Contents 1. Introduction ......................................................................3 2. Safety ................................................................................6 3. Presentation ......................................................................7 4. Installation.......................................................................10 5. Operation........................................................................ 16 6. Alarms ....................................
Resumo do conteúdo contido na página número 4
2
Resumo do conteúdo contido na página número 5
1. Introduction 1.1 Thank you! Thank you for selecting this uninterruptible power source (UPS). It is designed for many years of reliable, maintenance-free service. Important! Please read this manual. It provides safety, installation, and operating instructions that will help you get the fullest performance and service life from your UPS. This manual describes the inner workings of the UPS and how they relate to providing superior protection from utility power problems such as blackouts, brownou
Resumo do conteúdo contido na página número 6
1.3 Theory of Operation This high-performance, line-interactive, uninterruptible power source (UPS) provides clean, reli- able, AC power to computer systems and other electrical equipment — protecting them from power blackouts, brownouts, swells, sags, surges, and interference. It is designed to provide protec- tion for equipment that operates on 208 volts AC, as well as peripheral equipment requiring 120 volts AC. The UPS requires single phase 208 volts AC input for proper operation. Typically,
Resumo do conteúdo contido na página número 7
1.4 Features Intelligent Battery Management The UPS provides visual and audible indications of the battery’s present status including capacity, low battery condition, and replace battery condition. The UPS exercises the battery during its self-test, and detects a weak battery before it is put into service. The UPS normally performs a self-test at power up and every 14 days. Self-tests can also be conducted manually with the on/test button at any time. The UPS features user-replaceable batteries.
Resumo do conteúdo contido na página número 8
2. Safety CAUTION! ■ To reduce the risk of electric shock in conditions where load equipment grounding cannot be verified, disconnect the UPS from the AC power outlet before installing a computer interface or accessory slot signal cable. Reconnect the power cord only after all signaling connections are made. ■ Connect the UPS to a two-pole, three-wire grounding AC power outlet. The receptacle must be connected to appropriate branch protection (fuse or circuit breaker). Connection to any other
Resumo do conteúdo contido na página número 9
3. Presentation 3.1 Front panel With the UPS plugged in, press the on/test button to turn on the UPS and power the loads. See Sec. 5.1. On/test also activates the UPS’s self-test and utility line voltage displays. See sections 5.3 and 5.6. The overload LED lights when the loads connected to the UPS exceed the UPS’s capacity. See sec- tion 6.2. The battery charge/line voltage display shows the present battery charge as a percentage of battery capacity. See section 5.5. It also displays the voltag
Resumo do conteúdo contido na página número 10
3.2 Rear Panel Tower Models Rack Mount Models 8
Resumo do conteúdo contido na página número 11
Use the computer interface port for UPS monitoring and control. See section 7. The configuration button changes the UPS’s sensitivity to utility voltage variations and the low battery warning interval. See sections 5.9 and 5.10. The configuration LED indicates the voltage sensitivity setting and the low battery warning interval. See sections 5.9 and 5.10. The 120 VAC output circuit breaker trips when the connected load exceeds the rated capacity. The center plunger of the circuit breaker extends
Resumo do conteúdo contido na página número 12
4. Installation To obtain warranty coverage fill out and return the warranty registration card now. 4.1 Inspection Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is re- cyclable; save it for reuse or dispose of it properly. 4.2 Placement Tower Models Install the UPS in a protected area with adequate air flow and free of excessive dust. Do not oper- ate the UPS where the temperature and humidity is outside the specified limits. See section 12. Allow
Resumo do conteúdo contido na página número 13
Installing the Support Brackets 1. Verify the contents of the kit. It contains: two adjustable-length L-channel supports, eight clip nuts, eight 10-32 x 1/2” flat-head screws, and eight washers. The washers are for use with square rack holes only. 2. If the rack uses threaded holes, drill out the appropriate front rail rack holes with a 7/32” drill bit. This step is not required when mounting in racks with square holes. 3. Install clip nuts on the uppermost and lowermost holes at each end of the
Resumo do conteúdo contido na página número 14
4.3 Protection Strategies This UPS provides high performance power line protection to the loads. There are, however, other potential entry points for damaging surges in information systems. These include serial ports (RS- 232, RS-422, RS-485, etc.), parallel ports, telephone lines, and network connections. These other entry points must be considered in developing a comprehensive system protection strategy. Con- tact your dealer or call the number in the front of this manual for information on a
Resumo do conteúdo contido na página número 15
4.4 Install Accessory (Optional) Some UPS accessories connect to the computer interface (DB-9) port, while others install in the accessory slot. See the literature accompanying the accessory to determine proper installation. The screws holding the slot cover are #2 Phillips head type. To use the computer interface port, connect the accessory to the DB-9 connector and tighten down the connector’s screws. Connect the optional battery pack (3000 VA model only) according to the instructions with the
Resumo do conteúdo contido na página número 16
Completed XL installation with two battery packs. 4.6 Connect to Utility Plug the UPS into an L6-20 receptacle connected to a 208VAC, 20 Amp service. The service may be either 50 or 60 Hz, but it must be equipped with a safety ground. If the service at your location uses a receptacle other than an L6-20, the UPS plug may be replaced with an appropriate plug by a qualified individual. The UPS is not rated for more than 20 Amps and should not be connected to a service that supplies a higher curren
Resumo do conteúdo contido na página número 17
4.6 Charge the Battery The UPS charges its battery whenever it is connected to utility power. For best results, charge the battery for 2.5 hours before use. It is acceptable to use the UPS without first charging the battery, but on-battery run time may be reduced until the battery charges. 4.7 Connect the Loads Plug the loads into the output connectors on the rear of the UPS. To use the UPS as a master on/ off switch, make sure that all of the loads are switched on. Test the system with all load
Resumo do conteúdo contido na página número 18
5. Operation 5.1 Switch On With the UPS plugged in, press the on/test (upper) button to supply power to the loads. The loads are immediately powered while the UPS beeps and performs a self-test. See section 5.3. 5.2 Switch Off To switch off the UPS’s output power, press the off (lower) button. It may be convenient to use the on and off buttons of the UPS as a master on/off switch for the protected equipment. Note: The UPS is on (the internal processor is operating) whenever it is plugged in and
Resumo do conteúdo contido na página número 19
5.3 Self-test Use the self-test to verify both the operation of the UPS and the condition of the battery. With the UPS plugged in to normal utility power, activate the self-test by pressing the on/test button until the UPS beeps and the on-line LED flashes. Note: By default the UPS performs a self-test at power up and once every two weeks. During the self-test, the UPS briefly operates the loads on-battery (the on-battery LED comes on). If the UPS passes the self-test, it returns to on-line oper
Resumo do conteúdo contido na página número 20
5.5 Battery Charge Bar Graph The 5-LED display on the right of the front panel shows the present charge of the UPS’s battery as a percentage of the battery’s capacity. When all five LEDs light, the battery is fully charged. When the lowest LED is flashing, the battery can supply less than two minutes of run time for the load. 5.6 Utility Voltage Bar Graph This UPS has a diagnostic feature that displays the utility voltage. With the UPS plugged into the normal utility power, press and hold the on