Краткое содержание страницы № 1
IMI CORNELIUS REMCOR INC 500 REGENCY DRIVE GLENDALE HEIGHTS, IL 60139–2268
Telephone (800) 551–4423 Facsimile (800) 519–4423
Operator’s Manual
CHILLER (“CHILLER” SERIES)
Models: CH550 and CH 551
Part No. 91272
Revised: August 9, 2002
Revision C
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION
This Manual must be read and understood before installing or operating this equipment
PRINTED IN U.S.A
IMI CORNELIUS INC; 1999–2002
Краткое содержание страницы № 2
TABLE OF CONTENTS Page INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Краткое содержание страницы № 3
INTRODUCTION The REMCOR “CH” Series Water Chillers (Models CH550–A and CH551–A) are specifically designed to cool clean water before it is circulated to the cooling application. The Unit includes a complete refrigeration system and associated controls housed in a sturdy sheet metal enclosure with perforated panels for air circulation. Op- tions include a reservoir and a choice of pumps and temperature controls to provide a self–contained liquid cool- ing circulation system tailored to a particul
Краткое содержание страницы № 4
INSTALLATION INSTRUCTIONS LOCATION Locate the chiller indoors in a well ventilated area with ambient temperatures in the range of 65° to 100° F. Allow a minimum of six inches of clearance around the chiller for proper air circulation. Avoid hot air discharge from other equipment or enclosed areas where heat could build up and cause a rise in ambient temperature. PLUMBING Follow standard plumbing practices and local codes in making water connections. Piping that is exposed to high ambient tempera
Краткое содержание страницы № 5
When the flow rate to the process is critical, a flow meter and valve should be installed in the line in order to ob- tain the proper flow rate. On Units with optional bypass valve, the aforementioned valve can be omitted and the flow can be adjusted with this valve. Turning the valve clockwise increases the flow to the process whereas turning the valve counterclockwise decrease the flow to the process. Once these start–up procedures are complete, the chiller is ready for standard operation. NOT
Краткое содержание страницы № 6
3. Remove the screw securing the mounting bracket to the back of the thermostat. 4. Remove the thermostat from the front panel. 5. Install the new thermostat in the front panel and secure it with the mounting bracket. 6. Reconnect the wires at back of the thermostat. 7. Install the wrapper. REPLACING ELECTRONIC DIFFERENTIAL THERMOSTAT 1. Remove the wrapper as specified in REMOVING WRAPPER. 2. Remove the two screws securing the thermostat cover and remove the cover. 3. Loosen the screw terminals
Краткое содержание страницы № 7
FLUID RECOMMENDATION Remcor Chillers are designed to operate with water to provide maximum performance for temperatures of 40F–100F. Distilled Water Acceptable De–Ionized Water Acceptable (1–5 MEG/OHMS) De–Ionized Water Acceptable with Stainless Steel & PVC only (5+MEG/OHMS) *No Copper or Brass Propylene Glycol Acceptable – 30% Glycol/70% Water (Lab & Industrial Grade) *For Applications with Temperatures below 40F Lab & Industrial Grade Ethylene Glycol Acceptable – 30% Glycol/70% Water *For A
Краткое содержание страницы № 8
TROUBLESHOOTING GUIDE Trouble Probable Cause Remedy CHILLER DOES NOT A. No power. A. Check fuse or circuit breaker. OPERATE B. Loose or poor wire connection. B. Check wiring. Correct for loose or poor wire connection. C. Inoperable ON–OFF switch. C. Replace ON–OFF switch. D. Overload device open. D. Allow compressor to cool, then install new overload device; replace compressor if necessary. E. Inoperable relay. E. Replace relay. F. Low input voltage. F. Nominal voltage ± 10% is required. NO CIRC
Краткое содержание страницы № 9
PARTS LIST FIGURE 1. CH550 AND CH551 EXPLODED VIEW Item Item No. Part No. Name No. Part No. Name 1 31934 Switch, Illuminated (CH550) 10 61058 TXV 31935 Switch, Illuminated (CH551) 11 60514 Sight Glass 2 32386 Thermostat, Eliwell No. EWPC902 12 60502 Control, Low Pressure 3 620603708 Blade, Fan 13 61002 Filter Drier 4 620603711 Motor, Fan (CH550) 14 * Reciever 620603709 Motor, Fan (CH551) 15 Not Used 5 * Condenser 16 * Pump, Circulating 6 Not Used 17 32378 Transformer, Thermostat 7 620603701 Comp
Краткое содержание страницы № 10
Краткое содержание страницы № 11
WARRANTY IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workmanship un- der normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or Wilshire prod- uct, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the equipment model number, serial number and the date of purchase. IMI Cornelius Offices AUSTRALIA P.O. 210, RIVERWOOD, NSW 2210, AUSTRALIA (61) 2 533 3122
Краткое содержание страницы № 12
CORPORATE HEADQUARTERS: Remcor Incorporated 500 Regency Drive Glendale Heights, IL 60139