www.mgeups.com
Pulsar Evolution
2200/3000/3000 XL
Installation and user
manual
Краткое содержание страницы № 2
MGE UPS Systems 1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636 For service call 1-800-438-7373 www.mgeups.com IMPORTANT SAFETY INSTRUCTIONS Read before installing product SAVE THESE INSTRUCTIONS. This manual contains important instructions for 89347, 89348, and 89349 that should be followed during installation and maintenance of the UPS and batteries. Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. The Pulsar Evolution range has been designed wit
Краткое содержание страницы № 3
Introduction CAUTION: Safety of persons w The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC-power source. w Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel. w The UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the protected equipment does not exceed 3.5 mA by checki
Краткое содержание страницы № 4
Foreword Using this document Information may be found in two ways, using: w the contents; w the index. Pictograms IMPORTANT: Important instructions that must always be followed. NOTE: Information, advice, help. WARNING: Indicates present eminent danger, precautionary action required. CAUTION: Indicates to proceed with caution, precautionary action required. Visual indication. Action. Audio indication. In the illustrations on the following pages, the symbols below are used: LED off. LED on. LED
Краткое содержание страницы № 5
Contents 1. Presentation 1.1 Overall view .................................................................................................................................. 7 Tower position ..................................................................................................................................7 Rack position....................................................................................................................................7 1.2 Back ......................
Краткое содержание страницы № 6
Contents 6. Appendices 6.1 Technical data ..............................................................................................................................24 Simplified diagram..........................................................................................................................24 Technical characteristics ................................................................................................................25 Examples of battery backup times ............
Краткое содержание страницы № 7
1. Presentation 1.1 Overall view Tower position Dimensions in inches (W x H x D) Evolution 2200 Evolution 3000 17.24 (19") x 3.56 (2U) x 25.2 Evolution 3000 XL Weight in lbs Evolution 2200 75 Evolution 3000 82 Evolution 3000 XL 46 Rack position D H W 3400723100/AD - Page 7 P U L S A R Evolution 3 0 0 0 P U L S A R Evolution 3 0 0 0
Краткое содержание страницы № 8
P 0 3 - 5 1. Presentation 1.2 Back Pulsar Evolution 2200 USB communications port. 1 Data line protection R IN 34Z5 U.P.S. 1 RS232 RS232 communications port. 2 OUT SITE WIRING AC Input FAULT WARNING AC Input Volt 120V~1O 3 battery cabinets max Amps 16A MAX 2 Hertz 50/60 Hz BATTERY CONNECTOR TO BATTERY 72Vdc, 7Ah AC Output Volt 120V~1O 344-50282-00 Volt: 72Vdc 40A Hertz 50/60 Hz CABINET W/VA 1540W/1920VA Connector for automatic detection of an Pb 3 U.S. PAT. N
Краткое содержание страницы № 9
1. Presentation 1.3 Control panel 15 Illuminated ON/OFF button for the receptacles. Operation on battery power. 16 17 UPS fault. Battery fault. Overload. 18 Group 1 programmable receptacles supplied with power. 19 1 2 Group 2 programmable receptacles supplied with power. 20 Booster or fader mode. 21 Bar graph indicating percent load at output. 22 % % 23 Bar graph indicating the battery charge level. 76 to 100%. 51 to 75%. 26 to 50%. 0 to 25%. 3400723100/AD - Page 9
Краткое содержание страницы № 10
2. Installation 2.1 Unpacking and parts check 26 25 27 28 29 30 31 32 26 RS232 communications cable for Windows Operating Systems. For UNIX/Linux Operating Systems, please order, for free, the following part number: 66090 USB communications cable. 27 28 Telescopic rails for mounting in 19" bay with mounting hardware. 29 Two securing systems for equipment power cords. 30 CD-ROM with the Solution-Pac and UPS Driver software. 31 Product documentation. 32 Two supports for the upright position. Pa
Краткое содержание страницы № 11
2. Installation 2.2 Upright installation (tower position) Connect the two supports for the upright position. 3400723100/AD - Page 11 P U L S A R Evolution 3 0 0 0 P U L S A R Evolution 3 0 0 0
Краткое содержание страницы № 12
Краткое содержание страницы № 13
R 34Z5 U.P.S. AC Input AC Input Volt 120V~1O Amps 16A MAX Hertz 50/60 Hz BATTERY CONNECTOR AC Output Volt 120V~1O Volt: 72Vdc 40A Hertz 50/60 Hz W/VA 1540W/1920VA U.S. PAT. No. 6,094,363 AC Output 2. Installation 2.4 Connecting the protected equipment CAUTION: Check that the indications on the rating plate on the back of the UPS correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS. 1 - Re
Краткое содержание страницы № 14
Data line protection Data line protection IN IN RS232 RS232 OUT OUT SITE WIRING WARNING SITE WIRING WARNING 3 battery cabinets FAULT 3 battery cabinets FAULT max for 3000 max for 3000 12 battery cabinets 12 battery cabinets max for 3000XL max for 3000XL 72Vdc, 9Ah 72Vdc, 9Ah BATTERY CONNECTOR TO BATTERY Only for 3000 TO BATTERY Only for 3000 344-50297-00 Volt: 72Vdc 40A CABINET 344-50297-00 Pb CABINET Pb U.S. PAT. No. 6,094,363 2. Installation 2.5 Connection to the RS232 or USB communi
Краткое содержание страницы № 15
Data line protection IN RS232 OUT SITE WIRING WARNING 3 battery cabinets FAULT max for 3000 12 battery cabinets max for 3000XL 72Vdc, 9Ah TO BATTERY Only for 3000 344-50297-00 CABINET Pb 2. Installation 2.7 Installation of the communications-card option 1 - Remove the slot cover 5 secured by two screws. 2 - Insert the card in the slot. 5 3 - Secure the cover with the two screws. Slot for the communications-card It is not necessary to shut down the UPS to option. install the communications c
Краткое содержание страницы № 16
Краткое содержание страницы № 17
3. Operation 3.3 Operation on battery power (following failure of AC-input power) Transfer to battery power The AC-input power is out of tolerances, LED 16 goes ON. During operation on battery power, the buzzer beeps every ten seconds. The equipment connected to the UPS is supplied by the battery. 16 1 2 % % Threshold for the low-battery warning When the threshold is reached, the buzzer beeps every three seconds. The low-battery warning threshold can be set by the user, with the “UPS Driver”
Краткое содержание страницы № 18
Краткое содержание страницы № 19
3. Operation Voltage-thresholds tab Configurable function Default setting Options Output voltage on battery power 120 V 100 V - 127 V Upper threshold for transfer to battery power 151 V 141 V to 153 V Fader-mode cut-in threshold 132 V 127 V to 138 V Booster-mode cut-in threshold 102 V 92 V to 108 V Lower threshold for transfer to battery power 89 V 80 V to 94 V Maximum input-voltage range Disabled Enabled (1) Lower threshold for transfer to battery mode = 70 V Sensitivity tab Configurable functi
Краткое содержание страницы № 20