MODELS (A)JWSH100150 THRU (A)JWSH100250
SERIES 100 AND 101
COMMERCIAL GAS WATER HEATER
GAS-FIRED POWER BURNER
FOR DOMESTIC HOT WATER
• INSTALLATION • OPERATION • SERVICE • MAINTENANCE • LIMITED WARRANTY
WARNING: If the information in these
instructions is not followed exactly, a fire
or explosion may result causing property
damage, personal injury or death.
– Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other applian
Resumo do conteúdo contido na página número 2
MODELS (A)JWSH100150 THRU (A)JWSH100250 ROUGH-IN-DIMENSIONS GAS VALVE PIPING (A)JWSH100150, (A)JWSH100199, & 3/4" NPT (A)JWSH100250 Table 1. RECOVERY CAPACITIES - NATURAL GAS / L.P. TEMPERATURE RISE - DEGREES F - GALLONS PER HOUR Approx. Input Gas Model Gallon BTU/Hr. Usage 30 40 50 60 70 80 90 100 110 120 130 140 Capacity (A)JWSH100150 150,000 nat/lp 100 576 432 345 288 247 216 192 173 157 144 133 123 (A)JWSH100199 199,900 nat/lp 100 767 575 460 384 329 288 256 230 209 192 177 164 (A)JWSH10
Resumo do conteúdo contido na página número 3
TABLE OF CONTENTS PAGE PAGE ROUGH-IN DIMENSIONS ................................................................. 2 Thermometers ............................................................................... 13 FOREWORD ..................................................................................... 2 R
Resumo do conteúdo contido na página número 4
temperature be set for the lowest temperature which satisfies your hot water DISHWASHING MACHINE REQUIREMENT needs. This will also provide the most energy efficient operation of the water heater and minimize scale formation. All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between SETTING THE WATER HEATER TEMPERATURE AT 120°F/49°C WILL 15 and 25 pounds per square inch (103 Kpa and 173 Kpa). Flow pressures RE
Resumo do conteúdo contido na página número 5
LOCATING THE HEATER WARNING THIS WATER HEATER IS A CONDENSING UNIT AND REQUIRES A DRAIN WARNING THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS TO BE LOCATED IN CLOSE PROXIMITY TO ALLOW THE CONDENSATE GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS TO DRAIN SAFELY. THE CONDENSATE DRAINS FROM THE UNIT AT WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE THE EXHAUST ELBOW LOCATED AT THE BOTTOM OF THE UNIT. NOTE: DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR IT IS IMPORTAN
Resumo do conteúdo contido na página número 6
If the confined space is within a building of tight construction, air for combustion HARD WATER and ventilation must be obtained from outdoors. When directly communicating with the outdoors through vertical ducts, two permanent openings, located Where hard water conditions exist, water softening or the threshold type of in the above manner, shall be provided. Each opening shall have a free water treatment is recommended. This will protect the dishwashers, coffee area of not less than one
Resumo do conteúdo contido na página número 7
CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOMMENDED. CANADIAN POWER VENT FIGURE 5. CANADIAN DIRECT VENT FIGURE 6. 7
Resumo do conteúdo contido na página número 8
NOTE: TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING IMPORTANT TO THE AIR INTAKE IN WINDY/COLD AREAS, THE MAXIMUM The vent system must terminate so that proper clearances are maintained PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS as cited in local codes or the current editions of the National Fuel Gas Code, RECOMMENDED. ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, FOR ALL CAN/CSA-B149.1. MODELS Installation of this water heater must comply with CAN/CSA B149.
