Краткое содержание страницы № 1
HZ432 TrueZONE
Zone Panel Professional Installation Guide
69-2198-01
Краткое содержание страницы № 2
Installation Guide Tabl E Of C ONTENTs Specifications ................................................................................................................................. ii Accessories ....................................................................................................................................1 Mounting .........................................................................................................................................2 Wiring ............
Краткое содержание страницы № 3
HZ432 TrueZONE aCCE ss Ori Es Table 1. Recommended Thermostats. Table 3. Maximum Dampers.* System Non- Programmable Ambient Temp. Maximum Damper VA per Zone Programmable 100°F (38°C) 28.8 Single- TH5110D, TH3110D, TH8110U, TH6110D, 160°F (71°C) 16.8 Stage T87N TH4110D * Use an SDCR (Slave Damper Control Relay) for addi- Multi- TH5220D TH8320U, TH8321U, tional dampers. Stage TH6220D, YTH9421C Maximum dampers per panel is limited by transformer size. Heat- TH5220D (2H/1C TH8320U (Up to 3H/2C)
Краткое содержание страницы № 4
Installation Guide MOu NTi Ng Mount the HZ432 TrueZONE panel near the HVAC SPRD BYPASS ZD SERIES equipment; locate it on a wall, stud, roof truss, or cold- DAMPER ZONE DAMPERS 1 air return. NOTE: The HZ432 TrueZONE panel can be mounted in any orientation; level it for appearance only. SUPPLY DATS DUCT (ALTERNATE LOCATION) Please refer to TrueZONE Panel Frequently Asked TrueZONE PANEL Questions form 50-9694 for operating details. MOUNTED ON TrueZONE PANEL RETURN DUCT MOUNTED ON WALL DATS (AT L
Краткое содержание страницы № 5
ZONE 1 DAMPER ZONE 2 DAMPER HZ432 TrueZONE Wiri Ng CAUTION: Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning installation. Wire entire panel before applying transformer power. Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional sys- tems, refer to this page. For heat pump systems, see pages 6 and 7. For dual fuel systems, see pages 8 and 9. Wiring must comply with applicable codes, ordin
Краткое содержание страницы № 6
Installation Guide Wiri Ng DATS DATS Connect DATS as shown. 5 M24804 C7735A1000 Fig. 7 Connect outdoor air temperature sensor OT as shown. Required for dual fuel systems; OT 6 C7089U1006 optional for other multistage systems. OUTDOOR TEMPERATURE M28207 SENSOR Fig. 8 Connect equipment as shown. 7 The DS/BK terminal is used with a variable-speed fan. HVAC 24 VOLT TRANS. Connect the DS, BK, ODD, or DHUM terminal on the C R RH RC HVAC equipment to this terminal. When 1 zone is calling W1/E W (o
Краткое содержание страницы № 7
ZONE 1 THERMOSTAT ZONE 2 THERMOSTAT ZONE 3 THERMOSTAT DAMPER DAMPER DAMPER HZ432 TrueZONE CONv ENTi ONal The following diagram is an overall view of wiring for a conventional system as depicted in steps 3–9. ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED RRD OR MARD DAMPER M1 COMMON POWER-OPEN POWER-CLOSED M4 OPEN M6 CLOSED M1 M1 M4 M4 M6 M6 R Rc R Rc R C C R C W1/E W1/E C W W2 W2 W W2 W3 W3 W2 Y Y1 Y1 Y Y2 Y2 Y2 Y2 HVAC G G G G O/B O/B 24 VOLT TRANS. L L C R W RH M1 ARD OR ZD DAMPER W2 RC M4 SPRING
Краткое содержание страницы № 8
ZONE 1 THERMOSTAT ZONE 2 THERMOSTAT ZONE 3 THERMOSTAT DAMPER DAMPER DAMPER Installation Guide HEa T p u Mp Use the following diagram for wiring a 2-heat/1-cool heat pump with electric auxiliary heat. NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by heat pump thermostats. The diagram below shows a heat pump thermostat used with a heat pump system. ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED RRD OR MARD DAMPER M1 COMMON POWER-OPEN M4 OPE
Краткое содержание страницы № 9
