Resumo do conteúdo contido na página número 1
Installation & Operation Manual
Central Air Conditioner
10 to 13 SEER 1.5 to 5 Tons
Models: HC18-60A1VAR/S
HC18-60C1VAR
HC18-60D1VAR
No.0010572324
K
The information contained in this booklet is subject to change without notice.
Resumo do conteúdo contido na página número 2
! WARNING These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death. This product is designed and manufactured to permit installation
Resumo do conteúdo contido na página número 3
TABLE OF CONTENT 1.Introduction --------------------------------------------------------------------------------------- 1 2.Nomenclature for Model Number ------------------------------------------------------------- 1 3.Specification ------------------------------------------------------------------------------------- 2 4.Unit Inspection ----------------------------------------------------------------------------------- 5 5.Equipment Protection From Environment --------------------------------
Resumo do conteúdo contido na página número 4
3.SPECIFICATION The dimensions for the condensing unit are illustrated in Figure 1. Physical and electrical specifications are provided in Table 1 for 10 SEER systems respectively. Table 1: Model:HC18-60A1VAR/S 2 MODEL: HC18A1VAR HC24A1VAR HC30A1VAR HC36A1VAS HC42A1VAR HC48A1VAR HC60A1VAR Unit Supply Voltage 208/230-1-60 197 - 253 Normal Voltage Range Bristol Sanyo Bristol Sanyo Bristol Sanyo Compressor Brand Bristol H20R H29A 10.1 12.9 16.2 19.4 24.3 21.2 28.1 31.9 35.1 37.6 29.7 Minimum C
Resumo do conteúdo contido na página número 5
D W H Figure 1 Table 2:System Cooling Capacity Outdoor Unit With This Indoor Air handler Air Handler Compressor Model Number Cooling Capacity (Btu/h) SEER Rated Sensible Total CFM(Outdoor) brand HC18A1VAR HB2400VA1M20 Bristol 18000 13000 10 1850 Bristol HC24A1VAR HB2400VA1M20 17000 24000 10 1850 HC30A1VAR HB3000VA1M20 Bristol 20000 28000 10 1950 B
Resumo do conteúdo contido na página número 6
Table 4:System Cooling Capacity Outdoor Unit With This Indoor Air handler Model Number Air Handler Compressor Cooling Capacity (Btu/h) SEER Rated Sensible Total CFM(Outdoor) brand HC18C1VAR HB2400VC1M20 19000 Bristol 14820 12 1950 Bristol HC24C1VAR HB2400VC1M20 18720 24000 12 1950 HC30C1VAR HB3600VA1M20 Bristol 23400 30000 12 1950 Bristol HC36C1VAR
Resumo do conteúdo contido na página número 7
4.UNIT INSPECTION This product has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully. If damage is found, report immediately to the transportation agency. 5.EQUIPMENT PROTECTION FROM ENVIRONMENT The metal parts of the unit may be subject to rust or corrosion in adverse environmental conditions. This oxidation could shorten the unit life. Salt spray or mist in seacoa
Resumo do conteúdo contido na página número 8
Provide a level concrete slab. To prevent transmission of noise or vibration, slab should not be connected to building structure. Some sort of sound-absorbing material should be placed between the condenser and the slab. A good material to use is rubber and cork pad. For rooftop application, make sure the building construction can support the weight and that proper consideration is given to the weather-tight integrity of the roof. The condensing unit contains moving parts and can vibrate. Theref
Resumo do conteúdo contido na página número 9
OUTDOOR UNIT ADDITIONAL SUCTION LINE PITCH SUCTION LINE TOWARD OUTDOOR OIL TRAP FOR EACH 20 FOOT UNIT 1/2" FRO EVERY 10' OF LINE RISE OF PIPE INDOOR UNIT ABOVE OR LEVEL TO OUTDOOR UNIT 70' LIQUID LINE MAX. OUTDOOR UNIT SUCTION LINE OIL INDOOR UNIT TRAP WHEN INDOOR INDOOR UNIT UNIT IS 4 FEET OR LIQUID LINE MORE BELOW OUTDOOR UNIT A INDOOR UNIT BELOW OUTDOOR UNIT 6' B-1 INVERTED LOOP LIQUID LINE INDOOR UNIT 50' OUTDOOR UNIT MAX. SUCTION LINE Figure 3 B-2 Only refrigeration-grade copper piping (
Resumo do conteúdo contido na página número 10
Refrigerant Line Sizing Check the following table (Table 7) for correct suction and liquid line sizes for any combination of the unit size and the maximum refrigerant line length. Refrigerant Line Length (Ft) Unit Size 0 - 24 25 - 49 50 - 74 (Ton) Line Outside Diameter (In) Suction Liquid Suction Liquid
Resumo do conteúdo contido na página número 11
1.Tubing should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contamination from entering the system. 2.Make sure that both refrigerant stop valves at the outdoor unit are closed. 3.Push the tubing into the fitting until it stops. This prevents flux from getting into the system. 4.Remove the cap and Schrader valve core from the service port to protect the valve seals. 5.Wrap a wet rag around the valve stub before brazing. 6.Braze t
Resumo do conteúdo contido na página número 12
1.Fully open both shutoff valves. System Superheat 2.Connect service gage manifold to the valve service Ambient Return Air Temperature ( F) ports, being sure to evacuate lines. Temperature At 65 70 75 80 85 3.Startup the system (Refer to the Section 7 - "System Condenser Inlet ( F) Startup"). Run system at least 10 minutes to allo 60 17 25 30 33 37 pressur
Resumo do conteúdo contido na página número 13
The condensing unit rating plate and the tables of "Physical and Electrical Specifications / Outdoor Units" (Table 1 and 2) provide pertinent data necessary for the selection of proper size electrical service and over-current protection devices. Table 9 provides data on the minimum copper wire size as a function of supply wire length and circuit ampacity. Copper Wire Size - AWG (1% Voltage Drop) Supply Circuit
Resumo do conteúdo contido na página número 14
8.OPERATION Most single phase units are operated without start relay or start capacitor. Such systems should be off for a minimum of 5 minutes before restarting to allow equalization of pressures. The thermostat should not be moved to cycle unit without waiting 5 minutes. To do so may cause the compressor to stop on an automatic open overload device or blow a fuse. Poor electrical service can cause nuisance tripping in overloads or blow fuses. The compressor has an internal overload protector. U
Resumo do conteúdo contido na página número 15
Symptom Possible Cause Remedy Power off or loose electrical connection Make sure main switch is ON. Check and tighten all connections. Incorrect thermostat setting Set thermostat correctly No cooling Defective contactor Check for 24V at contactor coil.
Resumo do conteúdo contido na página número 16
SW-1 SW-2 HC18-60A1VAR/S HC18-60C1VAR HC18-60D1VAR Air Conditioner Wi ring Diagram LINE VOLTA GE FACTORY STANDARD 5 OPTIONAL FIELD INSTALLED ELECTRIC HEATER KIT OPTIONAL L1 BRK LOW VOLTAGE OFM FL BK 6 BK RD FACTORY STANDARD RD BR BK FIELD INSTALLED BK R FL M TL OPTIONAL RD S BR RD L2 TL YL USE COPPER CONDUCTORS ONLY RD C WARNING CABINET MUST BE PERMANENTLY GROUNDED 6 S RD RD AND ALL WIRING TO CONFORM TO I.E.C.,N.E.C.,C.E.C., BK RD R BK PU C.L.C. AND LOCAL CODES AS APPLICABLE. BL BR RD PU WH BK R
Resumo do conteúdo contido na página número 17
Made in P.R.C.