Краткое содержание страницы № 1 
                    
                         
 
 
 
Mitsubishi Electric Air Conditioning Network System 
TM
BACnet Interface: PAC-YG31CDA (Ver. 1.30) 
Operation Manual 
 
 
 
 
  
 
 
 
 
 
 Contents 
  
  
 
 
1.Safety Precautions             ………1
 
 
 
 
 
2.System Requirements            ………2
  
 
 
3.System Configuration             ………4
 
 
 
 
 
4.Functional specification             ………6
  
 
 
5.Installation                       ………16
 
 
 
 
 
6.Part Name and Functions          ………20
  
 
 
7.Initial Startup and Shutdown        
                    
                    Краткое содержание страницы № 2 
                    
                                                    Contents                1.Safety Precautions                                  ………1   2.System Requirements                               ………3   2.1 Requirements (system recommendations)        ………3   2.2 Compatible Airconditioner                        ………3   2.3 Restrictions                                     ………4     3.System Configuration                               ………5   3.1 System Configuration Example                  ………5   3.2 Hardware Connection Diagram  
                    
                    Краткое содержание страницы № 3 
                    
                          In this manual, Microsoft® Windows® XP Professional is called Windows XP.     Trademarks  MS, Microsoft, Microsoft logo, and Windows are registered trademarks and trade names of Microsoft  Corporation.  TM BACnet is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air –  Conditioning Engineers, Inc.).  Each company may use as registered trademarks and trade names the product names used in this  manual.                                                             
                    
                    Краткое содержание страницы № 4 
                    
                          1. Safety Precautions    Please read the Safety Precautions section very carefully before using the unit.   The safety cautions provided here are very important for your safety. Please observe them at all times.   The degrees of danger involved with incorrect operation of the unit are indicated in this manual using  the following symbols.    WARNING Incorrect operation could result in death or severe injury.      CAUTION Incorrect operation could result in injury or damage to property.     
                    
                    Краткое содержание страницы № 5 
                    
                         Safety Guidelines for the Computer Running the Integrated PAC-YG31CDA Software (Summary)      1. Selecting a Computer      Selecting a desktop Computer based UPS recommended     Depending on the function, it is recommended to use a  It is recommended to use a UPS to protect data from    desktop as opposed to a laptop computer as there is a momentary power outages or power cuts.     tendency for heat to build up in a laptop.         Use a computer/operating environment with specifications capa
                    
                    Краткое содержание страницы № 6 
                    
                          2.System Requirements       2.1 Requirements (system recommendations)  We recommend the following software and hardware when using this application (PAC-YG31CDA; BACnet IF).    Item Contents Note  PC PC/AT interchangeable machine   CPU Pentium 4 1.8GHz or faster   Memory 256 MB or more   HDD 2GB or more 4GB or more of C drive free space  necessary  Storage CD-ROM drive It is used at the time of installation of  device BACnetIF.  Resolution 1024 × 768 or higher, 65536 colors or more   LAN 2 por
                    
                    Краткое содержание страницы № 7 
                    
                         2.3 Restrictions  The following restrictions apply to the BACnet IF program.    (1) System configuration limits   Number of units Note  G-50A Max. 10 units G-50A Ver. 2.50 or higher  Indoor unit Max. 50 units/G-50A Max. 500 units (including all IC, KIC, AIC, LC, and FU) [Symbol] IC: Indoor unit, LC: LOSSNAY, FU: OA processing unit, AIC: “A” controller,   KIC: “K” controller     Checking the G-50A version     Check the centralized controller G-50A version. Update if it is not the applicable vers
                    
                    Краткое содержание страницы № 8 
                    
                          3.System Configuration     3.1 System Configuration Example      [Image drawing]                HUB    Outdoor unit   Indoor unit  Power  supply unit     LAN  Remote  controller     BACnet IF G-50A  Software    Power    supply unit         G-50A              3.2 Hardware Connection Diagram  (1) LAN connection  Connect the LAN cable to the PC. The location of the LAN connector of the PC, refer to the  Instruction Manual of the PC.        HUB 10BASE-T      straight cable    LAN BACnet IF  To G-5
                    
                    Краткое содержание страницы № 9 
                    
                        3.3 Group Configuration    In BACnet IF, a G-50A number + group number is a unit for management. The instance number of   BACnet consists of G-50A number + group number + member numbers. For details, it is "Chapter 4.3   Relation between object and management item" reference.  Below, a group number and G-50A number are explained.    1) G-50A number   This is set up with a Setting Tool program.  The ranges of the G-50A number are 1-10.    2) Group number  Two or more sets IC (Indoor Unit) are set
                    
                    Краткое содержание страницы № 10 
                    
                          4.Functional specification    4.1 Communication Protocol Specification      1) Protocol Outline  BACnet/IP which applied to ANSI/ASHRAE 135-1995, 135a, 135b correspondingly on UDP/IP  of Ethernet is used.      Ether Header IP Header UDP Header BVLL Header NPCIof BACnetNETWORK APDU of BACnet       2) Ether Header  A physical layer sets a transmission medium to 10 BASET by Ethernet.      3) IP Header  The private address of Class C is recommended (*1).    Subnet mask 255.255.255.0  *1: Recommend
                    
