Краткое содержание страницы № 1
®
GE Zoneline packaged
terminal air conditioners
2010 contract sales architects and engineers data manual
Краткое содержание страницы № 2
Quick Reference Full Specs on pages 52 and 53 ALL UNITS REQUIRE POWER CONNECTION KIT Power Connection Kit determines resistance heat output 7000 Btuh units are not offered with 4.7 KW resistance heater Dry Air 25 4100 Series Cooling with Electric Heat 4100 Series Cooling with Electric Heat MODEL COOLING MODEL COOLING EER EER NUMBER (Btuh) NUMBER (Btuh) AZ41E07DA* 7300/7100 12.8/12.8 AZ41E07DAP 6800/6600 12.2/12.2 AZ41E09DA* 9450/9250 12.3/12.3 AZ41E09DAP 9000/8800 11.8/11.8 AZ41E12DA* 11800
Краткое содержание страницы № 3
geappliances.com Power Connection Kits 230/208-Volt Line Cord Connection Units 230/208-Volt Sub-Base and Direct Connected Units Electric Electric Electric Min. Circuit Electric Electric Electric Min. Circuit Direct Line Cord Heat Heater Heat Protection Sub-Base Connection Heat Heater Heat Protection Kit BTUH Watts Amps (Amps) Kit BTUH Watts Amps (Amps) RAK3153A 8150/7900 2400/2320 11.0/11.6 15 RAK204D15P RAK4157 8150/7900 2400/2320 11.0/11.6 15 RAK3203A 11200/10900 3300/3200 1
Краткое содержание страницы № 4
® The Zoneline 4100 and 6100 Series have incorporated changes suggested by customers, along with enhancements by GE’s Technology Team and changes necessary to meet new UL and NEC requirements. “L” shaped condenser coil. Cross flow blower across the product line for quieter operation. The “Partial Open Vent Air” feature was a specific request by a customer. “Heat Sentinel” is an enhancement developed by GE’s Technology Team to help lodging professionals welcome their guests with a moder
Краткое содержание страницы № 5
geappliances.com Table of Contents Front Cover 1 Mini Specs 4100 and 6100 Series 2 Mini Specs Power Connection Kits and Nomenclature 3 The 4100/6100 and Dry 25 4 Table of Contents 5 Introduction 6 The Zoneline System 7 Features and Benefits Features Table 8 Features and Benefits 9–11 Auxiliary Control Settings 12–13 Central Desk Control 14 Remote Thermostat Control 15–17 Heat Pumps and Energy Savings 18–19 Installation and Dimensions Application Comments 20 Case Dimensions 21 Wall Case/Sub-Base
Краткое содержание страницы № 6
Introduction This manual is designed to provide product, performance Deluxe Line Optional Features: and application information to our customers and their • C orr o s i on P r o t ecti on architects and engineers for use in selection and design • I n t e r n a l C o n d e n s a t e R e m o v a l ( o n 6 1 0 0 S e r i e s ® of a zonal comfort control system utilizing GE Zoneline Heat Pump without Corrosion Protection) Packaged Terminal Air Conditioners (PTAC) and Packaged
Краткое содержание страницы № 7
geappliances.com The Zoneline System The typical Zoneline installation consists of the wall case (or sleeve), chassis, power cord and exterior grille. Some installations may use a sub-base for support of the unit or for ease of electrical connections. Each of the components should be the standard products offered by GE or, in the case of the exterior grille, approved by GE Applications Engineering. Use of components not specifically designed or approved for use with the Zoneline unit can resu
Краткое содержание страницы № 8
® Zoneline Features Resistance heat Heat pump AZ AZ AZ 41 Series 41 Dry Air 25 61 Series Cooling EER Range (230 Volts/265 Volts) 10.6 - 12.8 11.3 - 12.2 11.2 - 13.2 Heating COP Range (230 Volts/265 Volts) N/A N/A 3.3 - 4.0 Refrigerant type R-410A R-410A R-410A Cross-flow (tangential) blower Standard Standard Standard Enhanced Dehumidification Optional Standard — Heat pump with resistance heat back-up — — Standard Heat pump with supplemental resistance heat — — Standard Staged Heating — — 3-Sta
Краткое содержание страницы № 9
geappliances.com Features and Benefits Standard Physical Dimensions Automatic Emergency Heat GE has maintained the same dimensions since 1961 — Automatically uses electric resistance heat if the heat 42" wide x 16" high x 13-3/4" deep pump output is not sufficient to maintain selected room temperature. Replacement of older units is made easy. Reverse Cycle Heat Pump Defrost System Weather-Protected Electrical Components Standard on all Zoneline 6100 Series heat pumps. Vital electrical com
Краткое содержание страницы № 10
Features and Benefits Fan-Only Setting – HIGH/LOW Indoor Coil Frost Control The unit provides the option of selecting either HIGH or LOW Prevents indoor coil from freezing speed for Fan-Only operation. and causing complaints due to lack of cooling. Frost can form on the Fan-Cycle Switch – “SmartFan” indoor coil when the unit is operated Unique “SmartFan” allows unit to operate fan continuously in cooling when outdoor temperatures in cooling operation and fan cycle in heating to provide be
Краткое содержание страницы № 11
