Resumo do conteúdo contido na página número 1
255029-YTG-M-0610
DESCRIPTION
This fan coil line offers the ultimate in application flexibility. The
AHP (non-variable speed motor) models can be ordered upflow
only or as multi-position. The multi-position model can be
installed in downflow, upflow, horizontal right or left without the
need for additional field installed kits.
All UPG air handlers and coils utilize a TXV to provide our cus-
tomers with the optimum performance and refrigerant control
required for 13+ SEER systems. Air handlers c
Resumo do conteúdo contido na página número 2
255029-YTG-M-0610 DIMENSIONS J F 10-3/8” K BLOWER COMPARTMENT TOP OUTLET A CIRCUIT BREAKER DIMENSIONS PANEL D DRAIN CONNECTIONS REFRIGERANT FOR UPFLOW AND CONNECTIONS DOWNFLOW APPLICATIONS 7-11/32” E 18-9/32” 1-1/2” C B BOTTOM INLET FILTER DIMENSIONS DRAIN PAN CONNECTIONS ACCESS FOR HORIZONTAL APPLICATIONS Dimensions 1 Refrigerant Dimensions Wiring Knockouts Connections MODELS ABC JK Line Size DE F Height Width Depth Power Control Liquid Vapor 7/8” (1/2”) AHP18B3XH21 46 17.5 12-3/8 13-29/32 14-
Resumo do conteúdo contido na página número 3
255029-YTG-M-0610 COIL TECHNICAL DATA Refrig. Face Area Rows Fin Tube Tube Fin Models Application Coil Size TXV Geometry Dia. Type Conn. Types (Sq. Ft.) Deep Per In. AHP18B3XH21 None Cooling / Sweat 3.40 2 14 (2) 14 x 17.5 1 x 0.866 3/8 Enhanced Heat Pump AHP18B4FH21 4E AHP24B3XH21 None Cooling / Sweat 3.89 2 14 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced Heat Pump AHP24B4FH21 4F AHP30B3XH21 None AHP30B4GH21 4G Cooling / Sweat 3.89 3 12 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced Heat Pump AHP30B4HH21 4H
Resumo do conteúdo contido na página número 4
255029-YTG-M-0610 ACCESSORIES LIMITATIONS Refer to Price Manual for specific model numbers. These units must be wired and installed in accordance with all national and local safety codes. TXV Kits - TXV kits are available for “Flex-coil” applications and converting R22 to R410A or as a service replacement. All kits Voltage limits are as follows: are bolt-on and require no brazing to install. 1 Air Handler Voltage Normal Operating Non-Combustible Bases - A combustible floor base accessory Vol
Resumo do conteúdo contido na página número 5
255029-YTG-M-0610 AIR FLOW DATA - 60 Hz MODELS 230 Volt Blower 1 Models Motor CFM @ External Static Pressure - IWC Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 High 1054 989 923 862 791 665 581 202 N/A N/A AHP18B**H21 Medium 782 762 716 670 613 536 315 121 N/A N/A Low 541 519 479 445 397 298 168 N/A N/A N/A High 1232 1167 1098 1025 940 826 731 622 486 345 AHP24B**H21 Medium 966 915 868 799 724 641 540 452 347 224 Low 785 740 684 618 532 446 364 296 192 131 High 1434 1359 1297 1220 11
Resumo do conteúdo contido na página número 6
255029-YTG-M-0610 PHYSICAL & ELECTRICAL DATA Models AHP18B**H21 AHP24B**H21 AHP30B**H21 AHP36C**H21 Blower - Diameter x Width 9 x 6 10 x 9 10 x 9 10 x 10 HP 1/3 HP 1/4 HP 1/2 HP 3/4 HP Motor Nominal RPM 1075 1075 1075 1075 Voltage 230 Amps Full Load (230) 1.9 1.5 2.2 3.6 Type DISPOSABLE OR PERMANENT 1 Size 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 Filter Permanent Type Kit 1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK Shipping / Operating Weight (lbs.) - N Models 128/122 132/126 139/133 162/156