                    Краткое содержание страницы № 11 
                    
                        4.2 Object List    The list of the objects to be used is shown below.    Object type Note  Support  : Support  ×: Un-supporting  0    Analog Input  Analog Output 1 ×   Analog Value 2    Binary Input 3    Binary Output 4     Binary Value 5    Calendar 6 ×   Command 7 ×   Device 8    Event Enrollment 9 ×   File 10 ×   Group 11 ×   Loop 12 ×   Multi-state Input 13    Multi-state Output 14     Multi-state Value 19 ×   Notification Class 15    Program 16 ×   Schedule 17 ×   Averaging 18 ×  
                    
                    Краткое содержание страницы № 12 
                    
                        4.3 Object and Management Item    Object ID consists of object type + instance number.  An instance number consists of G-50A number + air-conditioner equipment group number + member number.    31                      22 21                                            0(bit)    BACnet object type Instance number      Instance number (decimal and 6 figures):  X X XX XX    Member number (01 ~ 99)  Group number (01 ~ 50)    G-50A number (01 ~ 10)    Note: G-50A number: Specify the IP address of G-50A 
                    
                    Краткое содержание страницы № 13 
                    
                        Management item  Object Object type Instance Note  number    Prohibition of local operation Binary Value xxxx15 Inactive: Permit Active: Prohibit  (filter reset)  *3)  Prohibition of local operation  Binary Value xxxx16 Inactive: Permit Active: Prohibit  (Set Temp.)  Communication State Binary Input  xxxx20 Inactive: Normal Active:   Abnormalities  System Forced Off Binary Value xx9921 Inactive: Released Active: Effective   *3)  01: Horizontal  Multi-State Output  Air direction (setup) xxxx22  0
                    
                    Краткое содержание страницы № 14 
                    
                        4.4 Service List    Service Initiate Execute Note  0 Acknowledge Alarm × ×   Confirmed COV Notification 1 ×     Confirmed Event Notification 2  ×   Get Alarm Summary 3 × ×   Get Enrollment Summary 4 × ×   Subscribe COV 5 × ×    Unconfirmed COV Notification 28  ×   29 Unconfirmed Event Notification  ×   Atomic Read File/Atomic Write File 6/7 × ×    Add List Element 8 × ×   9 Remove List Element × ×   Create Object/Delete Object 10/11 × ×   Read Property 12 ×     13 Read Property Conditional 
                    
                    Краткое содержание страницы № 15 
                    
                        4.5 Service list for every object  Service transceiver list for every object is shown below.         INIT  : BACnet IF transmits.    EXEC : BACnet IF receives.     Note  INIT              Time Synchronization  EXEC              INIT              I-Am  EXEC              INIT              Who-Is  EXEC              INIT              I-Have  EXEC              INIT              Who-Has  EXEC              Confirmed COV INIT  ▲  ▲ ▲ ▲ ▲ ▲ ▲    Notification EXEC              Confirmed Event INIT  ▲
                    
                    Краткое содержание страницы № 16 
                    
                        4.6 Event Service specification    It is shown whether Event Notification of each object is carried out or it does not carry out.  Event is used for the notice of Alarm. COV is used for announcement at the time of change of Present_Value.  Selection of Confirmed and Unconfirmed presupposes that it is possible for every notification point.    Object Object type Event COV Note  On/Off (setup) Binary Output     On/Off (state) Binary Input      Binary Input   Alarm signal    Error Code Multi-S
                    
                    Краткое содержание страницы № 17 
                    
                        4.8 Setting functional list           The list of the setting functions of BACnet IF is arranged below.   Chapter 8 explains the usage of each function.        Setting information takes backup. For the backup procedure, refer to Appendix 3.    Item Details  G-50A Tab G-50A and the air-conditioning unit for management are set up.  (*1)   G-50A setup The information on G-50A for management is set up.  G-50A number, IP address, Port number (80 fixation : for LAN communication of G-50A).   Group set
                    
                    Краткое содержание страницы № 18 
                    
                          5.Installation    5.1 Pre-installation Steps    Preparing for installation         Before installing BACnet IF program, do the following checks and preparatory steps.    Steps Action Details How to  1 Check the OS Check the OS Service Pack version * If not the correct version,  ・WindowsXP Professional:SP1and above upgrade to the correct  version.  2 Check the memory Check that there is at least 256MB of RAM * If necessary, add more RAM 3 Check the HDD free Check that there is at least 2GB of f
                    
                    Краткое содержание страницы № 19 
                    
                        5.2 BACnet IF Setup         This section describes how to set up BACnetIF and a setting tool (SetBACnet).    (1)CD-ROM directory structure      The folder composition of the setup disk (CD-ROM) of BACnet IF is shown.   [CD-ROM drive]  /BACnetIF :Set-up folder for BACnet IF     /SetBACnet :Set-up folder for Setting Tool      (2) Starting the setup program  Please click and start "SETUP.exe" in CD-ROM.        If there is no problem with cautions, click the        [Next] button to continue on the n
                    
                    Краткое содержание страницы № 20 
                    
                          (5) Check the installation folder      Check the location where the program is to be installed.      If the location needs to be changed, set the new location      by clicking the [Browse] button.      After checking the installation location, click the [Next]        button.              * Click the [Cancel] button to stop the installation.                       (6) Check the program folder       Check the program folder name that registers       the BACnet IF program into the start menu.