Model 1300/1400
OWNERS MANUAL
SOLID FUEL
WARM AIR FURNACE
*FOR PARALLEL INSTALLATION WITH
EXISTING FORCED AIR-GAS OR OIL
FIRED FURNACE (U.S. ONLY)
*FOR INSTALLATION AS A CENTRAL FURNACE
*CERTIFIED UNDER ANSI/UL 391 & CAN/CSA-B366.1-M91
IMPROPER INSTALLATION MAY VOID
CAUTION:
YOUR WARRANTY
READ ALL INSTRUCTIONS CARE-
FULLY BEFORE STARTING THE
INSTALLATION OR OPERATING DO NOT USE THIS FURNACE
THE FURNACE IN A MOBILE HOME OR TRAILER
UNITED STATES STO
Resumo do conteúdo contido na página número 2
CONGRATULATIONS! You've purchased one of America's Finest Wood and Coal Burning Furnaces. By heating with wood and coal you're helping CONSERVE AMERICA'S ENERGY! Wood is our Renewable Energy Resource. Please do your part to preserve our wood supply. Plant at least one tree each year. Future generations will thank you. NOTE: YOUR UNIT MUST BE INSTALLED BY A QUALIFIED FURNACE INSTALLER. TOOLS AND MATERIALS NEEDED TOOLS MATERIAL Pencil 6" Pipe, 6" Elbow, Collar and Thimble; 6 Foot Folding Rul
Resumo do conteúdo contido na página número 3
Caution Labels Your Furnace has the following labels. Read and Obey all labels. DANGER: RISK OF FIRE OR EXPLOSION. DO NOT burn garbage, gasoline, drain oil, or other flammable liquids. WARNING: FIRE HAZARD. DO NOT operate with fire draft exceeding .06 inches w.c. DO NOT operate with fuel loading or ash removal doors open. DO NOT store fuels, paints, thinners, flammable liquids, or other highly volatile substances in the furnace room. CAUTION: HOT SURFACES Keep children aw
Resumo do conteúdo contido na página número 4
Rules for safe installation and operation Read these rules and the instructions carefully. Failure to follow them will cause a hazard that could result in death, serious bodily injury, and/or property damage. 1. Check your local codes. The installation must comply with their rulings. 2. Do not install this furnace in a mobile home or trailer. 3. Always connect this furnace to a chimney and vent to the outside. Never vent to another room or inside a building. 4. Do not connect this furnace
Resumo do conteúdo contido na página número 5
HOW THE FURNACE FUNCTIONS PARALLEL INSTALLATION: (U.S. ONLY) Your HOTBLAST Furnace is designed (See Optional Wiring Diagram, Page 16, Fig. to be a supplemental or central heating source 15) The design is such that when the blower for your home. This Solid Fuel Furnace may comes on, the blower on the central system be installed in conjunction with a properly also comes on. The blower will only come on operating central furnace that is listed or cer- when the temperature in the plenu
Resumo do conteúdo contido na página número 6
DIMENSIONS OF FURNACE 41" Figure 1A Figure 1A 1300 1300 24-7/8" 21-1/32" 1-3/4" 33-7/8" 40-11/16" 9" 49-1/8" Figure 1B Figure 1B 1400 1400/1500 32-1/8" 24-1/16" 1-3/4" 33-7/8" 40-11/16" 9" 6
Resumo do conteúdo contido na página número 7
Locating the Furnace 18" 6" CHIMNEY 1. The furnace should be located in the same room as the central system and as close as possible, but not CENTRAL 12" 9" FURNACE closer than 9". There should be no wall between the furnace and the warm air outlet duct that is connected directly to the warm air outlet plenum of the central furnace. (See Fig. 2) 48" 2.The unit will require installation with the following clearances: Figure 2 Unit to sidewall............12"(305mm) Unit to backwall...........30"(
Resumo do conteúdo contido na página número 8
THIMBLE 6" ELBOW 6" SOLID DAMPER 6" BAROMETRIC DRAFT REGULATOR (OPTIONAL) 6" CHIMNEY NON-COMBUSTIBLE CONNECTOR WALL 6" ELBOW Chimney Connection Fig. 4 MASONRY CHIMNEY Before using an existing masonry chimney, clean the chimney and inspect the flue liner to be sure it is safe to use. Make repairs before attaching the furnace. See page 4, item 5. Look at Fig. 4. The connector pipe and fitt
Resumo do conteúdo contido na página número 9
Rules for Connector Pipe Installation NOTE: 1. The crimped end of the chimney connector fits A flue pipe shall not pass through an attic, inside the furnace flue collar. Install additional chim- roof space, closet or similar concealed space, a floor or ceiling of combustible construc- ney connectors and elbow with the CRIMPED END tion. Where passage through a wall or parti- TOWARD THE FURNACE. This will allow any tion is desired, installation must conform condensation in the flue to run back
Resumo do conteúdo contido na página número 10
CONNECTION OF CHIMNEY CONNECTOR TO A MASONRY CHIMNEY THROUGH A COMBUSTIBLE WALL Figure 8 shows how to connect the chimney connector of a heater to a masonry chimney through a combustible wall. There are five allowable ways that a chimney connector can be connected to a masonry chimney by passing through a combustible wall. NFPA Standard 211 allows the following wall pass-through systems. FIGURE 8 - CONNECTION OF CHIMNEY CONNECTOR TO A MA- SONRY CHIMNEY THROUGH A COMBUSTIBLE WALL CEILING SEE PAR
Resumo do conteúdo contido na página número 11
PART A, FIGURE 8 MINIMUM CHIMNEY CLEARANCE TO (FIGURE 8 CONTINUED ON NEXT PAGE) BRICK AND COMBUSTIBLES IS 2 IN. MINIMUM CLEARANCES 12 IN. OF BRICK ALL AROUND CHIMNEY CONNECTOR TO HEATER FIRE CLAY LINER MINIMUM 12 IN. (5/8" MIN. WALL THICKNESS) TO COMBUSTIBLES MASONRY CHIMNEY CONSTRUCTED TO MIN. 3-1/2" THICK BRICK NFPA 211 MASONRY WALL 1. Use a minimum 3-1/2" thick brick masonry wall framed into the combustible wall. A fireclay liner (ASTM C315 or equivalent) having a 5/8" minimum wall thickness
Resumo do conteúdo contido na página número 12
AIR SPACE PART B MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN. FIGURE 8 - (FIGURE 8 CONTINUED) FACTORY-BUILT MINIMUM CLEARANCE CHIMNEY LENGTH 9 IN. ALL AROUND NONSOLUBLE CHIMNEY CONNECTOR REFACTORY TO HEATER CEMENT CHIMNEY LENGTH FLUSH WITH INSIDE USE CHIMNEY MFRS. PARTS TO OF FLUE AIR SPACE ATTACH CONNECTOR SECURELY 9 IN. MINIMUM SOLID INSULATED, LISTED FACTORY-BUILT CHIMNEY LENGTH MASONRY CHIMNEY CONSTRUCTED SHEET STEEL SUPPORTS TO NFPA 211 (24 GAUGE M
Resumo do conteúdo contido na página número 13
Assembly of Furnace Your furnace requires the following items to be assembled or installed by the service person: Feed Door Pull Handle Feed Door Locking Handle Blower(s) and Blower Controls Electrical Connections Remove all parts from inside the furnace 1. Fig. 9 and inspect for damage, including the firebrick as some breakage could occur during shipment. Assemble the feed door pull handle as 2. shown in Figure 9. Install thermostat assembly and cover (complete with handle) as illustrated
Resumo do conteúdo contido na página número 14
LOAD LOAD FAN LIMIT FAN "OFF" LIMIT BREAK OFF INDICATOR INDICATOR LINE JUMPER FOR LINE LOW VOLTAGE FAN "ON" INDICATOR Honeywell LIMIT SWITCH R2 R1 WIRE COLOR CODE WIRE NUTS G- GREEN- GROUND WIRE COLOR CODE B- BLACK- POWER SUPPLY G - GREEN - GROUND W- WHITE- POWER SUPPLY B - BLACK - POWER SUPPLY R1- WHITE- FAN CONTROL W - WHITE - POWER SUPPLY GROUND R2- BLACK- FAN CONTROL R1 - WHITE - FAN CONTROL G M1- BLACK- BLOWER MOTOR R2 - BLACK - FAN CONTROL B G M1 - BLACK - BLOWER MOTOR M2- WHITE- BLOWER MO
Resumo do conteúdo contido na página número 15
Installation Pipe to combustible: Please see all methods of Installation in Sides: 18"(460mm) Appendix at the rear of this booklet. Back: 18"(460mm) This is a furnace, not a free standing stove. The installation must be made only on a noncom- You must direct heated air from 8" outlets away from bustible floor. the furnace, or it will not function properly. d) Install the smoke pipe connector to the chim- ney with
Resumo do conteúdo contido na página número 16
PLENUM 6" MIN. TO Figure 14 18" MIN. CEILING 2" MIN. AIR SPACE REQUIRED BY CODE CENTRAL FURNACE TO GAS/OIL/ELECTRIC TRANSFORMER AND Figure 15 COMBUSTION FAN OF SOLID FUEL UNIT COMBINATION CONTROL LIMIT H POWER SUPPLY JUMPER IN N FAN GAS/OIL/ELECTRIC POWER SUPPLY JUNCTION BOX CAUTION! DO NOT CONNECT PLENUM FAN CONTROL SWITCH ACROSS FURNACE LIMIT CONTROL. FURNACE BLOWER MOTOR Power Failure Instructions: Operation after loss of power-- 1. Remove filter if provided 2. Do not
Resumo do conteúdo contido na página número 17
CAUTION Operating Instructions GASES THAT ARE DRIVEN FROM FRESH FUEL, Model 1300 COAL MUST BE BURNED OR THEY WILL Egg size (1-3/16" or larger) bituminous coal ACCUMULATE AND EXPLODE. NEVER SMOTHER A FIRE WHEN ADDING FRESH for residential furnaces, or any of the specially COAL. packed fireplace coals can be used. Coal with a low ash content (2% to 6%) is recommended. FUEL, Model 1400 CAUTION Hardwood, 18" to 26" should be split and air dried DO NOT OPERATE WITH THE FEED AND/OR (seasoned) for 6
Resumo do conteúdo contido na página número 18
Service Hints If the chimney is operating too cool, water Do not expect a furnace to draw. It is the 4. chimney that creates the draft. Smoke spillage will condense in the chimney and run back into the furnace. Creosote formation will be into the house or excessive buildup of water or rapid and may block the chimney. Operate creosote in the chimney are warnings that the chimney is not functioning properly. Correct the the furnace at a high enough fire to keep the chimney warm, preventing th
Resumo do conteúdo contido na página número 19
13 27 14a 12 29 15 28 16 7 33 24 26 6 8 5 3 9 30 25 4 30 34 23 2 32 Model 1300 Repair Parts 11 10 19 35 1 20 17 18 22 21 31 14 14b 14c 37 38 36 19
Resumo do conteúdo contido na página número 20
PARTS LIST MODEL 1300 (SEE DIAGRAM, PAGE 19) KEY PART # DESCRIPTION QTY. 1 22684 CABINET LEFT SIDE 1 2 22682 CABINET BACK PANEL 1 22762 3 FORCED DRAFT RING 1 4 88032 FLUE COLLAR GASKET 1 5 40246 FLUE COLLAR 1 6 22761 FLUE COLLAR RING 1 83227 N/S BOLT (1/4-20 X 1) 6 83250 N/S KEP NUT (1/4-20) 6 7 22683 CABINET TOP PANEL 1 8 22685 CABINET RIGHT SIDE 1 9 22662 FEED DOOR HINGE BRACKET 1 23800 10 SMOKE CURTAIN 1 83337 N/S BOLT (5/16-18 X 1) 2 N/S 83338 LOCKNUT (5/16-18) 2 11 68218 ASH DOOR ASSEMBLY 1