PRO-E Series User's Manual 1. Introduction 2 2. Controls and Indicators 5 3. Installation 7 4. Operation 9 5. Troubleshooting 12 6. Replacing the Battery 13 7. Obtaining Service 16 8. Specifications 17 9. Configurable Parameters & Settings 18 10. Limited Product Warranty 19 11. Declaration of Conformity 21 © Copyright Para Systems, Inc., 2003 1 English
Краткое содержание страницы № 3
English Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS ! Please read this manual before installing your PRO-E Series UPS, models PRO500E, PRO700E, PRO1100E, PRO1500E, PRO500iE, PRO700iE, PRO1100iE, PRO1500iE, as it provides important information that should be followed during installation and maintenance of the UPS and batteries allowing you t
Краткое содержание страницы № 4
CAUTION! Connect the UPS to a two pole, three wire grounding AC wall outlet. The receptacle must be connected to the appropriate branch protection (circuit breaker or fuse). Connection to any other type of receptacle may result in a shock hazard and violate local elec- trical codes. CAUTION! To reduce the risk of electrical shock in conditions where the load equipment grounding cannot be verified, disconnect the UPS from the AC wall outlet before installing a computer interface cable. Reconn
Краткое содержание страницы № 5
English Receiving Inspection After removing your MINUTEMAN UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to MINUTEMAN, please use the original
Краткое содержание страницы № 6
On-Line/On-Battery/Boost/Buck LED Fault LED Overload LED Weak/Bad Battery LED On/Off/Test Button Press and release the ON/OFF/Test Button after 1 beep to turn the UPS ON or OFF (see section 4). On-Line On-Battery Buck Boost The On-Line/On-Battery/Boost and Buck (green) LED illuminates in a steady state when the UPS is on and supplying AC power to the load. The LED blinks and the audible alarm sounds, when supplying battery power to the load. The LED blinks and no audible alarm when the UPS
Краткое содержание страницы № 7
English REAR PANEL 1 10 2 120V Models 3 9 4 8 5 6 7 1. The Information/Rating Label. 2. The Battery Backup and Surge output power receptacles are NEMA 5-15R type (IEC 320 C13 sockets for 230V models). 3. The USB Communications Interface Port is for UPS monitoring and control. 4. The RS232 Communications Interface Port is for UPS monitoring and control. 5. The Dipswitches are for setting the Inverter output voltage. 6. The input power cord has a NEMA 5-15P Plug (IEC 320 C14 socket for 230
Краткое содержание страницы № 8
INSTALLATION PLACEMENT The PRO-E series is intended to be install in a temperature controlled environ- ment that is free of conductive contaminants. Select a location which will pro- vide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged. Operating Temperature (Maximum): 0 to 40 degrees C (+32 to 104 degrees F) Operating Elevati
Краткое содержание страницы № 9
English DO NOT plug Power Strips or Surge Protection Devices into WARNING! the Battery Backup Receptacles on the UPS. Plugging Power Strips or Surge Protection Devices into the Battery Backup Receptacles may cause internal damage to the UPS, the Power Strip, or the Surge Protection Device. CONNECTING THE UPS TO AN AC SOURCE Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use extension cords, adapter plugs, power strips or surge strips. CHECKING THE SITE WIRING FA
Краткое содержание страницы № 10
TURNING THE UNIT ON/OFF ON / OFF / Test Button Press and release the ON/OFF/Test Button after one beep to turn the UPS ON and supply power to the load. The load is immediately powered while the UPS runs a two-second self test. Press and release the ON/OFF/Test Button after one beep to turn the UPS OFF. The UPS will continue to charge the batteries whenever it is plugged into an AC outlet and there is AC present. SELF TEST The self test feature is useful to verify the correct operation of the
Краткое содержание страницы № 11
