2000 Series
Program Entry Guide
EN Control Panels
Resumo do conteúdo contido na página número 2
2000 Series | Program Entry Guide | About This Manual EN | 2 About This Manual This guide describes the programming parameters available to the 2000 Series Control Panels (except D2012/D2012U). This guide follows the organization of the D2212 Product Handler in the D5200 Programmer. The table of contents lists each programming section, program item, and its page number. Throughout this manual, programming prompts are shown in bold italic letters (such as Phone 1). Use the Program
Resumo do conteúdo contido na página número 3
2000 Series | Program Entry Guide | Contents EN | 3 Contents 1.0 System Configuration......................................5 2.0 Phone ..................................................................7 2.1 Phone Routing Set to No...................................7 2.2 Phone Routing Set to Yes..................................7 3.0 Reports..............................................................11 4.0 Receiver............................................................15 4.1 Mode
Resumo do conteúdo contido na página número 4
2000 Series | Program Entry Guide | Contents EN | 4 Figures Figure 1: Pulse Report Groups......................................18 Figure 2: View Mode......................................................65 Figure 3: Modify Mode ..................................................66 Tables Table 1: Phone Routing Set to No..................................7 Table 2: Modem II Reports Chart................................15 Table 3: Pulse Format.............................................
Resumo do conteúdo contido na página número 5
2000 Series | Program Entry Guide | 1.0 System Configuration EN | 5 3 Keyswitch 1.0 System Configuration Default: Momentary The System Configuration Group contains the Account Number, Swinger Count, Keyswitch, Easikey, Momentary Selection: Custom Idle Text, and Custom Service Text prompts. 0 Easikey 1 Momentary 1 Account Number Refer to the Installation Guide for instructions on Default: 0000 connecting a momentary keyswitch to a point. 0 to 9, B to F Selection: This contr
Resumo do conteúdo contido na página número 6
2000 Series | Program Entry Guide | 1.0 System Configuration EN | 6 6 Custom Service Text Default: Blank A to Z, 0 to 9, Selection: ! # , . - / : < > The system displays the text you enter here in the second line of the keypad display when ever the first line reads, CALL FOR SERVICE. You can enter the phone number for your service department as the Custom Service Text. Up to 15 Seconds for Text to Load: It can take up to 15 seconds for the custom text you program here to appear i
Resumo do conteúdo contido na página número 7
2000 Series | Program Entry Guide | 2.0 Phone EN | 7 Table 1: Phone Routing Set to No 2.0 Phone The Phone Group contains prompts that configure the Attempt Phone Number system for dialing and sending reports on the 1 Phone Number 1 telephone line. 2 Phone Number 1 1 DTMF Dialing 3 Phone Number 2 4 Phone Number 2 Default: Yes 5 Phone Number 1 Selection: Yes, No 6 Phone Number 2 7 Phone Number 1 0 No 8 Phone Number 2 1 Yes 9 Phone Number 1 When DTMF Dialing is set to Yes,
Resumo do conteúdo contido na página número 8
2000 Series | Program Entry Guide | 2.0 Phone EN | 8 5 Fire Route 8 Restoral Route Default: Local Default: Local Local, Phone 1 only, Phone 2 only, Local, Phone 1 only, Phone 2 only, Selection: Selection: Both Both Local 0 Local 0 Phone 1 only 1 Phone 1 only 1 Phone 2 only 2 Phone 2 only 2 Both 3 Both 3 Reports: Fire Alarm Reports from points or ABC Reports: keys. • Restoral Reports from Fire and Non-Fire points combined 6 Non-Fire Route • RF Battery Restorals Default: Local
Resumo do conteúdo contido na página número 9
2000 Series | Program Entry Guide | 2.0 Phone EN | 9 11 Cancel Route 13 Sys Trbl Route Default: Local Default: Local Local, Phone 1 only, Phone 2 only, Local, Phone 1 only, Phone 2 only, Selection: Selection: Both Both Local 0 Local 0 Phone 1 only 1 Phone 1 only 1 Phone 2 only 2 Phone 2 only 2 Both 3 Both 3 Reports: Cancel Reports Reports: • RAM Access OK Reports (successful connection 12 Sys Trbl Route to a remote programmer) Default: Local • Comm Restoral Reports (successful
Resumo do conteúdo contido na página número 10
2000 Series | Program Entry Guide | 2.0 Phone EN | 10 15 Test Route Default: Local Local, Phone 1 only, Phone 2 only, Selection: Both Local 0 Phone 1 only 1 Phone 2 only 2 Both 3 Reports: • Test Reports • Service Start (stand-by pin locked down, installer code entered.) • Service Stop (standby-by pin unlocked. The control panel only sends a Service Stop Report if a Service Start Report was transmitted). Bosch Security Systems | 7/05 | 35114F
Resumo do conteúdo contido na página número 11
2000 Series | Program Entry Guide | 3.0 Reports EN | 11 3 Restricted O/C 3.0 Reports Default: No 1 O/C Rpts – All On Yes, No Selection: Default: No 0 No Selection: Yes, No 1 Yes 0 No Set the Restricted O/C prompt to Yes. The system only sends Opening Reports when the user turns the 1 Yes system off after an alarm. The system attaches an If you set the O/C Rpts-All On prompt to Yes, the AFTER ALARM message to the Modem II system transmits Closing Reports to the receiver Openi
Resumo do conteúdo contido na página número 12
2000 Series | Program Entry Guide | 3.0 Reports EN | 12 If the system is on with No Delay, alarm output at 6 Restoral Rpts Terminals 4 and 5 follows the alarm delay programmed here. The alarm sounds at the keypad Default: No without delay. No, Yes, Delay Selection: When mixing Delay Alarm points (Digit 2 set for 7 or 8), with No Delay Alarm points (Digit 2 set for 5, 0 No 6, or 9), the alarm output follows the programmed alarm delay if Delay Alarm points are faulted first. 1 Yes
Resumo do conteúdo contido na página número 13
2000 Series | Program Entry Guide | 3.0 Reports EN | 13 When set to Buzz, Report the system flashes the OK light at the keypad, sounds the trouble tone, and sends an AC Fail Report to the receiver. When set to Buzz, Tag-Along Rpt the system flashes the OK light and sounds the trouble tone at the keypad after 60 seconds. It sends an AC Fail Report to the receiver as a tag along with all reports sent to the receiver until AC restores. When set to No Buzz, Report the system flashes the
Resumo do conteúdo contido na página número 14
2000 Series | Program Entry Guide | 3.0 Reports EN | 14 Notes: Bosch Security Systems | 7/05 | 35114F
Resumo do conteúdo contido na página número 15
2000 Series | Program Entry Guide | 4.0 Receiver EN | 15 4.0 Receiver 4.1 Modem Reports 1 Rcvr Format Default: Modem Modem, Pulse Selection: 0 Pulse 1 Modem Set Rcvr Format to Modem to transmit reports in Modem II format with its advanced reporting capabilities. You need firmware revision 8.00 or greater installed in your D6500 Receiver. Table 2 shows the reports available. The D6500 line card ack tone table must contain “Modem II for D9112.” Refer to the 6500: Line Program En
Resumo do conteúdo contido na página número 16
2000 Series | Program Entry Guide | 4.0 Receiver EN | 16 Table 2: continued Modem II Report Description Closing Report when passcode is not used. Refer to the Passcode Rquired prompt in Section CLOSING REPORT 15.0 Passcodes. Using a Keyswitch or a remote programmer also sends this Closing Report with no user ID. Closing Report with user ID for users 1 to 8. CLOSING REPORT ID 001 (-008) Communication Failure event. Refer to Phone 1, Phone 2 in Section 2.0 Phone. COMM FAIL PHO
Resumo do conteúdo contido na página número 17
2000 Series | Program Entry Guide | 4.0 Receiver EN | 17 Table 2: continued Modem II Report Description Point 1 to 24 bypassed. Points can be bypassed from the keypad or from a remote POINT BYPASS POINT 001 (-024) programmer. Bypass Reports are only sent when Opening and Closing Reports are enabled in Section 6.0 Open/Close. Normal remote programmer session termination. RAM ACCESS OK Remote programmer made connection with control panel, but passcode was incorrect, or call RAM A
Resumo do conteúdo contido na página número 18
2000 Series | Program Entry Guide | 4.0 Receiver EN | 18 4.2 Pulse Report Groups If you select the Pulse Format you need to set the report code for each report group. Pulse 4x2 reports consist of a four-digit account number, a one-digit report group code, and a one-digit point or User ID number. For example, a control panel with the Account Number prompt set to 1213, the Rcvr Format prompt set to pulse, the Fire Group prompt set to 3, and Point 1 programmed as a Fire point would send the
Resumo do conteúdo contido na página número 19
2000 Series | Program Entry Guide | 4.0 Receiver EN | 19 3 Non-Fire Group 7 Opening Group Default: 0 Default: 0 Selection: 0 to 9, B to F Selection: 0 to 9, B to F 1 to 8 Non-Fire alarm from Points 1 to 24. Opening Report when keyswitch is 0 used, or Part On No Delay, or Part On 9 or 0 Non-Fire alarm from key A, B, or C. with delay. Refer to Section 7.0 ABC Keys. Opening Report with User ID for users 1 to 8 There are no Pulse Format versions of 1 to 8. the Modem II Alarm recent C
Resumo do conteúdo contido na página número 20
2000 Series | Program Entry Guide | 4.0 Receiver EN | 20 10 Sys Res Group Default: 0 Selection: 0 to 9, B to F 1 Successful connection to a remote programmer. 2 Not used. 3 Control panel reset with the stand-by switch (refer to the Installation Guide) or a remote programmer. 4 Not used. 5 Not used. 6 Not used. 7 Reports missing or low battery restored. 8 Restored AC power. 9 Communication Restoral event for Phone 1. B Communication Failure event for Phone 2. C RF tamper rest