1015N-2MFM-1A
FIELD MANUAL
1015N-2M DIAL-UP MODEM
OPTION CARD
FOR SYSTEM 1010N
FLOWMETERS
FOR TECHNICAL ASSISTANCE
Call: (800) 275-8480
(631) 231-3600
Fax: (631) 231-3334
E-mail: TSG.ultrasonicflow@siemens.com
FOR GENERAL INFORMATION
Website: www.controlotron.com
E-mail: info.ultrasonicflow@siemens.com
Or: sales.ultrasonicflow@siemens.com
Copyright©2006 Siemens Energy & Automation, Inc. All Rights Reserved Made in the USA
Resumo do conteúdo contido na página número 2
IMPORTANT NOTICE Controlotron is now part of: Siemens Energy & Automation, Inc. Process Instrumentation Business Unit (PI BU) CoC Ultrasonic Flow 1015N-2M DIAL-UP MODEM OPTION CARD FOR SYSTEM 1010N FLOWMETERS This equipment contains components that are susceptible to electrostatic discharge (ESD). Please observe ESD control measures during the handling and connection process. Field Manual 1015N-2MFM-1A June 2006 For use with Operating System Software Version 2.00.15 or later Prepared By Date Re
Resumo do conteúdo contido na página número 3
Manual Changes NOTE: For the latest updates and revisions to this field manual go to www.controlotron.com/downloads.htm and check the Product Manual listing.
Resumo do conteúdo contido na página número 4
Table Of Contents 1015N-2MFM-1A TABLE OF CONTENTS Page 1. Introduction ......................................................................................................1 2. 1015N-2M Modem Card Setup......................................................................1 2.1 Option 1 Mounting Kit 1015N-2M-MK1 ......................................................1 2.2 Option 2 Mounting Kit 1015N-2M-MK2 ......................................................1 2.3 Option 3 Mounting Kit 10
Resumo do conteúdo contido na página número 5
1015N-2MFM-1A 1015N-2MFM-1 MODEM CARD INSTALLATION INSTRUCTIONS 1. INTRODUCTION The 1015N-2M Modem Card is one of three option cards used for remote communications within the Controlotron 1010N family of flowmeters. External communication is achieved through an on board dial-up miniature modem with asynchronous line speeds of 2400 bps, TM 1200 bps, or 300 bps. Implementation of Windows HyperTerminal or any other communication software allows for the direct control of the modem’s Hayes compatible
Resumo do conteúdo contido na página número 6
1015N-2MFM-1A TB1 Network Connection (2-Wire Hook Up) Con 2 Network Connection (RJ11 Connector) 1015N-2M Modem Card Captive Screws (4) Module ID Label Top View Side View Figure 1. 1015N-2M Modem Card and Attaching Hardware 3. TECHNICAL SPECIFICATIONS Interface: RS-232 Supply Voltage: 5 volts DC Supply Current: 48 mA Modem Line Speeds: 2400, 1200 and 300 bps Asynchronous DTE Rates: 2400, 1200, 300 bps Modulation: V.22bis, V.22, Bell 212A, Bell 103 Phone Line: Dial Up or 2 Wire Leased Line Exte
Resumo do conteúdo contido na página número 7
1015N-2MFM-1A 5.1 1015N-2M MODEM CARD INSTALLATION WARNING: Set flowmeter and instrumentation power to OFF when inserting or removing the 1015N-2M Modem Card. Before proceeding with the following installation procedures, identify the Module Loading option and installation drawing for your Modem Card (see Appendix A). The options are as follows: a. Module Loading Option 1 1010N-5 with 1010N-2 in 1010N/DN Type System. Use Mounting Kit 1015N-2M-MK1. Refer to Installation Drawing 1015N-2M-MK-7 (shee
Resumo do conteúdo contido na página número 8
1015N-2MFM-1A CAUTION: Do not connect a serial data cable to J1 on the 1015N-2M Modem Card or damage to the Modem Card and flowmeter may result. 4. Loosen the four captive screws (1) at the corners of the 1010N-2 module (7) and carefully lift out the module disengaging it from the connector on the 1010N-5 module (2). 5. Lift off the shield (3) covering the 1010N-5 module (2). 6. Leave the 1010N-5 module in place. Check to assure that the four corner standoffs (4) are securely threaded in place.
