DESCRIPTION
YORK Sunline Magnum™ units are convertible single pack-
TECHNICAL GUIDE
age high efficiency rooftops. All models have independent
dual refrigerant circuits for efficient part load operation.
Although the units are primarily designed for curb mounting
on a roof, they can also be slab-mounted at ground level or
set on steel beams above a finished roof.
SINGLE PACKAGE GAS/ELECTRIC UNITS
All units include:
AND SINGLE PACKAGE AIR
Powder Paint finish that meets A
Streszczenie treści zawartej na stronie nr. 2
036-21410-001-A-0502 TABLE OF CONTENTS DESCRIPTION .. .... ... ... ... ... .... ... ... . 1 Tbl. # Pg. # NOMENCLATURE.... ... ... ... ... .... ... ... . 3 14 COOLING CAP FOR DJ240 AT 85°F ... ... .. 23 FEATURES .. ... .... ... ... ... ... .... ... ... . 8 15 COOLING CAP FOR DJ240 AT 95°F ... ... .. 24 FACTORY-INSTALLEDOPTIONS ... .... ... ... . 9 16 COOLING CAP FOR DJ 240 AT 105°F . . . . . . . 25 FIELD-INSTALLEDACCESSORIES .. .... ... ... 10 17 COOLING CAP FOR DJ 240 AT 115°F . . . . . . . 26 G
Streszczenie treści zawartej na stronie nr. 3
036-21410-001-A-0502 PRODUCT NOMENCLATURE 15-25T Sunline Magnum Model Number Nomenclature D J 240 N 2 4 A 2 A AA 1 A Product Category D = Air Cond., Single Package A = A Product Generation 1 = First Generation J = R-22 Super High Efficiency (Magnum) A = N o Options Installed B = 1 C = 2 2 = 208/230-3-60 D = Option s1&2 4 = 460-3-60 Nominal Cooling E = 3 5 = 575-3-60 Capacity - MBH F = 4 G = s1&3 180 = 1 5 Ton H = Option s1&4 210 = 17.5 Ton J = 1 ,2&3 240 = 2 0 Ton K = & 4 300 = 2 5 Ton L = & 4
Streszczenie treści zawartej na stronie nr. 4
036-21410-001-A-0502 PRODUCT NOMENCLATURE - Continued 15-25T Sunline Magnum™ Model Number Nomenclature Additional Options AA None AB Phase Monitor AC Coil Guard AD Dirty Filter Switch AE Phase Monitor & Coil Guard AF Phase Monitor & Dirty Filter Switch AG Coil Guard & Dirty Filter Switch AH Phase Monitor, Coil Guard, & Dirty Filter Switch BA Hinged Filter Door & Tooless Access Panels BB Phase Monitor, Hinged Filter Door & Tooless Access Panels BC Coil Guard, Hinged Filter Door & Tooless Access P
Streszczenie treści zawartej na stronie nr. 5
036-21410-001-A-0502 Additional Options EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil
Streszczenie treści zawartej na stronie nr. 6
036-21410-001-A-0502 Additional Options JB Johnson UNT Controller, DFS, APS & Phase Monitor JC Johnson UNT Controller, DFS, APS & Coil Guard JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Gua
Streszczenie treści zawartej na stronie nr. 7
036-21410-001-A-0502 Additional Options TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch TJ Technicoat Evaporator Coil TK Technicoat Evaporator Coil & Phase Monitor TL Technicoat Evaporator Coil & Coil Guard TM Technicoat Evaporator Coil & Dirty Filter Switch TN Technicoat Evapora
Streszczenie treści zawartej na stronie nr. 8
036-21410-001-A-0502 Anti-Short Cycle Protection - To aid compressor FEATURES life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further All models are available with a wide variety of factory- ensured by programmable minimum run times. For mounted options such as stainless steel heat exchangers, testing, the anti short cycle delay can be temporarily phase monitor, dirty filter switch, and coil guard to make them overridden with the push of a