Resumo do conteúdo contido na página número 7
255029-YTG-M-0610 ELECTRICAL DATA - 208/230-1-60 1 kW Staging Total Heat Heater Max. Min. Speed Models kW MBH W1 Only W2 Only W1 + W2 Models* Static Tap 208V 240V 208V 240V 208V 240V 208V 240V 208V 240V 4HK*6500206 0.5 Lo 1.9 2.5 6.4 8.5 1.9 2.5 1.9 2.5 1.9 2.5 AHP18B**H21 4HK*6500506 0.5 Med 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8 4HK*6500806 0.5 Med 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5 4HK*6500206 0.5 Lo 1.9 2.5 6.4 8.5 1.9 2.5 1.9 2.5 1.9 2.5 4HK*6500506 0.5 Lo 3.6 4.8 12.3 16.4 3.6
Resumo do conteúdo contido na página número 8
255029-YTG-M-0610 ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60 Field Wiring Heater Heater 1 Models Amps Min. Circuit Ampacity 75°C Wire Size - AWG Max. O.C.P. Amps/Type Models* 240V 208V 240V 208V 240V 208V 240V 4HK*6500206 10.4 13.5 15.4 15 20 12 12 AHP18B**H21 4HK*6500506 20.0 23.8 27.4 25 30 10 10 4HK*6500806 31.3 36.0 41.5 40 45 8 8 4HK*6500206 10.4 13.0 14.9 15 15 12 12 4HK*6500506 20.0 23.4 26.9 25 30 10 10 AHP24B**H21 4HK*6500806 31.3 35.6 41.0 40 45 8 8 4
Resumo do conteúdo contido na página número 9
255029-YTG-M-0610 ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60 1 Min. Circuit Ampacity 75°C Wire Size - AWG Max. O.C.P. Amps/Type Circuit Circuit Circuit Heater Models Models 1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240 AHP24B**H21 4HK16501306 40.9/47.0 19.5/22.5 – 45/50 20/25 – 8/8 10/10 – 4HK16501306 41.6/47.9 19.5/22.5 – 45/50 20/25 – 8/8 10/10 – AHP30B**H21 4HK165N1506 45.8/52.8 21.7/25.0 – 50/60 25
Resumo do conteúdo contido na página número 10
255029-YTG-M-0610 ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60 Field Wiring Heater Heat Kit - 1 Models Amps Min. Circuit Ampacity 75°C Wire Size - AWG Max. O.C.P. Amps/Type Three Phase 240V 208V 240V 208V 240V 208V 240V AHP24B**H21 4HK06501025 23.1 27.1 31.3 30 35 10 8 4HK06501025 23.1 26.8 30.8 30 35 10 8 AHP30B**H21 4HK065N1525 34.7 40.0 46.1 40 50 8 8 4HK06501025 23.1 27.5 31.6 30 35 10 8 AHP36C**H21 4HK06501525 34.7 40.0 46.1 40 50 8 8 4HK06501025 23.1 29.1 3
Resumo do conteúdo contido na página número 11
255029-YTG-M-0610 CONTROL WIRING - AHP or MA Series Air Handler And Newer UPG Single Stage HP Systems Single Stage H/P with Standard Demand Defrost Control Board AIR HANDLER HEAT PUMP THERMOSTAT BOARD R R R G G Y Y/Y2 Y Y1 W2 W2 W1 66 E W1 W W/W1 O O O * HUMIDISTAT HUM X/L X/L X/L C C COM SINGLE-STAGE COOLING WIRING * Optional dehumidification humidistat switch contacts open on rise. Notes: 1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60
Resumo do conteúdo contido na página número 12
Subject to change without notice. Published in U.S.A. 255029-YTG-M-0610 Copyright © 2010 by Johnson Controls, Inc. All rights reserved. Supersedes: 255029-YTG-L-0708 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069