Resumo do conteúdo contido na página número 9
1015N-2MFM-1A 11. Install the 1015N-2M Modem Card (9) on top of the 1010N-2 module (7) carefully engaging connector P1 on the 1015N-2M with its mate P1 on the 1010N-2 module. Secure the 1015N- 2M by engaging its four captive screws with the four standoffs on the 1010N-2 module. 12. Install the large threaded cover mount standoff (10) from the mounting kit through the hole at the center of the 1015N-2M Modem Card (9) and into the threaded receptacle on the shield (5) previously installed in Step
Resumo do conteúdo contido na página número 10
1015N-2MFM-1A Serial Data Cable - Not used with 1015N-2M START VIEW Modem Card. FINISH VIEW (7) 1010N-2 I/O Module Cover (7) 1010N-2 I/O (4) 1015N-2M Module Cover Modem Card (2) 1010N-2 I/O (2) 1010N-2 I/O Module Assy Module Assy (8) Captive Screw (8) Captive Screw (5) Cover Mount Standoff (1) Captive Screws (3) Threaded Standoff (6) 1010N-1 Module Shield (6) 1010N-1 Module Shield Figure 4. Option 2 Installation (side view) 9. Install the large threaded
Resumo do conteúdo contido na página número 11
1015N-2MFM-1A 4. Loosen the four captive screws (1) at the corners of the 1010N-8M module (2) and carefully lift out the module disengaging it from the ribbon cable connecting it to the 1010N-2M module (3). 5. Leave the 1010N-2M module in place. Check to assure that the four corner standoffs (4) are securely threaded in place. CAUTION: Do not connect a serial data cable to J1 on the 1015N-2M Modem Card or damage to the Modem Card and flowmeter may result. ASSEMBLY (see Figure 5) 6. Remove the fo
Resumo do conteúdo contido na página número 12
1015N-2MFM-1A 8. Install the 1015N-2M Modem Card (7) on top of the 1010N-8M module (2) carefully engaging connector P1 on the 1015N-2M with its mate P2 on the 1010N-8M module. Secure the 1015N-2M by engaging its four captive screws (1) with the four standoffs (4) on the 1010N- 8M module. 9. Install the large threaded cover mount standoff (8) from the mounting kit through the hole at the center of the 1015N-2M Modem Card, through the standoff on the 1010N-8M module and then into the threaded rece
Resumo do conteúdo contido na página número 13
1015N-2MFM-1A 6. COMMUNICATIONS CONFIGURATION The 1015N-2M Modem Card has been pre-configured at the factory to allow for proper interface with Controlotron’s System 1010N flowmeters. CAUTION: The 1015N-2M Modem Card will not function properly if the precon- figured settings are altered. If the settings are altered, refer to reconfiguration procedure below. TM 7. WINDOWS HyperTerminal SETUP TM Step 1. Invoke HyperTerminal (generally found in the Program Files / Accessories Folder). Step 2. Give
Resumo do conteúdo contido na página número 14
Appendix A 1015N-2MFM-1A APPENDIX A “AT” COMMAND SET and “S” REGISTERS The command set for the 1015N-2M modems is fully compatible with the Hayes AT command set. The modem is controlled and configured by the AT (attention command). Each command consists of the following elements (with exception of the A/and the +++ command which will be discussed later). 1. The two character sequence AT 2. A command 3. A command parameter 4. A carriage return A command is not entered until a carriage return
Resumo do conteúdo contido na página número 15
Appendix A 1015N-2MFM-1A “AT” Commands Command Function Command Function Basic AT Commands X0 Report basic call progress result codes, i.e., OK, AI Re-execute command. CONNECT, RING, NO CARRIER (also, for busy, A Go of(-hook and attempt to answer a call. if enabled, and dial tone not detected), B0 Select V.22 connection at 1200 bps. NO ANSWER and ERROR. B1 Select Bell 212A connection at 1200 bps. X1 Report basic call progress result codes and C1 Return OK message. connections speeds (OK CONNECT,
Resumo do conteúdo contido na página número 16
Appendix A 1015N-2MFM-1A “AT” Commands Command Function Command Function &C0 Force CD active regardless of the carrier state. &T0 Terminate any test in progress. &C1 Allow CD to follow the carrier state. &T1 Initiate local analog loopback. &D0 Interpret DTR ON-to-OFF transition per &Qn: &T2 Returns ERROR result code. &Q0, &Q5, &Q6 The modem ignores DTR. &T3 Initiate local digital loopback. &Q1, &Q4 The modem hangs up. &T4 Allow remote digital loopback. &Q2, &Q3 The m
Resumo do conteúdo contido na página número 17
Appendix A 1015N-2MFM-1A “S” Registers Register Function S0 Rings to auto-answer* S1 Ring counter S2 Escape character* S3 Carriage return character S4 Line feed character S5 Backspace character S6 Maximum time to wait for dial tone* S7 Wait for carrier* S8 Pause time for dial delay modifier* S9 Carrier detect response time* S10 Carrier loss disconnect time* S11 DTMF Tone Duration* S12 Escape code guard time* S13 Reserved S14 General bit mapped options* S15 Reserved S16 Test mode bit mapped optio
Resumo do conteúdo contido na página número 18
Appendix A 1015N-2MFM-1A “AT” COMMANDS and “S” REGISTERS EXCLUSIVE TO THE PE2400 Dial Modifiers Command Factory Default Parameters/Description ; (semicolon) Return to Idle State. “ ; ” forces the modem to remain in the command state after dialing a number without disconnecting. The semicolon must be placed at the end of the dial command. Parameters: none @ WaIt for Quiet Answer Command. ” @ ” causes the modem to look for rings followed by 5 seconds of silence before processing the next symbol i
Resumo do conteúdo contido na página número 19
Appendix A 1015N-2MFM-1A “AT” COMMANDS and ‘S” REGISTERS EXCLUSIVE TO THE PE2400 Ampersand (AT&) Commands Command Factory Default Parameters / Descrlptlon &Dn n = 0 Data Terminal Ready Option. &Dn controls the Data Terminal Ready (DTR) options. Parameters: n = 0, 1, 2, 3 n = 0 Modem ignores DTR (factory default) n = 1 Modem assumes command state when ON-to-OFF transition Is detected on DTR. n = 2 Modem hangs up, assumes command state and disables auto-answer upon detecting ON-to-OFF transition o
Resumo do conteúdo contido na página número 20
Appendix A 1015N-2MFM-1A “AT”COMMANDS and “S” REGISTERS EXCLUSIVE TO THE PE2400 “S” Registers Register Range Units Default Description S17 0-250 4 ms 00 Fax Mode Null Byte Timer increments S20 0-127 seconds 00 Fax Mode Inactivity Timer S22* Bit none 76 hex Bit Mapped Options Register Mapped Notes: *This S-Register is stored in the modem NVRAM upon receipt of the &W command so that the contents are preserved when modem power is removed. A-7