Streszczenie treści zawartej na stronie nr. 9
036-21410-001-A-0502 FIGURE 1: UNIT CUTAWAY Electric Heat Operation - All electric heat models (fac- POWER EXHAUST - Our single economizer options are tory installed only) are wired for a single power source available with power exhaust. Whenever the outdoor air and include a bank of nickel chromium elements intake dampers are opened for free cooling, the exhaust mounted at the discharge of the supply air blower to pro- fan will be energized to prevent the conditioned space vide a high veloc
Streszczenie treści zawartej na stronie nr. 10
036-21410-001-A-0502 FILTER OPTIONS - Standard units are shipped with 2” The rainhood is painted to match the basic unit and must throw-away filters installed. 2” pleated and 4” pleated fil- be field-assembled before installing. ters are offered as a factory installed option. Power exhaust is not available as a field installed option. CONVENIENCE OUTLET - This 110 volt outlet can be MOTORIZED OUTDOOR AIR INTAKE DAMPER - “powered” by the unit with a stepdown transformer or Includes a slide-
Streszczenie treści zawartej na stronie nr. 11
036-21410-001-A-0502 ENTHALPY ACCESSORY CONTROL KIT-Thiskit CO SENSOR-SensesCO levels and automatically 2 2 contains the required components to convert a single overrides the economizer when levels rise above the enthalpy economizer to dual enthalpy. present limits. BURGLAR BARS - Mount in the supply and return COIL GUARD - Customers can purchase a coil guard kit openings to prevent entry into the duct work. to protect the condenser coil from damage. This is not a hail guard kit. FLUE
Streszczenie treści zawartej na stronie nr. 12
036-21410-001-A-0502 1 TABLE 1: SOUND POWER RATING -12 SOUND POWER (db 10 Watts) ESP BLOWER UNIT Octave Band Centerline Frequency (Hz) dB(A) CFM SIZE SWL @ dB(A) 2 IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000 10Ft. 180 6,000 1.00 1,080 4.60 99 99 89 82 84 77 72 67 89 56 210/240 8,000 1.00 1,120 6.65 102 102 92 85 87 80 75 70 92 59 300 10,000 1.30 1160 12.5 108 108 98 91 93 86 81 76 98 65 1. These values have been accessed using a model of sound propagation from a point source into the hemi
Streszczenie treści zawartej na stronie nr. 13
036-21410-001-A-0502 TABLE 4: COOLING CAPACITIES FOR DJ180 AT 85°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 85 1 GROSS INPUT GROSS SENSIBLE CAPACITY (MBH) WB 1 2 CFM CAPACITY POWER (RETURN AIR DRY BULB TEMP. - (°F) ) TEMP °F (MBH) (kW) 86 83 80 77 74 71 68 72 210.2 12.36 121.0 108.2 95.3 82.5 69.7 #N/A #N/A 67 193.0 11.97 151.5 138.6 125.8 113.0 100.2 87.3 74.5 4500 62 177.6 11.68 177.6 167.6 154.8 141.0 129.1 116.3 103.5 57 182.7 11.62 182.1 169.2 156.4 143.6 130.7 117.9 105.1 72 216.7 12.4
Streszczenie treści zawartej na stronie nr. 14
036-21410-001-A-0502 TABLE 5: COOLING CAPACITIES FOR DJ180 AT 95°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 95 1 GROSS INPUT GROSS SENSIBLE CAPACITY (MBH) WB 1 2 CFM CAPACITY POWER (RETURN AIR DRY BULB TEMP. - (°F) ) TEMP °F (MBH) (kW) 86 83 80 77 74 71 68 72 201.7 13.56 117.1 104.3 91.5 78.6 65.8 #N/A #N/A 67 184.2 13.27 147.0 134.2 121.4 108.5 95.7 82.9 70.0 4500 62 172.1 13.01 172.1 159.9 147.1 134.3 121.4 108.6 95.8 57 173.0 12.92 173.0 161.7 148.8 136.0 123.2 110.3 97.5 72 207.4 13.65 1