geappliances.com Features and Benefits Up-Front Air Filters Corrosion Protection (Optional) Two interchangeable 4100 and 6100 Series units may be ordered with special up-front filters, easy protection to better withstand damage from salt air and to remove and reinstall, salt water in seacoast areas. may be cleaned without Corrosion protection is standard on the Dry Air 25 models. opening or removing Heat pump units with ICR are not available with corrosion the room front. protection
Краткое содержание страницы № 12
Auxiliary Control—Aux Set Button The auxiliary control push button is located behind the room cabinet, below the control panel. The auxiliary controls come preset to the modes most desired by customers. However, the owner is responsible for ensuring the auxiliary controls are set to the desired function. There are 9 different modes that can be set using the auxiliary set button. To change modes: • Pr ess A U X S E T (“ A U” appears on the display ) . • P r e s s t h e M O
Краткое содержание страницы № 13
geappliances.com Auxiliary Control Settings (cont) Mode 3—Freeze Sentinel/Heat Sentinel The default settings for Mode 3 are: Heat Sentinel is off Freeze Sentinel is on. When Freeze Sentinel is activated, it automatically provides heat without user interface. This helps to prevent plumbing damage by turning the heater and indoor fan ON at 41ºF and OFF at 46ºF. When Heat Sentinel is activated, it automatically provides cooling without user interface. This helps to prevent an excessively
Краткое содержание страницы № 14
Central Desk Control Some installations may want to govern the ability of the unit 4. R ecommended wire size must be followed as a minimum to operate from a control device remote to the unit or even requirement. remote to the room in which the unit is located. The general Wire Size #AWG Maximum Allowable Length term given to systems such as this is Central Desk Control. #22 600 Ft. The most common installation of this type of system is a #20 900 Ft. switch mounted at the registration de
Краткое содержание страницы № 15
geappliances.com Remote Thermostat Control In some installations, control of the operation of the unit at The fan speed for the 4100 Series in remote thermostat a location remote from the unit itself may be desired. A unit operation is selected by the connection of the fan wire from mounted high in the wall or over a door, for instance, where the thermostat to either the HIGH or LOW terminal on the unit. the unit-mounted controls are inaccessible, can be connected See the sketch of the unit
Краткое содержание страницы № 16
Remote Thermostat Control Heat Pump Models Feature Heat Pump Electric Heat ® The Zoneline 6100 Series heat pump units may be Indoor Frost Control Yes Yes ™ connected to a single-stage cooling/two-stage heating Freeze Sentinel Yes Yes thermostat designed for use with heat pump systems. Heat Sentinel Yes Yes GE offers two thermostats compatible with the Auto Fan Speed No No 6100 series units: Electronic Temperature Limiting No No Switch to Resistance Heat Based on Indoor Determined by Tem
Краткое содержание страницы № 17
geappliances.com Remote Thermostat Control Selection Chart For Zoneline Packaged Terminal Units Zoneline Series Thermostat Model Type Function Low-Voltage Conductors 4100 RAK164D1 Digital 5 Cooling and Heating RAK164P1 Digital Programmable 5 6100 RAK148D1 Digital 6 Single-Stage Cooling – 2-Stage Heating RAK148P1 Digital Programmable 6 Thermostat wire size – up to 60 feet AWG20 – up to 66 feet AWG18 For remote thermostat operation follow the steps below: 1. Turn on the unit and ensure it is
Краткое содержание страницы № 18
Heat Pumps and Energy Savings ® • G E Z oneline heat pumps are designed to provide Balance Point cost-efficient heat pump operation while monitoring An important consideration in the selection of a heat pump room conditions to maintain comfort. unit is the “balance point” of the installation. Virtually every The units employ a logic system monitoring both outdoor room is unique—with different insulation, different sizes and indoor temperatures to determine the heat source, thus and t
Краткое содержание страницы № 19
geappliances.com Heat Pumps and Energy Savings An option is provided in the auxiliary controls (Mode 8) to Heat Pump Operation — Zoneline 6100 Series allow the unit to operate only in resistance heat. The use of Heat sources: Heat pump, heat pump and simultaneous this option significantly increases the cost for heating. electric resistance heat or electric resistance heat. Zoneline heat pumps employ a highly featured microprocessor Heat pump defrost — Zoneline 6100 Series control system int
Краткое содержание страницы № 20
Application Comments Use and Care Manual and installation instructions are High Wall Mount — For units ® shipped with Zoneline units. It is important that any air mounted high in the wall, the conditioning system be properly sized and applied in order discharge louvers should be to achieve the desired temperature and humidity levels in at a setting that provides the the space to be conditioned. Zoneline units are designed most horizontal air discharge. primarily to provide heating and co