Краткое содержание страницы № 1
SAG582135000
System Application Guide
Spec. No. 582135000 (Model LXP48F1)
Issue AE, January 31, 2007
Home
SYSTEM OVERVIEW
Description: -48VDC power system @ up to 555 Amperes, 25000 Watts max.
The Model LXP48F1 is a complete Power System containing power conversion,
intelligent monitoring and control, and distribution. An LXP Power System typically
consists of...
• Distribution Cabinets
The system always includes a minimum of one Distribution Cabinet, which
provides DC distri
Краткое содержание страницы № 2
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Home Family: LXP Spec. No.: 582135000 Model: LXP48F1 Output Voltage: -48 Volts DC System Output Capacity: System (Three Power Shelves): 555 Amperes, 25500 Watts max. (208/240V) 277.5 Amperes, 12750 Watts max. (120V) Main Power Shelf: 163 Amperes, 7500 Watts max. (208/240V) 81.5 Amperes, 3750 Watts max. (120V) Expansion Power Shelf: 196 Amperes, 9000 Watts max. (208/240V) 98 Amperes,
Краткое содержание страницы № 3
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Home 582135000 Distribution Cabinet List BD, BL, BS, GA, LB, LD, LS, LX Power Shelf(s) List 1 SEE ALSO OTHER OPTIONS and ACCESSORIES System Overview Table of Contents List 61: 1U Wireway List Structure Table Distribution Devices List 62: 2 U Wireway Lugs List 93: Battery Tray Relay Rack Options Load Shed Card Replacement Cables List of Parts Specifications Dimensional
Краткое содержание страницы № 4
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) TABLE OF CONTENTS System List Accessory List of Physical Size Related Picture Specifications Overview Information Information Parts Information Documentation SYSTEM OVERVIEW................................................................................................................................................ 1 TABLE OF CONTENTS.......................................................
Краткое содержание страницы № 5
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Cables ................................................................................................................................................................. 31 RJ-45 MCA Control Bus Cable......................................................................................................................... 31 MCA Control Bus Interconnect Cable ....................................
Краткое содержание страницы № 6
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Home LIST INFORMATION (If viewed electronically, more detailed information is available for each option by clicking on the desired number in the column entitled List No. in the table below.) Main List Numbers Mounting List Positions Part Number Description Notes Description No. (1U = 1-3/4”) 2 per shelf, 1 58213500001 Model LXP9000SHF Integrated Power System 1, 2 6 max. 61 582135
Краткое содержание страницы № 7
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Home List Descriptions List 1: Model LXP9000SHF List of Parts Integrated Power System Features ♦ Complete LXP Integrated Power System platform, provides Main Power Shelf, MCA, up to two Expansion Power Shelves, and up to 17 PCUs. ♦ For more information, refer to System Application Guide SAG589200100. Restrictions ♦ List 20 of 589200100 (Bulk Termination Panel) cannot be used when syste
Краткое содержание страницы № 8
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Home List of Parts List 93: Battery Tray, Pre-cabled Features ♦ Provides one battery tray that mounts four (4) 12V front terminal VLRA batteries. Batteries are configured as one (1) 48V string. Battery cabling is factory-connected to Power System main bus. ♦ Accepts various Valve Regulated Lead Acid (VLRA) batteries. See Ordering Notes below. ♦ Tray dimensions are 21.3” wide X 22.4” dee
Краткое содержание страницы № 9
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Home 4) Specify rack spacing of 7U (12.25”) or 8U (14”) between trays and above top tray as required for battery clearance. See table above. 5) Specify with or without Battery Disconnect circuit breakers. Note: All List 93 trays in a bay will be furnished with or without Battery Disconnect circuit breakers as specified for the first tray ordered. 6) If ordering List 93 with circuit break
Краткое содержание страницы № 10
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Home List BD: Distribution Cabinet List of Parts (18) Fuse/Circuit Breaker Positions with Low Voltage Battery Disconnect and Battery Shunt Features ♦ Single Voltage Distribution (-48V) ♦ Maximum Capacity: Input: 500A max. Total Distribution: 300A max. Battery Recharge Current: 500A max. @ +50°C; 400A @ +65°C. Battery Terminals as Remote Feed: 200A max. ♦ (18) Mounting Positions f