English ALARMS ON BATTERY When the UPS is operating on the batteries, the On-Battery LED will blink and the audible alarm will sound once every 10-seconds. The alarm will stop once the UPS returns to the On-Line operation. LOW BATTERY WARNING The UPS will sound two beeps every five-seconds when the battery reserve runs low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion. WEAK/BAD BATTERY The UPS automatically tests the batterys condition and will i
Краткое содержание страницы № 12
COMMUNICATIONS PORTS (RS232 and USB) The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure capability. The PRO-E series UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port. To change the port configuration requires the unit be turned off and restarted with the desired cable connected. The pinout for the port is depicted per the chart below. Pin 1: EPO Emergen
Краткое содержание страницы № 13
English What To Do Symptom Possible Cause UPS will not turn on On/Off/Test button not Press and release the On/Off/ pushed Test button to start UPS UPS operates in Input AC circuit breaker is Reset circuit breaker by battery mode only, tripped pressing the plunger back in. even though there is If the AC circuit breaker trips normal AC present after UPS starts up, reduce the load on the UPS Fault LED is UPS has detected an Call for service illuminated internal fault Have a Qualified Electrician
Краткое содержание страницы № 14
REPLACING THE BATTERY (AUTHORIZED SERVICE PERSONNEL ONLY) The PRO-E Series UPS has an easy to replace hot-swappable batteries. Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. This Uninterruptible Power Supply contains potentially hazardous WARNING! voltages. Do not attempt to disassemble the UPS beyond battery replacement p
Краткое содержание страницы № 15
English CAUTION: Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressure operated vents. These UPSs contain sealed non-spillable lead acid batteries. PRO-E PRO700E PRO500E PRO1100E PRO1500E Model # PRO700iE PRO500iE PRO1100iE PRO1500iE Battery 1-12V9Ah 2-12V7Ah 3-12V7Ah 3-12V9Ah Model # Panasonic LC-R129 LC-R127 LC-R127 LC-R129 Part # Yuasa Part # REW45-12 NP 7-12 NP 7-12 REW45-12 BATTERY REPLACEMENT PROCEDURE PLEASE READ THE CAUT
Краткое содержание страницы № 16
9. Disconnect the positive (red) wire from the battery positve terminal. 10. Disconnect the battery negative (black) wire from the battery negative terminal. NOTE: Use CAUTION, do not touch the battery positive wire to the battery negative wire. 11. Remove the battery bracket retaining screw and slide the battery bracket upwards. 12. Using the pull tab, pull the batteries out completely. DO NOT pull the batteries out by pulling the battery jumper wires. 13. Remove the battery
Краткое содержание страницы № 17
English IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.Verify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3.Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax MINUTEMAN Technical Support at the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or visit our Web site at www.minutemanups.com the "Discussion Board".
Краткое содержание страницы № 18
PRO500E PRO700E PRO1100E PRO1500E MODEL NUMBER (PRO500iE) (PRO700iE) (PRO1100iE) (PRO1500iE) (230V Models) Acceptable Input voltage 0 - 165VAC (0 - 290VAC) Input voltage (AC Mode) 75 - 145VAC (150 - 280VAC) Output voltage (AC Mode) 120VAC: 105-130VAC (230VAC: 206-250VAC) Nominal input frequency 50 or 60 Hz, autosensing Input protection Resettable circuit breaker Frequency limits (AC Mode) 50 or 60 Hz, +/-6Hz Transfer time 2-6 mS typical 500VA 700VA 1100VA 1500VA Maximum load 350W 490W 770W 1050
Краткое содержание страницы № 19
English (These items may require optional software or hardware) Function Factory User Choices Description Default UPS ID PRO-E Up to 64 Use this function to uniquely characters identify the UPS in your network to define configuration the UPS Battery Date of Date of battery Enter the current date when install manufacture replacement - replacing batteries date month/day/year XX/XX/XXXX Battery 1826 Up to 5 At first battery replacement, reset life in characters to reflect actual number of days days
Краткое содержание страницы № 20
Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equip- ment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para S