps ® ® 1. All models feature Copeland Scroll compressors offering maximum reliability, efficiency, and quiet operation. 2. One-piece top over the indoor section with drip lip, drawn painted base pan, and 1" [25.4 mm] raised flanges for supply/return air connections provides superior water management. 3. Convertible horizontal and vertical airflow design allows maximum field flexibility and minimizes inventory requirement
Краткое содержание страницы № 5
MODEL IDENTIFICATION—RJNA- SERIES R J NA—A036 JK 000 Electric Heat 000 = No Resistance Heat 010 = 10 kW Resistance Heat 015 = 15 kW Resistance Heat 020 = 20 kW Resistance Heat Drive Package K = Direct Drive L = Belt Drive M = Belt Drive—High Static Electrical Designation J = 208-230 V, 1 PH, 60 Hz C = 208-230 V, 3 PH, 60 Hz D = 460 V, 3 PH, 60 Hz Nominal Cooling Capacity (BTUH) [kW] 036 = 36,000 [10.55] 042 = 42,000 [12.31] 048 = 48,000 [14.07] 060 = 60,000 [17.58] Future Technical Variations D
Краткое содержание страницы № 6
OPTIONS—RJNA- SERIES FACTORY INSTALLED OPTION CODES FOR RJNA (3-5 Ton) [10.6-17.6 kW] (A036, A042, A048, A060) Low Ambient Reduced Height Option Code Hail Guard Time Delay Side Flow Baserails Freeze Stat AA No Options AD x AF x AK x AL x BD x x BS x x BX x x CK x x x Example: RJNA-A060CK000XXX (where XX is factory installed option) Example: No Options RJNA-A060CK000 Example: No Options with Factory Installed Economizer RJNA-A060CK000AAB Example: Options with Hail Guard, Low Ambient, Time Delay a
Краткое содержание страницы № 7
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series A036CK A036CL A036CM A036DK 1 Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 37,600 [11] 2 EER/SEER 11.6/13 11.6/13 11.6/13 11.6/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] ARI Net Cooling Capacity Btu [kW] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5] Net Sensible Capacity Btu [kW] 2
Краткое содержание страницы № 8
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series A036DL A036DM A036JK A042CK 1 Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 42,500 [12.5] 2 EER/SEER 11.6/13 11.6/13 11.6/13 11.8/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1400/1400 [661/661] ARI Net Cooling Capacity Btu [kW] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5] 40,500 [11.9] Net Sensible Capacity Btu [kW]
Краткое содержание страницы № 9
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series A042CL A042CM A042DK A042DL 1 Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.5] 42,500 [12.5] 42,500 [12.5] 2 EER/SEER 11.8/13 11.8/13 11.8/13 11.8/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1400/1400 [661/661] 1400/1400 [661/661] ARI Net Cooling Capacity Btu [kW] 40,500 [11.9] 40,500 [11.9] 40,500 [11.9] 40,500 [11.9] Net Sensible Capacity Bt
Краткое содержание страницы № 10
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series A042DM A042JK A048CK A048CL 1 Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.5] 49,500 [14.5] 49,500 [14.5] 2 EER/SEER 11.8/13 11.8/13 11.65/13 11.65/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1600/1600 [755/755] 1600/1600 [755/755] ARI Net Cooling Capacity Btu [kW] 40,500 [11.9] 40,500 [11.9] 47,000 [13.8] 47,000 [13.8] Net Sensible Capacity
Краткое содержание страницы № 11
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series A048CM A048DK A048DL A048DM 1 Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 49,500 [14.5] 49,500 [14.5] 49,500 [14.5] 49,500 [14.5] 2 EER/SEER 11.65/13 11.65/13 11.65/13 11.65/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] ARI Net Cooling Capacity Btu [kW] 47,000 [13.8] 47,000 [13.8] 47,000 [13.8] 47,000 [13.8] Net Sensible Capacit
Краткое содержание страницы № 12
