AT 1 Use arrows to choose the time of day that the Weekly Test is performed. Press to confi rm. FOR 1 Use arrows to choose the duration (engine run time) of the Weekly Test. Press to confi rm. NOW IN WEEK 1 Use arrows to choose current time frame in reference to the Weekly Test schedule. Press to confi rm. (Example: If test is programmed for every 2 weeks on Sunday and today were Friday then - If testing
Resumo do conteúdo contido na página número 18
SETTINGS HIGH RESERVOIR FEATURE SETTINGS AUDIBLE 1 Use arrows to enable or disable the audible alarm for High Reservoir Level. Press to confi rm. COMMON ALARM 1 Use arrows to enable or disable the common alarm output (ALR relay) for High Reservoir Level. Press to confi rm. PUMP ROOM 1 Use arrows to select the alarm output relay for High Reservoir Level (Disabled, PTR (Pump Room Trouble), ETR (Engine Trouble), Both PTR and ET
Resumo do conteúdo contido na página número 19
REMOVE DRIVE 1 Use arrows to enable or disable the Remove Drive feature. Press to confi rm. Much like a computer, the Remove Drive feature ensures fi le closure prior to removing the USB fl ash drive from the Mark IIXG. Use of this feature helps prevent fi le corruption. NOTE: The Mark IIXG also features an automatic daily save function. Every day at midnight (0:00) the events for that day are written to a fi le on the USB fl ash drive. This fi le is also a text fi le (
Resumo do conteúdo contido na página número 20
FACTORY DIAGNOSTICS RAW INPUT: ANALOG Input values are shown. This information is for factory level troubleshooting purposes. RAW INPUT: DISCRETE Input values are shown. This information is for factory level troubleshooting purposes. RAW INPUT: KEYS Input values are shown. This information is for factory level troubleshooting purposes. RAW OUTPUT: DISCRETE Output values are shown. This information is for factory level troubleshooting purposes. MARK IIXG STARTS Displays the total number of ti
Resumo do conteúdo contido na página número 1
F FT TA A1100 1100
Inst Installation and Ope allation and Oper ration Instru ation Instruc ct tions ions
Mark II Mark IIX XG G Dies Diese el l Engine Fire Pump C Engine Fire Pump Co on ntrolle troller rs s
NS1100-50
ECN 225126
Resumo do conteúdo contido na página número 2
Table of Contents INTRODUCTION ...........................................................................................................................1 MOUNTING CONTROLLER ............................................................................................................1 Wall Mount ................................................................................................................... 1 - 2 Floor/Base Plate Mount ........................................................
Resumo do conteúdo contido na página número 3
Pressure (continued) Overpressure Alarm .................................................................................................10 Recording - Delta .....................................................................................................10 Sensor ......................................................................................................................10 Calibration .....................................................
Resumo do conteúdo contido na página número 4
MAIN MENU - FACTORY (continued) Confi guration - Model Pressure Sensor ........................................................................................................15 Autostart NC ............................................................................................................15 User Input Number ...................................................................................................15 Low Suction ......................
Resumo do conteúdo contido na página número 5
WARNING RISK OF ELECTRICAL SHOCK Personal injury could occur. Ensure all power is disconnected before installing or servicing this equipment. These instructions are intended to assist in the understanding of the installation and operation of the FTA1100. Read through these instructions thoroughly prior to connecting the controller. If there are any questions unanswered in these instructions, please contact the local Firetrol representative or factory service department. INTRODUCTION ® Firetr
Resumo do conteúdo contido na página número 6
5. Using either the dimension print or by measuring the distance between the center lines of the 2 lower bracket slots, transcribe this dimension onto the wall. Note: The bottom edge of the en- closure should be a minimum of 12” (305 mm.) from the fl oor in case fl ooding of the pump room occurs. 6. Drill and put 2 anchors into the wall for the 2 lower bracket slot mounts. 7. Mark on the wall, the location of the holes in the upper mounting ears. 8. Drill and put 2 anchors into wall for the upp
Resumo do conteúdo contido na página número 7
2. Verify that the controller information is what is required on the project: • Firetrol catalog number • Engine voltage and polarity of grounding • Incoming line voltage and frequency • Maximum system pressure 3. Project electrical contractor must supply all necessary wiring for fi eld connections in accordance with the National Electrical Code, local electrical code and any other authority having jurisdic- tion. 4. Refer to the appropriate fi eld connection drawing for wiring informatio
Resumo do conteúdo contido na página número 8
6. Connect AC power to “L1” and “L2” (CB1) —120 Volt, 60 Hz or as called for on controller data plate. 7. Connect remote normally open START push-button wires to terminals “13” and “14” (if used). 8. If deluge valve is used, remove jumper from terminals “16” and “17”. Connect wires from normally closed contact on deluge valve to terminals “16” and “17”. 9. Connect remote normally open shutdown interlock wires to terminals “15” and “16” (if used). A factory installed jumper will be install
Resumo do conteúdo contido na página número 9
Mark IIXG User Interface and Display SYSTEM STATUS 1 Ready 132 psi AC POWER AVAILABLE 1 11.7 0.8A 120~ 2 11.5 0.7A 118~ ALARM MAIN SWITCH IN AUTO 09-28-2009 14:37:06 MAIN SWITCH IN MANUAL SYSTEM PRESSURE LOW DIESEL ENGINE RUNNING ENGINE FAIL TO START ENGINE TEMPERATURE HIGH 2 3 ENGINE OIL PRESSURE LOW ENGINE OVERSPEED ENGINE ALTERNATE ECM ENGINE FUEL INJECTOR MALFUNCTION Esc Esc Enter Enter FUEL LEVEL LOW AUTOMATIC SHUTDOWN DISABLED 4 CHARGER MALFUNCTION Silence Silence BATTERY #1 TRO
Resumo do conteúdo contido na página número 10
Mark IIXG User Menu Structure Main Menu Settings System Setup Date & Time Timers Engine & Cranking Feat. Settings Opt. Settings Pressure Alarm Limits AC Failure Start (As ordered Display Time On Delay Time Units Control Overpressure Language/Units Date Min. Run Time Start Interlock Alarm with controller) # Attempts Sys DC Volt Set Low Press Aud Passwords Daylight Saving Stop Crank Time DC Volt Min Low Suction Auto Shtdwn Rest Time DC Volt Max Overpressure Main Sw Mis-Set Overspeed Term 1 AC Volt
Resumo do conteúdo contido na página número 11
Programming Notes The Firetrol Mark IIXG is multi-level password protected. User programmable functions are protected by a Level 1 password. LEVEL 1 PASSWORD 2 - 1 - 1 - 2 Indicates the level of password required to modify a setting. 1 Note: Many menu settings feature an “enable/disable” option. These options are indicated by a “ ” for enabled or a “x” for disabled. In many cases this can also be interpreted as “ ” for yes or a “x” for no. WARNING RISK OF PROPERY LOSS, DEATH OR
Resumo do conteúdo contido na página número 12
Mark IIXG User Menu Settings Note: Many menu settings feature an “enable/disable” option. These options are indicated by a " ” for enabled or a “x” for disabled. Indicates the level of password required to modify setting. 1 System Setup - Display SETTINGS SYSTEM SETUP DISPLAY BRIGHTNESS 1 Use and arrows to set desired display brightness. Press to confi rm. SETTINGS SYSTEM SETUP DISPLAY CONTRAST 1 Use and arrows to set desired display contrast. Press
Resumo do conteúdo contido na página número 13
SETTINGS DATE & TIME DAYLIGHT SAVING 1 Use arrows to enable or disable automatic Daylight Saving time adjustments. Press to confi rm. (+/-) Use arrows to set number of minutes to adjust for at the beginning or end of Daylight Saving time. Press to confi rm. (DST +) “Begin” - Hour Use arrows to set the hour of day that Daylight Saving time begins. Press to confi rm. (DST +) “Begin” - Day Use
Resumo do conteúdo contido na página número 14
SETTINGS PRESSURE OVERPRESSURE ALARM 1 Use arrows to enable or disable the overpressure alarm feature. Press to confi rm. Use arrows to set the pressure limit for the overpressure alarm. Press to confi rm. Limit SETTINGS PRESSURE RECORDING - DELTA 1 Use arrows to set pressure delta recording limit. Press to confi rm. Note: Pressure will be recorded whenever pressure changes by more than set limit. HOURLY Use
Resumo do conteúdo contido na página número 15
SETTINGS ALARM LIMITS MAX 1 Use arrows to set maximum voltage point for Battery Trouble alarm. Press to confi rm. SETTINGS ALARM LIMITS V MIN 1 Use arrows to set minimum voltage point for AC Voltage Low alarm. Press to confi rm. ENABLED 1 Use arrows to enable or disable the AC Voltage Low alarm. Press to confi rm. SETTINGS ALARM LIMITS V MAX 1 Use arrows to set maximum voltage point for AC Voltage Hi
Resumo do conteúdo contido na página número 16
FEATURE SETTINGS MANUAL TEST SETTINGS DURATION 1 Use arrows to set the minimum run time (duration) when manual test push-button is used (10 - 99 min.). Press to confi rm. PUMP RUN ALARM SETTINGS FEATURE SETTINGS AUDIBLE 1 Use arrows to enable or disable the audible alarm for Pump Run. Press to confi rm. COMMON ALARM 1 Use arrows to enable or disable the common alarm output (ALR relay) for Pump Run. Press to confi