Resumo do conteúdo contido na página número 9
5. Glue the intake vent terminal to the section of the pipe. VERTICAL VENT TERMINAL INSTALLATION 6. Slide the wall plate over the pipe to stop against intake vent terminal. IMPORTANT 7. Place a bead of caulking (not supplied) around the gap between the pipe WHEN TERMINATING THROUGH A ROOF, THE FOLLOWING and the wall. Place some of the caulking on the back of the plate to hold SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE it against the wall after installation. FOLLOWED. 8. If the
Resumo do conteúdo contido na página número 10
NOTE: for Water Heaters in locations with high ambient temperatures (above INSTALLATION OF VENT SYSTEM 100°F or 38°C) and/or insufficient dilution air, it is recommended that CPVC pipe and fittings marked ULC S636 compliant (MUST USE SUPPLIED VENT WARNING TERMINAL) be used. THE OPTIONAL INTAKE VENTING ARRANGEMENT AND THE 4. It is important that condensate not be allowed to buildup in the exhaust EXHAUST VENTING ARRANGEMENT MUST BE INSTALLED TO vent pipe. To prevent this from happening th
Resumo do conteúdo contido na página número 11
LOW GAS PRESSURE SWITCH CONTROLS AND SWITCHES (SEE FIGURE 12) All models are provided with four pressure switches. These switches are The Low Gas Switch (LGS) is a single-pole, normally open pressure switch essential to the safe and proper operation of the unit. All switches are wired that will close its contacts when a rising pressure of 5.0 in. (1.25Kpa) W.C. in series. The controller is set up to shut the unit down whenever there is a is encountered. The contacts will open when the pres
Resumo do conteúdo contido na página número 12
WARNING THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 10.5" (2.59 KPa) WATER COLUMN SUPPLY GAS PRESSURE. HIGHER GAS SUPPLY PRESSURES REQUIRE SUPPLEMENTAL REDUCING SERVICE REGULATION. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE GAS CONTROLS WHICH COULD RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM THE GAS VALVE MUST BE CHECKED FOR SAFE OPERATION. MAKE SUR
Resumo do conteúdo contido na página número 13
DISCONNECT THE APPLIANCE AND ITS MANUAL GAS SHUTOFF RELIEF VALVE VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45Kpa). GAS This heater is equipped with an approved temperature and pressure relief SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE valve. ASME ratings cover pressure relief. CSA ratings cover release rate HEATER. FOR TEST PRESSURES OF 1/2 PSIG (3.45Kpa) OR LESS, THE with temperature actuation. APPLIANCE NEED NOT BE DISCON
Resumo do conteúdo contido na página número 14
3. This unit may never be connected to any existing heating system or THE CONTROLLER TO MALFUNCTION. A HIGH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST. component(s) previously used with non-potable water heating MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT appliance. COVERED UNDER YOUR WARRANTY. 4. When the system requires water for space heating at temperatures higher The controller is wired to the heater as shown in Figure 15. The model and
Resumo do conteúdo contido na página número 15
USING THE ELECTRONIC CONTROLLER 1. Overview Interaction with the water heater controller is done through an up, a down, and three operation buttons. These buttons are illustrated to the right. Operation of the three lower buttons is defined immediately above them on the screen. The [UP] and [DN] buttons are used to navigate through the menus and make adjustments to the water heater. While the water heater is operating, the user interface will display the desktop screen (if there are no activ
Resumo do conteúdo contido na página número 16
2. Operating States In the main desktop screen, there are some specific Operating States that are indicated on the status line. These are summarized below: ACTION: 3. Adjusting the Operating Set Point Press Change then use the UP and DOWN buttons to change the Set The Operating Set Point of this water heater determines the regulated Point. temperature for the water in the tank. This parameter is adjusted in the Temperature menu. Items in this menu allow you to monitor different tem- perature
Resumo do conteúdo contido na página número 17
There are two types of conditions that can occur during operation. These 4. Changing the Display Units are Warnings and Faults: The display interface to the heater has the option of selecting between de- grees Fahrenheit and degrees Celsius for temperature displays. This can be • Warnings: This is a non-safety related condition that the control has found in the “Display Settings” menu. Also in this menu, you may adjust how detected that may cause the water heater to operate in a less than
Resumo do conteúdo contido na página número 18
ACTION: 7. Viewing the Fault History To get to the current fault information screen, press Menu. The controller for this water heater will store a history of ten of the last Fault and Warning conditions that occurred. This is stored in the Fault History. DISPLAY: Along with all the information about the fault, including a estimate time of when the fault occurred, information regarding the advanced diagnostics for that fault can be accessed at any time. ACTION: Press the DOWN button f
Resumo do conteúdo contido na página número 19
5. Check the vent system seams and joints and ensure that there is no OPERATING INSTRUCTIONS discharge of flue products into the room. IMPORTANT 6. Check the input rate. IT IS RECOMMENDED THAT A QUALIFIED SERVICE TECHNICIAN PERFORM THE INITIAL FIRING OF THE HEATER. AT THIS TIME THE For appliance installation locations with elevations above 6500 feet USER SHOULD ASK THE TECHNICIAN ANY QUESTIONS IN REGARD (1982 meters) refer to HIGH ALTITUDE INSTALLATIONS section of this TO THE OPERAT
Resumo do conteúdo contido na página número 20
HIGH ALTITUDE INSTALLATIONS WARNING UNDER NO CIRCUMSTANCES SHOULD THE INPUT EXCEED THE RATE SHOWN ON THE HEATER RATING PLATE. OVER FIRING COULD RESULT WARNING IN DAMAGE OR SOOTING OF THE HEATER. THE (A)JWSH100199 AND (A)JWSH100250 HEATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 10,100 ft. (3078 m). THE (A) CATHODIC PROTECTION JWSH100150 HEATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 7,700 ft. (2347 m). INSTALLATIONS ABOVE THESE CAUTION ALTITU