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series A048JK A060CK A060CL A060CM 1 Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 49,500 [14.5] 63,500 [18.6] 64,000 [18.8] 64,000 [18.8] 2 EER/SEER 11.65/13 11.55/13 11.55/13 11.55/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 2000/2000 [944/944] 2000/2000 [944/944] 2000/2000 [944/944] ARI Net Cooling Capacity Btu [kW] 47,000 [13.8] 61,500 [18] 61,500 [18] 61,500 [18] Net Sensible Capacity Btu
Краткое содержание страницы № 13
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series A060DL A060DM A060JK 1 Cooling Performance Gross Cooling Capacity Btu [kW] 64,000 [18.8] 64,000 [18.8] 63,500 [18.6] 2 EER/SEER 11.55/13 11.55/13 11.55/13 Nominal CFM/ARI Rated CFM [L/s] 2000/2000 [944/944] 2000/2000 [944/944] 2000/2000 [944/944] ARI Net Cooling Capacity Btu [kW] 61,500 [18] 61,500 [18] 61,500 [18] Net Sensible Capacity Btu [kW] 43,800 [12.8] 43,800 [12.8] 43,800 [12.8] Net Latent Capacity Btu [kW
Краткое содержание страницы № 14
GENERAL DATA—RJNA- SERIES NOTES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI co
Краткое содержание страницы № 15
SYSTEMS PERFORMANCE—RJNA- SERIES COOLING PERFORMANCE DATA—RJNA-A036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453] DR ➀ .16 .13 .08 .16 .13 .08 .16 .13 .08 Total BTUH [kW] 46.4 [13.60] 44.8 [13.13] 43.1 [12.63] 43.4 [12.72] 41.9 [12.28] 40.4 [11.84] 41.1 [12.05] 39.7 [11.63] 38.2 [11.20] 75 Sens BTUH [kW] 27.9 [8.18] 25.5 [7.47] 23.1 [6.77] 33.5 [9.82
Краткое содержание страницы № 16
SYSTEMS PERFORMANCE—RJNA- SERIES COOLING PERFORMANCE DATA—RJNA-A042 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1680 [793] 1400 [661] 1120 [529] 1680 [793] 1400 [661] 1120 [529] 1680 [793] 1400 [661] 1120 [529] DR ➀ .18 .15 .11 .18 .15 .11 .18 .15 .11 Total BTUH [kW] 50.3 [14.74] 48.5 [14.21] 46.8 [13.72] 47.6 [13.95] 46.0 [13.48] 44.3 [12.98] 45.0 [13.19] 43.4 [12.72] 41.9 [12.28] 75 Sens BTUH [kW] 30.8 [9.03] 28.2 [8.26] 25.6 [7.50] 37.2 [1
Краткое содержание страницы № 17
SYSTEMS PERFORMANCE—RJNA- SERIES COOLING PERFORMANCE DATA—RJNA-A048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1920 [906] 1600 [755] 1280 [604] 1920 [906] 1600 [755] 1280 [604] 1920 [906] 1600 [755] 1280 [604] DR ➀ .18 .15 .11 .18 .15 .11 .18 .15 .11 Total BTUH [kW] 59.9 [17.55] 57.8 [16.94] 55.7 [16.32] 56.2 [16.47] 54.3 [15.91] 52.3 [15.33] 53.5 [15.68] 51.7 [15.15] 49.8 [14.59] 75 Sens BTUH [kW] 35.6 [10.43] 32.6 [9.55] 29.5 [8.65] 43.0 [
Краткое содержание страницы № 18
SYSTEMS PERFORMANCE—RJNA- SERIES COOLING PERFORMANCE DATA—RJNA-A060 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 2500 [1180] 2000 [944] 1500 [708] 2500 [1180] 2000 [944] 1500 [708] 2500 [1180] 2000 [944] 1500 [708] DR ➀ .22 .19 .15 .22 .19 .15 .22 .19 .15 Total BTUH [kW] 74.9 [21.95] 71.6 [20.98] 68.4 [20.05] 71.3 [20.90] 68.2 [19.99] 65.1 [19.08] 67.6 [19.81] 64.6 [18.93] 61.7 [18.08] 75 Sens BTUH [kW] 44.2 [12.95] 39.6 [11.61] 35.0 [10.26] 5
Краткое содержание страницы № 19
AIRFLOW PERFORMANCE—RJNA- SERIES 19 DIRECT-DRIVE BLOWER 208 AIRFLOW PERFORMANCE Nominal Manufacturer Blower Size/ CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil Factory Cooling Recommended Motor Motor External Static Pressure—Inches W.C. [kPa] Motor Capacity Air-Flow Range HP [w] & Speed Speed 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] Tons [kW] (Min/Max) CFM # of Speeds 10x10 CFM 1275 [602] 1235 [583] 1210 [571] 1181 [
Краткое содержание страницы № 20
AIRFLOW PERFORMANCE—RJNA- SERIES 20 BELT-DRIVE AIRFLOW PERFORMANCE Models RJNA-A036 [10.55 kW] & A042 [12.31 kW]—Heat Pump (13 SEER) Voltage 208/230-460—3 Phase Air Flow External Static Pressure—Inches of Water [kPa] CFM [L/s] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37] RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W 900 [425] — — — — 665 290 730 300