Краткое содержание страницы № 11
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Home List BL: Distribution Cabinet List of Parts (18) Fuse/Circuit Breaker System Positions with Low Voltage Battery Disconnect, Battery Shunt and Load Shunt Features ♦ Single Voltage Distribution (-48V) ♦ Maximum Capacity: Input: 500A max. Total Distribution: 300A max. Battery Recharge Current: 500A max. @ +50°C; 400A @ +65°C. Battery Terminals as Remote Feed: 200A max. ♦ (18) Mo
Краткое содержание страницы № 12
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Home List BS: Distribution Cabinet List of Parts (18) Fuse/Circuit Breaker System Positions with Battery Shunt Features ♦ Single Voltage Distribution (-48V) ♦ Maximum Capacity: Input: 500A max. Total Distribution: 300A max. Battery Recharge Current: 500A max. @ +50°C; 400A @ +65°C. Battery Terminals as Remote Feed: 200A max. ♦ (18) Mounting Positions for Load Distribution Fuses or
Краткое содержание страницы № 13
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Home List GA: Distribution Cabinet List of Parts (20) GMT Fuse System Positions with Split Bus Features ♦ Single Voltage Distribution (-48V) ♦ Maximum Capacity: Input: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C. Total Distribution: 30A per bus, 60A total @ +65°C Battery Recharge Current: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C. Battery Terminals as Remote Feed: 103A @ +40°C; 95A @ 50°
Краткое содержание страницы № 14
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Home List LB: Distribution Cabinet List of Parts (18) Fuse/Circuit Breaker Positions with Low Voltage Load Disconnect, Battery Shunt and Load Shunt Features ♦ Single Voltage Distribution (-48V) ♦ Maximum Capacity: ♦ Maximum Capacity: Input: 500A max. Total Distribution: 300A max. Battery Recharge Current: 500A max. @ +50°C; 400A @ +65°C. Battery Terminals as Remote Feed: 200A ma
Краткое содержание страницы № 15
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Home List LD: Distribution Cabinet List of Parts (18) Fuse/Circuit Breaker System Positions with Low Voltage Load Disconnect and Load Shunt Features ♦ Single Voltage Distribution (-48V) ♦ Maximum Capacity: Input: 500A max. Total Distribution: 300A max. Battery Recharge Current: 500A max. @ +50°C; 400A @ +65°C. Battery Terminals as Remote Feed: 200A max. ♦ (18) Mounting Positions f
Краткое содержание страницы № 16
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Home List LS: Distribution Cabinet List of Parts (18) Fuse/Circuit Breaker System Positions with Load Shunt Features ♦ Single Voltage Distribution (-48V) ♦ Maximum Capacity: Input: 500A max. Total Distribution: 300A max. Battery Recharge Current: 500A max. @ +50°C; 400A @ +65°C. Battery Terminals as Remote Feed: 200A max. ♦ (18) Mounting Positions for Load Distribution Fuses or Ci
Краткое содержание страницы № 17
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Home List LX: Distribution Cabinet List of Parts (18) Fuse/Circuit Breaker System Positions with Battery Shunt and Load Shunt Features ♦ Single Voltage Distribution (-48V) ♦ Maximum Capacity: Input: 500A max. Total Distribution: 300A max. Battery Recharge Current: 500A max. @ +50°C; 400A @ +65°C. Battery Terminals as Remote Feed: 200A max. ♦ (18) Mounting Positions for Load Distri
Краткое содержание страницы № 18
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Hom Home e ACCESSORY INFORMATION Distribution Devices Bullet Nose Type Circuit Breakers Each circuit breaker plugs into a single mounting position. Ordering Notes 1) Order circuit breakers per Table 1. Note: Load should not exceed 80% of device rating. Caution: A circuit breaker with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other overcur
Краткое содержание страницы № 19
System Application Guide SAG582135000 Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007 Home TPS/TLS-Type Fuses A single fuseholder provides for installation of a 3 to 100 ampere Bussmann TPS-type or Littelfuse TLS-type fuse. This fuseholder plugs into a single mounting position on the compatible distribution bus options described in this document. This fuseholder provides a GMT-A alarm type fuse, which operates open to provide an alarm indication if the distribution fuse op
Краткое содержание страницы № 20
SAG582135000 System Application Guide Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1) Plug-In GMT Fuse Distribution Assembly (Part No. 524679) (10) GMT Alarm-Type Fuse Positions Features ♦ Mounts in (5) distribution positions of any Distribution Cabinet. ♦ 30A Maximum Capacity ♦ Provides (10) Load Distribution Fuse Positions (0.25 to 15A GMT Alarm-Type Fuses) ♦ Screw clamp type terminals ♦ Includes 10 dummy fuses equipped with safety fuse covers. Restrictions When fact