                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 
APC Smart-UPS RT 
 
BID SPECIFICATIONS FOR 
3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC 
Uninterruptible Power Supply 
 
 
PART 1 - GENERAL 
1.1 SUMMARY 
A. This specification describes the operation and functionality of a continuous duty, single-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as 
the UPS. 
B. The UPS utilizes double conversion online topology designed to protect electronic 
equipment by sup
                    
                    Resumo do conteúdo contido na página número 2 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM  H. Configuration Specifics:     The UPS is available in one of the following configurations:   MODEL SKU #  TOWER  APC Smart-UPS RT 3000VA RM 230V SURT3000XLI  APC Smart-UPS RT 5000VA RM 230V SURT5000XLI  APC Smart-UPS RT 6000VA RM 230V SURT6000XLI  RACK MOUNT  APC Smart-UPS RT 3000VA RM 230V SURT3000RMXLI  APC Smart-UPS RT 5000VA RM 230V SURT5000RMXLI  APC Smart-UPS RT 6000VA RM 230V SURT6000RMXLI    1.2 STANDARDS  A. EN50091-1  B. EN50091-2  C. 
                    
                    Resumo do conteúdo contido na página número 3 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM  A. Online: The input PFC power stage and the output power stage (inverter) shall operate  in an on-line manner to continuously regulate power to the critical load. The input PFC  stage shall be capable of full battery recharge while simultaneously providing regulated  power to the load for all line and load conditions within the range of the UPS  specifications.   B. On Battery: Upon failure of the AC input source, the critical load shall continue
                    
                    Resumo do conteúdo contido na página número 4 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM  2.1 MECHANICAL DESIGN  A. The UPS is contained in a rugged steel cabinet with two plastic front bezels;  B. The UPS dimensions are 13 x 43 x 66cm (5.1 x 17 x 26 in.);  C. The UPS cabinet is capable of conversion between Tower and Rack-Mount  configurations;  2.2 SYSTEM CHARACTERISTICS  A. System Capacity:   1. The system is rated to be capable of supporting:  a. 3000VA or 2100W whichever limit is reached first (for the 3000VA  model).  b. 5000VA o
                    
                    Resumo do conteúdo contido na página número 5 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM    3. Output frequency: 50/60 +/- 3Hz tracking or 50/60 +/- 0.1Hz tracking (user  selectable);    4. AC output voltage distortion: Max. 2% @ 100% linear load; Max. 5% @ 100%  non-linear Load;    5. AC output static voltage regulation: +/-1%;    6. AC output dynamic voltage regulation: +/- 8% maximum for 100% load step at  less than 10ms recovery time;    7. Overload Rating:     a. Online: 105% - infinite; 125% - 1 minute; 150% - 30 seconds;    b. I
                    
                    Resumo do conteúdo contido na página número 6 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM  C. Input Current Limit:    1. The input converter shall control and limit the input current draw from utility to  150% of the UPS output. During conditions where input current limit is active,  the UPS shall be able to support 100% load, charge batteries at 10% of the UPS  output rating, and provide voltage regulation with mains deviation of up to +/- 20% of the nominal input voltage.    2. In cases where the source voltage to the UPS is nominal a
                    
                    Resumo do conteúdo contido na página número 7 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM  condition is removed from the critical bus output of the system. Automatic transfers of  load to bypass also take place if for any reason the UPS cannot support the critical bus.  D. Manual Transfers:  Manually initiated transfers to and from bypass may be initiated  through the UPS computer interface (via serial or USB communications) or by  engaging the bypass switch on the rear panel of the unit.  2.7 BATTERY  A. The UPS battery system is compr
                    
                    Resumo do conteúdo contido na página número 8 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM    6. Self-diagnostics, self-test and proactive fault detection;    7. Communication to the host server via serial port;    8. Communication to the Network Interface Card or another SmartSlot accessory  card if equipped.    9. Etc.  B. Display/Control Unit: A display/control comprised of 16 LEDs and 2 pushbutton  switches is located on the front side of the UPS. The display/control unit may be turned  90 degrees clockwise or counterclockwise to acc
                    
                    Resumo do conteúdo contido na página número 9 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM    6. The UPS is in fault state;    7. The battery needs to be replaced;    8. The battery capacity/utility voltage LED bar   G. Audible Alarms:  Using audio signal, the UPS will notify the user about important  events. The following is the list of distinct audio alarms:    1. The UPS is on battery;    2. The UPS is on battery and the remaining battery capacity is low;    3. The UPS has shutdown due to low battery capacity;    4. The battery needs 
                    
                    Resumo do conteúdo contido na página número 10 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM  3.2 SOFTWARE AND CONNECTIVITY  A. Network Adaptor: APC SmartSlot Network Management Card shall allow one or more  network management systems (NMS) to monitor and manage the UPS in TCP/IP  network environments.  B. Unattended Shutdown    1. The UPS, in conjunction with a network interface card, shall be capable of  gracefully shutting down one or more operating systems during when the UPS is  on battery mode.    2. The UPS is also capable of using 
                    
                    Resumo do conteúdo contido na página número 11 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM    7. TurboLinux v.7.0 and 8.0    8. Novell Netware 6.0 with Support Pack 1     9. Novell Netware 6.5     10. Novell Netware 5.1 with Support Pack 3 or above (using PowerChute Business  Edition v6.2.2 agent)     11. Sun Solaris 8 and 9  PART 4 - Part 4 - EXECUTION  4.1 FACTORY ASSISTED START-UP   If a factory assisted UPS start-up is requested, factory trained service personnel shall      perform the following inspections, test procedures, and on-s
                    
                    Resumo do conteúdo contido na página número 12 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM  1. Ensure proper system start-up.    2. Verify proper firmware control functions.    3. Verify proper firmware bypass operation.    4. Verify proper bypass switch operation (where applicable).    5. Verify proper inverter operation and regulation circuits.    6. Simulate utility power failure.    7. Verify proper charger operation.    8. Document, sign, and date all test results.    E. On-Site Operational Training: During the factory assisted star
                    
                    Resumo do conteúdo contido na página número 13 
                    
                        CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM  identification and operation, system controls and adjustment, preventative maintenance,  and troubleshooting.    End Of Section 16611  CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM