Краткое содержание страницы № 1
GOLD CGs
Gas-Fired Water Boilers
• Installation • Maintenance
Boiler Manual
• Startup • Parts
This manual must only be used by a qualified heating installer/service technician. Before installing, read all
instructions, including this manual, the burner manual and any related supplements. Perform steps in the order
given. Failuret oc omplyc ould result in severe personalinj ury, deatho r substantialp ropertydamag e.
DO NOT USE BOILER DURING CONS
Краткое содержание страницы № 2
GOLD CGs Gas-Fired Water Boiler — Boiler Manual How it works . . . Control module ① The control module responds to signals from the room thermostat, air pressure switch and boiler limit circuit to operate the boiler circulator, pilot burner, gas valve and inducer. When roomthe rmostat callsf or heat, the c ontrol module startsthe system circulatorand inducer. The control module runs the inducer long enough to purge the boiler flue passage
Краткое содержание страницы № 3
GOLD CGs Gas-Fired Water Boiler — Boiler Manual GOLD CGs Gas-Fired Induced-Draft Water Boiler 3 Part number 550-110-260/0107
Краткое содержание страницы № 4
GOLD CGs Gas-Fired Water Boiler — Boiler Manual Contents Howit works ....................................................2–3 Hazard definitions ............................................... 4 Please read before proceeding ............................ 5 1 Prepare boiler location ...................................6–11 2 Prepare boiler ...............................................12–13 3 Water piping .................................................14–23 4 Ventin
Краткое содержание страницы № 5
GOLD CGs Gas-Fired Water Boiler — Boiler Manual Please read before proceeding Installer User • This manual is for use only by your qualified Read all instructions before in- heating installer/service technician. stalling. Follow all instructions in • Please refer to the User’s Information Manual for proper order to prevent personal your reference. injuryo r death. • We recommend regular service by a qualified • Alsor efer toCGs Venting Supplements. service tec
Краткое содержание страницы № 6
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1a Prepare boiler location — codes & checklist Installations must followthese codes: • Local, state, provincial, andnat ional codes, la ws,r egulations and ordinances. • National Fuel Gas Code, ANSIZ 3.1–latest edition. • Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ ASME CSD-1, w hen required. • National Electrical Code. • For Canada only: B149.1 or B149. Installation Cod
Краткое содержание страницы № 7
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1b Prepare boiler location — clearances Recommended SERVICE clearances Figure 2 Required MINIMUM clearances (Fig. 1) 1. Provide clearances for cleaning and servicing the boiler and for access to controls and components. See Figure1 for recommenda- tions. . Provide at least screwdriver clearance to jacket front panel screws for removal of front panel for inspection and minor service. If unable to pro
Краткое содержание страницы № 8
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1c Prepare boiler location — vent system Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury ord eath. Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause severe personal injury or death. DO NOT COMMON VENT — Do not install the CGs into a common vent
Краткое содержание страницы № 9
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1d Prepare boiler location — contamination Please review the following information on potential Refer to Table 1 for products and areas which may cause combustionair c ontamination problems. contaminated combustionair . To prevent potential of severe personal injury or death, check for products or areas listed below beforeinstal ling boiler. If anyo f thesec ontaminants are found: • removec ontami
Краткое содержание страницы № 10
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1e Prepare boiler location — air openings mended in Figure 3 will allow adequate ventilation and Combustion air opening location and sizing combustion air provided the boiler room is not sub- requirements depend on the clearances around jected to negative pressure due to exhaust fans or other the boiler. Check the boiler placement compared to mechanical ventilation devices. Refer to the National Figure1,
Краткое содержание страницы № 11
GOLD CGs Gas-Fired Water Boiler — Boiler Manual Figure 3 Sizing air openings for CGs installations ✷ 11 Part number 550-110-260/0107
Краткое содержание страницы № 12
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 2a Prepare boiler — placement & setup Inlet air box top panel must be in Place boiler/crate near position during boiler operation. position Failure to do so could result in severe personal injury, death or 1. Leave boiler in crate and on pallet until installation substantial propertydamag e. site is ready. . Move entire crate and pallet next to selected loca- tion. 3. Remove crate. Orifice re
Краткое содержание страницы № 13
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 2b Prepare boiler — pressure test 5. Slowly reopen boiler drain valve until test pressure Hydrostatic pressuretest on the pressure/temperature gauge reaches no more Pressure test boiler before attaching water or gas piping than: (except as noted below) or electrical supply. • 45 psigf orb oilersw ith 30 psig relief valve. Prepareboiler for test • 75 psig for boilersw ith 50 psig relief valve. 1. Remove t
Краткое содержание страницы № 14
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3a Water piping — general information Generalpiping information Circulator If installation is to comply with ASME or Canadian requirements, an ad- The circulator is shipped loose (wiring pre-attached to ditional high temperature limit is needed. Install control in supply piping boiler) to allow you to locate it either in the return or between boiler and isolation valve. Set second control to mini
Краткое содержание страницы № 15
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3b Water piping — single-zone system Diaphragm-typeor bladder- Closed-type expansion tank type expansion tank (Figure 4) (Figure 5) 1. Ensure expansion tank size will handle boiler and 1. Ensure expansion tank size will handle boiler and system water volume and temperature. Tank must system water volume and temperature. See tank be located in boiler return piping as close to boiler manufacturer’s inst
Краткое содержание страницы № 16
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3c Water piping — multiple zones Piping multiple zones Piping forradiant heating Follow instructions on pages 14 and 15 to install near- systemsor converted gravity boiler or single-zone piping. (Also refer to Piping for systems radiant heating systems or converted gravity sys- tems,b elow, if ap plicable.) Converted gravity (or steam)systems See Figure 6 or Figure 7, page1 , to complete instal- Wh
Краткое содержание страницы № 17
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3c Water piping — multiple zones (continued) Figure 6 Zoning with circulators Figure 7 Zoning with zone valves — return water 130°F or higher. — return water 130°F or higher. 1 Boiler isolation (balancing) 10 Automatic air vent (with diaphragm-type expansion tank), or connect valves to tank fitting (closed-type expansion tank). DO NOT use an automatic air vent when using closed-type expansion tank. It would allow
Краткое содержание страницы № 18
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3d Piping — low temp systems the water temperature being supplied to the radiant Primary/secondary (preferred) tubing. bypass piping method Gauge 8 is required on all systems to assure the return Primary/secondary bypass piping is preferred because water temperature is accurately set for a minimum of the flow rate and temperature drop in the heating 130°F. If this gauge is not available however, a
Краткое содержание страницы № 19
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3d Piping — low temp systems (continued) Figure 8 Primary/secondary piping Figure 9 Primary/secondary piping Zoning with circulators Zoning with zone valves 9 Relief v alve 1 Boiler isolation (balancing) valves 10 Automatic air vent (with diaphragm-type expansion tank), or 2 Flow/check valve connect to tank fitting (closed-type expansion tank). DO NOT use an automatic air vent when using closed-type expansion 3 Sys
Краткое содержание страницы № 20
GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3d Piping — low temp systems (continued) justed using cold (or room temperature) return water BOILER-bypasspiping to the boiler. (When setting the valves without gauge method 4a installed — using cold or room temperature water — assume the return water temperature to be 60°F. Set This piping method (Figures 10 and 11, page 1) is thev alves so gauge 8 reads at least 10°F. called a boiler-bypass