Resumo do conteúdo contido na página número 1
QTEC Wall Sleeve
Models: QWS48A
INSTALLATION
QWS48A-16
INSTRUCTIONS
QWS48A-19
QWS48A-23
QWS48A-30
Manual No.: 2100-319F
Bard Manufacturing Company
Supersedes: 2110-319E
Bryan, Ohio 43506
File: Vol. II Tab 14
Since 1914 . . . Moving ahead just as
Date: 11-07-05
planned.
© Copyright 2003
Manual 2100-319F
Page 1 of 10
Resumo do conteúdo contido na página número 2
CONTENTS Getting Other Information and Publications 3 Figures QTEC Wall Sleeve General Information Figure 1 Wood Framed Installation ..................... 4 Shipping Damage .................................................. 4 Figure 2 Application of Sealant to 2 x 6 Plate ..... 5 General .................................................................. 4 Figure 3 Application of Sealant to Flanges ......... 5 Installation Instructions Figure 4 Masonry Construction Installation ......... 6 Instal
Resumo do conteúdo contido na página número 3
Getting Other Information and Publications These publications can help you install the air FOR MORE INFORMATION, CONTACT THESE conditioner or heat pump. You can usually find these at PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard. 1712 New Hampshire Avenue, NW Washington, DC 20009 Telephone: (202) 483-9370 Standard for the Installation of ........... ANSI/NFPA 90A Fax
Resumo do conteúdo contido na página número 4
SHIPPING DAMAGE INSTALLATION – WOOD FRAMED WALLS Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is For wood frame construction walls, the dimensions of found, the receiving party must contact the last carrier the opening must be 48 inches tall by 43 inches wide. A immediately, preferably in writing requesting inspection 2 x 6 header will be required for the opening. The sides by the carrier’s agent. of the opening must have trimmer s
Resumo do conteúdo contido na página número 5
FIGURE 2 APPLICATION OF SEALANT TO 2 X 6 PLATE SLEEVE OPENING OUTSIDE WALL TREATED 2 X 6 BOTTOM SUPPORT AND SEAL PLATE APPLY CONSTRUCTION APPLY CONSTRUCTION ADHESIVE TO SEAL. ADHESIVE TO SEAL. APPLY CONSTRUCTION ADHESIVE TO SEAL. FRONT VIEW FIGURE 3 APPLICATION OF SEALANT TO FLANGES Manual 2100-319F Page 5 of 10
Resumo do conteúdo contido na página número 6
The sleeve is then reinserted into the prepared opening INSTALLATION – MASONRY from the outside of the building. All of the mounting CONSTRUCTION WALLS flanges must contact the exterior wall. Check to see For masonry construction walls, the dimensions for the that there is enough sealant to make this joint opening will be 48-1/4 inches tall by 43-1/4 inches wide. watertight. Additional sealant must be applied as These dimensions are plus or minus 1/4 inch and are necessary. The sleeve must b
Resumo do conteúdo contido na página número 7
sealant must be applied as required. The sleeve must be square in the opening. A slope is built into the bottom of the sleeve from the inside to the outside. This will allow anchored to the wall. All four mounting flanges must be fastened with two fasteners each to the outside wall. any water that gets into the sleeve to drain out. Once the test fitting has been checked out, the sleeve should be The gaps between the side flanges, and the top and bottom flanges must be sealed to the wall. re
Resumo do conteúdo contido na página número 8
INSTALLATION WITH 16" THICK WALLS INSTALLATION WITH 23" THICK WALLS When an application is required on a building with 16" wall, When an application is required on a building with 23" wall, a Wall Sleeve model number QWS48A-16 is required. a Wall Sleeve model number QWS48A-23 is required. The installation of the QWS48A-16 is similar to the The installation of the QWS48A-23 is similar to the QWS48A with one exception. A condenser fill plate is QWS48A with one exception. A condenser fill plate i
Resumo do conteúdo contido na página número 9
drain of the QTEC. This system allows the QTEC unit to ACCESSORY ITEM be installed or removed from the sleeve without The QCDS48 is a condensate disposal system for use on connecting or disconnecting the drain line. all QTEC models. The system consists of a drain box The installation of the QCDS48 requires that a recessed and a rear drain assembly. The drain attaches to the side area next to the sleeve opening be built. See Figure 7 for of the sleeve. The drain box has a rear drain and an di
Resumo do conteúdo contido na página número 10
To use this method, discard the two side mounting ATTACHMENT OF WALL SLEEVE TO QTEC UNIT brackets. Remove the nuts and washers from the threaded studs and retain for use later. Remove the All Wall Sleeve Models covered in this manual are lower cabinet door and locate the mating holes in the equipped with two different methods to attach the QTEC rear of the cabinet. It may be necessary to clear the Model being applied. holes of gasket material. The first method is with brackets supplied with t