Краткое содержание страницы № 1
MICRONIX PC/104
POWER SUPPLY
PV-5127, PV-5127A
POWER SUPPLY MODULE WITH UPS & BATTERY CHARGER
User Manual
&
Installation Guide
VERS. 1.1
DOC: M5236DM
Micro Technic A-S • Denmark •
Tel. +45 6615 3000 • Fax +45 6615 3077
E-mail: support@micro-technic.com
Website: www.micro-technic.com
Краткое содержание страницы № 2
Users Manual & Installation Guide PV- 5127: Power supply module with UPS Table of contents TABLE OF CONTENTS ................................................................................................................................................. 2 REVISION HISTORY ..................................................................................................................................................... 4 GENERAL INFORMATION.................
Краткое содержание страницы № 3
Users Manual & Installation Guide PV- 5127: Power supply module with UPS J1............................................................................................................................................................................. 28 ST3 .......................................................................................................................................................................... 28 J2...............................
Краткое содержание страницы № 4
Users Manual & Installation Guide PV- 5127: Power supply module with UPS Revision history Revision number Reason for change Date 1.0 Initial revision 23-Mar-04 1.1 Error in mechanical layout 21-Oct-05 changed – page 27. Page 4 of 31
Краткое содержание страницы № 5
Users Manual & Installation Guide PV- 5127: Power supply module with UPS General information Ordering codes PV-5127-S PV-5127A-S S=Stack-through PC/104 connector Available models: Model no Description PV-5127-S 75W PC/104 Power Supply Module (+5V, +12V), 18-35V input supply with UPS/Battery charger PV-5127A-S 75W PC/104 Power Supply Module (+5V, +12V), 10-35V input supply Accessories These accessories must be ordered separately if needed.
Краткое содержание страницы № 6
Users Manual & Installation Guide PV- 5127: Power supply module with UPS Description The Micronix PV-5127 is a high efficiency PC/104 power supply for embedded, vehicular and automotive systems applications. It will withstand extended temperatures and the shock and vibration of mobile equipment. Micronix PV-5127 has an input supply range of 18-35V (PV- 5127A: 10-35V), which is convenient for automotive and low-voltage applications. Intelligent back-up b
Краткое содержание страницы № 7
Users Manual & Installation Guide PV- 5127: Power supply module with UPS The mains supply is continuously monitored. There is hysteresis on the mains monitor so that a mains failure is reported when the mains voltage drops below 16.5V, and mains is reported OK when the voltage rises above 17.5V.
#$
%&$'()
!"
The connected lead-acid bac
Краткое содержание страницы № 8
Users Manual & Installation Guide PV- 5127: Power supply module with UPS Connectors The PC-5127 is equipped with nine connectors:
* * +, * +, * #$* +, "-
+, 0
12(
* '
*34# * / / /49 Power input connector (KL2) Power into PV-5127 (Mains and battery) is supplied through KL2 that is a four-pole removable screw clamp connector. The layout of this connector is prin
Краткое содержание страницы № 9
Users Manual & Installation Guide PV- 5127: Power supply module with UPS Heater and fan control and external LEDs connector (CN2) Status for PV-5127 can be shown on external LEDs. These must be connected to CN2 by a 10 position ribbon cable with a mating connector. Furthermore, the +5V Standby and logical outputs for the external heating element and the external fan are placed in this connector. The layout of this connector is shown in the schematic to t
Краткое содержание страницы № 10
Users Manual & Installation Guide PV- 5127: Power supply module with UPS ATX connector (CN10) The ATX connector holds the three ATX-signals: PS_ON, PWR_GOOD and +5V Standby. The layout of this connector is shown in the schematic. The function of the individual ATX signals is shown in the table: ATX signal Pin no Function GND 1 System GND * 2 For factory use only * 3 For factory use only * 4 For factory use only * 5 For factory use only * 6 For fact
Краткое содержание страницы № 11
Users Manual & Installation Guide PV- 5127: Power supply module with UPS PC/104 bus connector (CN1) The PC/104 connector is for connecting the PV-5127 to the CPU and other PC/104 boards. There is a female connector on the top, and pins on the bottom so that you can mount other PC/104 boards both above and below the PV-5127. The main +5V and +12V outputs are available in the PC/104 connector, so you don’t need to use the KL3 outputs when drawing smaller