ZONE 1 THERMOSTAT ZONE 2 THERMOSTAT ZONE 3 THERMOSTAT DAMPER DAMPER DAMPER HZ432 TrueZONE HEa T p u Mp Use the following diagram for wiring a 3-heat/2-cool heat pump with electric stage 3 heat. ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED RRD OR MARD DAMPER M1 COMMON POWER-OPEN M4 OPEN POWER-CLOSED M6 CLOSED M1 Rc M1 R M4 M4 Rc C M6 M6 R E R R C 1 AUX C C E Y W1/E W1/E AUX 1 Y2 W2 W2 Y G W3 W3 Y2 AIR 2 O/B Y1 Y1 G L HANDLER Y2 Y2 O/B 2 G G L 24 VOLT TRANS. O/B O/B C R L L EM. HEAT E ARD OR ZD DAMP
Краткое содержание страницы № 10
ZONE 1 THERMOSTAT ZONE 2 THERMOSTAT ZONE 3 THERMOSTAT DAMPER DAMPER DAMPER Installation Guide Dual f u El Use the following diagram for wiring a dual-fuel system with single-stage furnace and single-stage heat pump. ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED RRD OR MARD DAMPER M1 COMMON POWER-OPEN POWER-CLOSED M4 OPEN M6 CLOSED M1 M1 M4 M4 M6 M6 R Rc R Rc C R C R C W1/E W1/E C E W2 W2 E AUX W3 W3 AUX Y Y1 Y1 Y Y2 Y2 Y2 Y2 G G G G FURNACE O/B O/B O/B O/B L L L 24 VOLT TRANS. L C R RH W M1 ARD OR Z
Краткое содержание страницы № 11
ZONE 1 THERMOSTAT ZONE 2 THERMOSTAT ZONE 3 THERMOSTAT DAMPER DAMPER DAMPER HZ432 TrueZONE Dual f u El Use the following diagram for wiring a dual-fuel system with two-stage furnace and two-stage heat pump. ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED RRD OR MARD DAMPER M1 COMMON POWER-OPEN POWER-CLOSED M4 OPEN M6 CLOSED M1 M1 M4 M4 M6 M6 R Rc R Rc R C C R C W1/E W1/E C E W2 W2 E AUX W3 W3 AUX Y Y1 Y1 Y Y2 Y2 Y2 Y2 G G G G FURNACE O/B O/B O/B O/B L L L L 24 VOLT TRANS. C R HEAT 1 W RH M1 ARD OR ZD
Краткое содержание страницы № 12
Installation Guide CONfigura Ti ON To enter Configuration: WIRELESS HOME WIRELESS HOME CONFIG CONFIG CHECK OUT CHECK OUT MODE MODE Press the Mode button (the Config LED will 1 light up). BACK ADJUST SETTING NEXT BACK ADJUST SETTING NEXT Use the Back and Next buttons to navigate M24799 M24810 through the configuration menus. Pressing Fig. 17 2 Next enters the selected option for that menu item and advances to the next menu. Adjust settings up or down by pressing the Adjust Setting button. T
Краткое содержание страницы № 13
HZ432 TrueZONE CONNECT Wir El Ess D Evi CEs WIRELESS HOME CONFIG CHECK OUT MODE Press the Mode button until the Wireless LED lights up. The TrueZONE must be configured for wireless 4 devices to select Wireless mode. BACK ADJUST SETTING NEXT M28194 Press Next to add devices. While the display alternates the Press Connect and Exit screens, push the Connect button(s) on the wire- less device(s). -OR- Follow the instructions that came with the wireless device(s). Press Next to exit. Fig. 19 TM
Краткое содержание страницы № 14
Installation Guide aD av NCED CONfigura Ti ON Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 10 for instructions on using these buttons. Table 5. Advanced Configuration. Menu Name Menu Title (LCD Menu Options (LCD bottom Menu option description Notes: top line) line; defaults in bold) Heat Fan HEAT FAN [HVAC] PANEL Fan control by HVAC In heat mode, fan controlled by HVAC or turned CONTROL on by panel in call for heat. HVAC [PA
Краткое содержание страницы № 15
HZ432 TrueZONE Op Era Ti ON The HZ432 TrueZONE panel contains an LED display that communicates system and zone status. The LEDs indicate the following information. Much of this information, as well as configuration information, is listed on the label on the inside of the HZ432 cover. For users who prefer French or Spanish labels, HZ432 they are provided in form 69-2198FS. Cut them out and attach them to the inside of the HZ432 cover. Table 6. LED Operation. HEAT 1 ZONE 1 HEAT 2 LED Descript
Краткое содержание страницы № 16
Warra NTy Honeywell warrants the products in this catalog (except those parts designated on Honeywell’s price lists as not covered by this warranty) to be free from defects due TM to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPRO , FocusPRO®, PRO TM TM TM 4000, PRO 3000, LineVolt PRO, Digital Round , and Modern Round (T87K, N) Series Thermostats with a date code of 0501 or later: sixty (60) months from date