Streszczenie treści zawartej na stronie nr. 15
036-21410-001-A-0502 TABLE 6: COOLING CAPACITIES FOR DJ180 AT 105°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 105 1 GROSS INPUT GROSS SENSIBLE CAPACITY (MBH) WB 1 2 CFM CAPACITY POWER (RETURN AIR DRY BULB TEMP. - (°F) ) TEMP °F (MBH) (kW) 86 83 80 77 74 71 68 72 190.3 15.40 112.3 99.5 86.7 73.9 61.0 #N/A #N/A 67 173.9 15.02 142.1 129.3 116.5 103.6 90.8 78.0 65.2 4500 62 163.2 14.66 163.2 152.1 139.3 126.5 113.6 100.8 88.0 57 162.5 14.58 162.5 154.8 142.0 129.2 116.3 103.5 90.7 72 195.4 15.52
Streszczenie treści zawartej na stronie nr. 16
036-21410-001-A-0502 TABLE 7: COOLING CAPACITIES FOR DJ180 AT 115°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 115 1 GROSS INPUT GROSS SENSIBLE CAPACITY (MBH) WB 1 2 CFM CAPACITY POWER (RETURN AIR DRY BULB TEMP. - (°F) ) TEMP °F (MBH) (kW) 86 83 80 77 74 71 68 72 178.8 17.24 107.6 94.7 81.9 69.1 56.2 #N/A #N/A 163.6 16.78 137.2 124.4 111.6 98.8 85.9 73.1 60.3 67 4500 154.2 16.31 154.2 144.3 131.5 118.7 105.9 93.0 80.2 62 152.0 16.24 152.0 148.0 135.1 122.3 109.5 96.6 83.8 57 183.3 17.38 119.6
Streszczenie treści zawartej na stronie nr. 17
036-21410-001-A-0502 TABLE 8: COOLING CAPACITIES FOR DJ180 AT 125°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 125 1 GROSS INPUT GROSS SENSIBLE CAPACITY (MBH) WB 1 2 CFM CAPACITY POWER (RETURN AIR DRY BULB TEMP. - (°F) ) TEMP °F (MBH) (kW) 86 83 80 77 74 71 68 72 167.4 19.08 102.8 89.9 77.1 64.3 51.4 #N/A #N/A 67 153.3 18.53 132.3 119.5 106.7 93.9 81.0 68.2 55.4 4500 62 145.3 17.95 145.3 136.6 123.7 110.9 98.1 85.2 72.4 57 141.5 17.91 141.5 141.1 128.3 115.5 102.6 89.8 77.0 72 171.3 19.24 114.
Streszczenie treści zawartej na stronie nr. 18
036-21410-001-A-0502 TABLE 9: COOLING CAPACITIES FOR DJ210 AT 85°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 85 1 GROSS INPUT GROSS SENSIBLE CAPACITY (MBH) WB 1 2 CFM CAPACITY POWER (RETURN AIR DRY BULB TEMP. - (°F) ) TEMP °F (MBH) (kW) 86 83 80 77 74 71 68 238.9 14.24 142.6 125.5 108.4 91.3 74.2 #N/A #N/A 72 221.2 13.83 178.6 161.5 144.4 127.3 110.2 93.1 76.0 67 6000 207.4 13.57 207.4 192.8 175.7 158.5 141.4 124.3 107.2 62 197.6 13.52 197.6 195.7 178.6 161.4 144.3 127.2 110.1 57 246.1 14.36
Streszczenie treści zawartej na stronie nr. 19
036-21410-001-A-0502 TABLE 10: COOLING CAPACITIES FOR DJ210 AT 95°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 95 1 GROSS INPUT GROSS SENSIBLE CAPACITY (MBH) WB 1 2 CFM CAPACITY POWER (RETURN AIR DRY BULB TEMP. - (°F) ) TEMP °F (MBH) (kW) 86 83 80 77 74 71 68 222.9 15.81 136.5 119.4 102.3 85.2 68.1 #N/A #N/A 72 207.1 15.38 172.8 155.7 138.6 121.5 104.4 87.2 70.1 67 6000 197.6 15.09 197.6 181.0 163.8 146.7 129.6 112.5 95.4 62 186.0 15.06 186.0 181.8 164.7 147.6 130.5 113.4 96.3 57 231.8 15.91 1
Streszczenie treści zawartej na stronie nr. 20
036-21410-001-A-0502 TABLE 11: COOLING CAPACITIES FOR DJ210 AT 105°F RETURN AIR OUTDOOR AMBIENT TEMPERATURE (°F): 105 1 GROSS INPUT GROSS SENSIBLE CAPACITY (MBH) WB 1 2 CFM CAPACITY POWER (RETURN AIR DRY BULB TEMP. - (°F) ) TEMP °F (MBH) (kW) 86 83 80 77 74 71 68 210.2 17.65 131.0 113.9 96.8 79.7 62.6 #N/A #N/A 72 195.1 17.21 167.5 150.4 133.3 116.2 99.1 82.0 64.9 67 6000 186.9 17.01 186.9 170.6 153.5 136.4 119.3 102.2 85.1 62 174.4 16.80 174.4 172.3 155.2 138.1 121.0 103.9 86.8 57 218.3 17.77 1