Краткое содержание страницы № 12
Users Manual & Installation Guide PV- 5127: Power supply module with UPS System temperature The PV-5127 has a temperature measuring circuit that can control an external fan and heater, and prevent the CPU from starting if the temperature is too low or too high. It monitors the system temperature as long as +5V STB is on. As system temperature sensor, you can use the onboard sensor, or an external sensor of type Infineon KTY 11-5 connected to J2 (label
Краткое содержание страницы № 13
Users Manual & Installation Guide PV- 5127: Power supply module with UPS Note that the heater and fan outputs are logical outputs that become 3.3V when they are active. If necessary, the user must provide driving circuitry to drive an actual heater and fan. The positions of the two outputs in CN2 are shown here. If the temperature is too cold or too hot, the CPU cannot be turned on until it changes to cool or warm. But if it the CPU is on, and th
Краткое содержание страницы № 14
Users Manual & Installation Guide PV- 5127: Power supply module with UPS UPS Control The PV-5127 provides several methods for the CPU to get UPS status information, and to turn off power. The CPU can get status information through the RS232 and the PC/104 interface, and it can perform a software-controlled power-off through the ATX PS_ON signal, through an RS232 signal, and through the PC/104 interface. PS_ON signal Two of the ATX functions that are s
Краткое содержание страницы № 15
Users Manual & Installation Guide PV- 5127: Power supply module with UPS RS232 The PV-5127 has a connector (CN3, labelled “RS232”) that can be connected to an RS232 port on the CPU. The PV-5127 provides two handshake outputs with status information, and one handshake input for controlling shutdown. The RxD and TxD signals are not used, the only used signals are Ground and the three handshake signals. The three signals are compatible with the “simple s
Краткое содержание страницы № 16
Users Manual & Installation Guide PV- 5127: Power supply module with UPS RS232 Status signals The Battery low and Mains failure signals together can tell three different states: Mains failure Battery low Status 0 0 Running normally on mains power. 1 0 Mains alarm, running on battery. The CPU is advised to shut down if mains power doesn’t come back within reasonable time. This time should be configured in the UPS monitoring software. 1 1 Critical alarm
Краткое содержание страницы № 17
Users Manual & Installation Guide PV- 5127: Power supply module with UPS PC/104 interface The PV-5127 has a software interface where the CPU can read status information and perform a power-off through the PC/104 bus. The power-off can be delayed up to 253 seconds, so that the UPS monitoring can start the delayed power-off, then start a shutdown of the operating system, and the actual power-off happens after the operating system has finished shutting down.
Краткое содержание страницы № 18
Users Manual & Installation Guide PV- 5127: Power supply module with UPS b (STATUS bit 3): Battery present. b=0: Battery not present (empty or disconnected) b=1: Battery present BAT_STATUS (port 252h, read only): nn0cctvv This port contains the following read-only battery status information bits. vv (BAT_STATUS bit 1-0): Battery voltage. See the section Battery monitor and charger. vv=00: Empty or low vv=01: Medium vv=10: Full vv=11: Disconnec
Краткое содержание страницы № 19
Users Manual & Installation Guide PV- 5127: Power supply module with UPS 00h: SOFT_OFF (first half of 2-second delay) FEh: SOFT_ON FFh: SOFT_OFF (second half of 2-second delay), or SOFT_TEMPBAD Other values: SOFT_DELAY, delayed shutdown in progress. value = remaining seconds until SOFT_OFF Software normally won’t read the values 00h and FFh since the 5V+12V is off at this time. Writing 00h will turn off power immediately, and it will stay off for at l
Краткое содержание страницы № 20
Users Manual & Installation Guide PV- 5127: Power supply module with UPS Battery monitor and charger Battery voltages The PV-5127 monitors the voltage of the battery as long as the main DC/DC converter is on. The voltage status controls the charger, the RS232 alarm output, the battery LED, and it can be read through PC/104. The possible ranges are: Range Thresholds Below 9.5V Empty Between 9.5V and (10.75V, 11.25V) Low Between (10.75V, 11.25V) and