Краткое содержание страницы № 1
61-86-03-13
Herculine 11280S
9/01
Page 1 of 14
Smart Actuator
Specification
Overview
Honeywell’s HercuLine 11280S Smart
actuators incorporate all of the high
quality and reliable features of the
traditional HercuLine actuators plus
the added benefits of a microprocessor-
based Enhanced Electronics Unit (EEU).
These additional benefits provide:
• Faster set-up and commissioning
• Network capability
• Health parameter monitoring for
proactive maintenance planning.
He
Краткое содержание страницы № 2
61-86-03-13 Page 2 Features (continued) Health Monitoring A standard feature on all 11280S Operation actuators accumulates information • Factory Calibration – Factory • Control Signals – 0/4 to 20 mA, about actuator operation. This 0/1 to 5 Vdc, 0 to 10 Vdc, Digital calibration is stored in non-volatile information then can be used to remote setpoint (RS485 Modbus memory and can be restored via evaluate and determine predicted or the local HMI at any time. RTU protocol).
Краткое содержание страницы № 3
61-86-03-13 Page 3 Local Display and Keypad Configuration and set-up is through the local HMI, consisting of a display and keypad interface (Figure 2). A high intensity 10-character LED display and simple pushbuttons provide quick access for actuator set up and status information. If relay outputs are specified, all configuration can be done through either the local HMI interface. If mechanical switches are specified, then the user must manually set the auxiliary output. Control
Краткое содержание страницы № 4
61-86-03-13 Page 4 Set Up/Configuration Parameters Configuration parameters are logically grouped and accessed using the local HMI. Actuator calibration is also accomplished through a simple procedure using the keypad. By pressing the SETUP button on the HMI, you can step through the set up groups that contain all of the configuration parameters. The table below summarizes the configuration parameters available within the various set up groups. Full details of all configuration para
Краткое содержание страницы № 5
61-86-03-13 Page 5 Set Up Group Configuration Parameter Selections/Settings LOCKID – Set Security Password SET LOCK Enables lock out or access to selected LOCK – Lock Out set up group parameters and calibration values. FAILSF – Failsafe CFGTST – Configuration Test Diagnostic READ STATUS Displays failsafe condition RAMTST – RAM Test Diagnostic CALTST – Calibration Test Diagnostic and the results of various SEETST – Serial EEPROM Test diagnostics performed Diagnostic durin
Краткое содержание страницы № 6
61-86-03-13 Page 6 Specifications – General, Continued Physical Torque Output Shaft Key Output Maximum Handwheel Approx. Model # lb-ft (N_M) Shaft Size Size Shaft Overhang Diameter Maximum Length Load Weight 11284S 425 2" 1/2" 5" 3700 lb. 18" 300 lb. (576) (51 mm) (13 mm) (127 mm) (1678 kg) (457 mm) (136 kg) 11285S 840 2" 1/2" 5" 3700 lb. 18" 300 lb. (1139) (51 mm) (13 mm) (127 mm) (1678 kg) (457 mm) (136 kg) 11286S 1500 2" 1/2" 5" 3700 lb. 18" 300 lb. (2033) (51 mm) (13 mm) (127
Краткое содержание страницы № 7
61-86-03-13 Page 7 Specifications – Actuator Electrical Input Signals Analog: 0/4 to 20 mA (With supplied 250 ohm shunt resistor for current range) 0/1 to 5 Vdc 0 to 10 Vdc Digital: Remote Setpoint via Modbus RTU (RS485) Input Impedance Input Input Impedance 0/4 to 20 mA 250 ohms 0/1 to 5 Vdc 10 K ohms Provides characterization of the input signal. Input Characterization Selections are: Linear, Square Root or Custom. Sensitivity 0.2 % to 5 % of 90° span, proportion
Краткое содержание страницы № 8
61-86-03-13 Page 8 Pipe Linkage Kit Pipe linkage kits are available from Honeywell and can be used for linkage lengths from 24 to 240 inches (61 to 610 cm). The kits include the mechanical pipe couplings, load rod end (left-hand thread), connecting rods and locking nuts. See Figure 4. The actuator rod end (right-hand thread), nut and bolt are supplied with the actuator. The customer must supply a piece of schedule 40 pipe 2 ½” * (both ends with right-hand NP threads) and a nut and
Краткое содержание страницы № 9
61-86-03-13 Page 9 External Transformers 120 Vac (Single Phase) For customer applications requiring 120/240 Vac single phase operation, a step-up transformer is mounted in a separate enclosure (Model Selection Guide Table I, option 1). Figure 6 shows the installation for the transformer enclosure. 575 Vac (3 Phase) For customer applications requiring 575/460 Vac 3 phase operation, a step-down transformer is mounted in a separate enclosure (Model Selection Guide Table I, option 6). Fig
Краткое содержание страницы № 10
61-86-03-13 Page 10 Model Selection Guide Reference 62-86-16-19 Instructions Select the desired key number. The arrow to the right marks the selection available. Make the desired selections from Tables I thru VIII using the column below the arrow. A dot ( ) denotes unrestricted availability. Key Number I II III IV V VI VII VIII IX _ _ _ _ _ _ _ - _ - _---- _ _ _ _ _ _ _ _ _ - _ - _ _ _ _ _ _ - _ _ KEY NUMBER - Electronics Selection Availability Output Torque (lb. - ft.) (N - M) 4
Краткое содержание страницы № 11
61-86-03-13 Page 11 Model Selection Guide, continued 01128_ _ 4S 5S 6S 8S TABLE V - SWITCH AND RELAY OUTPUTS (2 mech end-of-travel limits standard) Selection 9S 7S Auxiliary Switches None 00 _ and 2 Aux. SPDT Switches 20 _ 2 Aux. + 2 Programmable Relay Outputs 22 _ 2 Programmable Relay Outputs 02 _ 4 Programmable Relay Outputs 04 _ Auto/Manual Switch None _ _0 One Auto/Manual Switch with Out-of-Auto Contact _ _1 TABLE VI - CONFIGURATION INTERFACE RemoteNone 0 Local Integrally mounted
Краткое содержание страницы № 12
61-86-03-13 Page 12 Figure 7 Mounting and Outline Dimensions for 11284S, 11285S, 11286S, 11288S, and 11289S Weather-Proofed Motor Actuators - Right Hand Floor Mounting, Handwheel Shaft Horizontal (D-MTG-616-200)
Краткое содержание страницы № 13
61-86-03-13 Page 13 Figure 8 Mounting and Outline Dimensions for 11284S, 11285S, 11286S, 11288S, and 11289S Weather-Proofed Motor Actuators - Left Hand Floor Mounting, Handwheel Shaft Horizontal (D-MTG-616-210)
Краткое содержание страницы № 14
61-86-03-13 Page 14 Warranty/Remedy Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantabilit