Resumo do conteúdo contido na página número 1
www.regency-fi re.com
Owners &
Freestanding Woodstoves
Installation Manual
MODELS: F1100S F3100L S3100L
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
908-288b FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4 02/22/06
Resumo do conteúdo contido na página número 2
Thank-you for purchasing a REGENCY FIREPLACE PRODUCT. The pride of workmanship that goes into each of our products will give you years of trouble-free enjoyment. Should you have any questions about your product that are not covered in this manual, please contact the REGENCY DEALER in your area. Keep those REGENCY FIRES burning. SAFETY NOTES: If this woodstove is not properly installed, a house fi re may result. For your safety, follow the installation instructions, contact local building or
Resumo do conteúdo contido na página número 3
TABLE OF CONTENTS SAFETY LABEL PARTS LIST Safety Label For F1100S ...............................................4 F1100 & F3100 Stove Main Assembly .........................22 Safety Label For F3100L ...............................................5 S3100 Step Stove Main Assembly ..............................23 Safety Label For S3100L ...............................................6 Pedestal, Bottom Shield & Leg Options ......................24 Firebrick ........................................
Resumo do conteúdo contido na página número 4
SIDEWALL SIDE SAFETY LABEL SAFETY LABEL FOR F1100S This is a copy of the label that accompanies We have printed a copy of the contents here NOTE: Regency units are constantly being each Regency Small Freestanding Woodstove for your review. improved. Check the label on the unit and if (F1100S). there is a difference, the label on the unit is the correct one. duplicate serial number 100 DO NOT REMOVE THIS LABEL LISTED SPACE HEATER, SOLID FUEL TYPE, ALSO SUITABLE FOR MOBILE HOME INSTALLATION 10
Resumo do conteúdo contido na página número 5
SIDEWALL SIDE SAFETY LABEL SAFETY LABEL FOR F3100L This is a copy of the label that accompanies We have printed a copy of the contents here NOTE: Regency units are constantly being each Regency Large Freestanding Woodstove for your review. improved. Check the label on the unit and if (F3100L). there is a difference, the label on the unit is the correct one. 102 DO NOT REMOVE THIS LABEL LISTED SPACE HEATER, SOLID FUEL TYPE, SUITABLE FOR MOBILE HOME INSTALLATION 102 MODEL: REGENCY LARGE FRE
Resumo do conteúdo contido na página número 6
SAFETY LABEL SAFETY LABEL FOR S3100L This is a copy of the label that accompanies We have printed a copy of the contents here NOTE: Regency units are constantly being each Regency Large Freestanding Step Wood- for your review. improved. Check the label on the unit and if stove (S3100L). there is a difference, the label on the unit is the correct one. Regency Freestanding Woodstove 6
Resumo do conteúdo contido na página número 7
INSTALLATION 12) A chimney connector cannot pass through an fuels. For other types of chimneys check with RESIDENTIAL attic or roof space, closet or similar concealed your local building code offi cials. Do not con- space, or a fl oor, ceiling, wall or partition of fuse a chimney with a type “B” Venting System INSTALLATION combustible construction. In Canada, if pas- used for gas appliances as suitable for a wood 1) Read all instructions before installing your sage through a wall, or parti
Resumo do conteúdo contido na página número 8
INSTALLATION MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS Please read the section below carefully as clearances depend on whether the airmate or the rear heat defl ector is installed on the stove. Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall. Residential Installation “C” Vent (Single Wall) Unit From Unit From Corner From Flue Center-line A B C D E F Small F1100S with
Resumo do conteúdo contido na página número 9
INSTALLATION Minimum Alcove Clearance to Combustible Materials The Regency Freestanding models have been alcove approved and must be installed with a listed double wall connector to the ceiling level. Note: Minimum alcove ceiling height - 84" Maximum depth of alcove - 36" From From Flue Min. Min.Hearth Unit Unit Center-line Width to Rear Wall G H I J K L Small F1100S with Airmate 11" 7" 23" 13.5" 46" 39" wit
Resumo do conteúdo contido na página número 10
INSTALLATION Pedestal Assembly Rear Heat Defl ector Assembly STOVE ASSEMBLY Small 850-115 for F1100 & F3100 Large 850-315 PRIOR TO Small 815-555 1) For easier assembly, tip the stove on its INSTALLATION Large 815-556 back (onto a soft surface to prevent scratch- ing). All units require either the pedestal or 4 legs at- The rear heat defl ector is supplied with the stove tached to the base. The F1100 and F3100 stoves and must be installed unless the optional airmate Hint: If you have
Resumo do conteúdo contido na página número 11
INSTALLATION 8) To complete your chimney installation, install Leg and Bottom Shield Assembly STEP BY STEP the double wall connector pipe from the stove’s fl ue collar to the chimney support Bottom Shield CHIMNEY AND device. Small 850-121 CONNECTOR Large 850-321 9) If you are using a horizontal connector, INSTALLATION the chimney connector should be as high Legs (set of 4) as possible while still maintaining the 18" Steel - Painted Black 850-125 Note: These are a generic set of chi
Resumo do conteúdo contido na página número 12
INSTALLATION MASONRY CHIMNEY Ensure that a masonry chimney meets the mini- mum standards of the National Fire Protection Association (NFPA) by having it inspected by a professional. Make sure there are no cracks, loose mortar or other signs of deterioration and blockage. Have the chimney cleaned before the stove is installed and operated. When connecting the stove through a combustible wall to a masonry chimney, special methods are needed. Ensure that an effective vapour barrier at the
Resumo do conteúdo contido na página número 13
INSTALLATION COMBUSTIBLE WALL CHIMNEY CONNECTOR PASS-THROUGHS Method A: 12" (304.8 mm) Clearance to Combustible Wall Member: Using a minimum thickness 3.5" (89 mm) brick and a 5/8" (15.9 mm) minimum wall thickness clay liner, construct a wall pass-through. The clay liner must conform to ASTM C315 (Standard Specifi cation for Clay Fire Linings) or its equivalent. Keep a minimum of 12" (304.8 mm) of brick masonry between the clay liner and wall combustibles. The clay liner shall run from the
Resumo do conteúdo contido na página número 14
INSTALLATION TABLE 1 MINIMUM RECOMMENDED FLUE HEIGHTS IN FEET (Measured from the top of the unit) # OF ELBOWS ELEVATION (FT) o o o o o o ABOVE SEA LEVEL 0 2 x 15 4 x 15 2 x 30 4 x 30 2 x 45 4 x 45 0-1000 12.0 13.0 14.0 15.0 18.0 16.0 20.0 1000-2000 12.5 13.5 14.5 15.5 19.0 16.5 21.0 2000-3000 13.0 14.0 15.0 16.0 19.5 17.0 21.5 3000-4000 13.5 14.5 15.5
Resumo do conteúdo contido na página número 15
INSTALLATION LISTED COMPONENTS FOR MOBILE HOME INSTALLATION The Regency Small and Large Freestanding pedestal units are approved for installation in a Mobile Home if one of the following pipe systems is used. AMERI-TEC HS U.S. Installation* Canadian Installations* Qty.Part # Description 1 6DCC Connector METALBESTOS SSII SECURITY S2100 (see above for details) 1 6HSRS-12 Roof Support (6PLRS-12-BK) Qty. Part # Description 1 6DS-VK Connector Kit 1 6F Flashing ICC EXCEL 2100 (see above for detail
Resumo do conteúdo contido na página número 16
INSTALLATION Small Stoves F1100S BRICK FLUE BAFFLE & 1) If the two air tubes are installed continue on SECONDARY AIR TUBE to Step 2), if not, follow the instructions below. INSTALLATION Install the air tube into the holes in the side channels. The notch goes on the right hand The fl ue baffl e system located in the upper area side with the air holes facing toward the door. of the fi rebox is removable to make cleaning Slide the tube into the left hand side, as far your chimney system easier
Resumo do conteúdo contido na página número 17
INSTALLATION Pedestal Ash Drawer Kit (850-100) BRICK INSTALLATION 1) Remove the bricks from the fl oor of the Firebrick is included to extend the life of your fi rebox. stove and radiate heat more evenly. Check to see that all fi rebricks are in their correct posi- 2) If using ashdrawer, discard cover plate. tions and have not become misaligned during shipping. 3) Remove the ash dump cover plates (one inside the fi rebox and one on the underside The "AD" brick in the drawings above is the
Resumo do conteúdo contido na página número 18
White Low (Red) High (Black) INSTALLATION Blower/Fan (846-515) 1) Remove the two screws from the top of the fan housing. 2) Slide the fan up into the rear heat shield. 3) After aligning holes, secure the fan to the rear heat shield using the two screws removed earlier. Note: The connection cord should not be in contact with any hot surfaces. NOTE: This appliance, when installed, must Read the operating instructions for the fan be electrically grounded in accordance with local codes or, in
Resumo do conteúdo contido na página número 19
OPERATING INSTRUCTIONS good updraft in the fl ue to establish the fi re. 13) All fuel burning appliances consume oxygen OPERATING (Leaving the door slightly open will help your during operation. It is important that you fi re start more rapidly.) supply a source of fresh air to your unit INSTRUCTIONS while burning. A slightly opened window is CAUTION: Never leave unit unattended suffi cient for the purpose. If you also have With your unit now correctly installed and safety if door is left
Resumo do conteúdo contido na página número 20
OPERATING INSTRUCTIONS Bottom Shield (with Legs) Units: 8) The stove consumes air while operating, ASH DISPOSAL To remove the drawer, lift slightly and slide provide adequate ventilation with an air it out, and carry it away. duct or open a window while the stove is in During constant use, ashes should be removed use. every few days. The Ash Drawer option features a convenient ash dump for easy removal of ash, 9) Do not connect this unit to a chimney fl ue refer to the "Modular Options