Streszczenie treści zawartej na stronie nr. 1
254597-YTG-B-0507
DESCRIPTION
®
YORK Sunline Ultra units are convertible single package air
TECHNICAL GUIDE
conditioners with a common cabinet and a common roof curb
for the 3, 4 and 5 ton sizes. The units were designed for light
commercial and commercial applications. They can easily be
installed on a roof curb, slab, roof jack or frame.
All units include:
SINGLE PACKAGE GAS/ELECTRIC UNITS
• Powder Paint finish that meets ASTM-B-117 1000 hour
AND SINGLE PACKAGE
salt spray standards
• P
Streszczenie treści zawartej na stronie nr. 2
254597-YTG-B-0507 TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 LIST OF TABLES PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 Tbl. # Pg. # FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . . . 8 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5 2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . . 8 3 GAS HEAT RATINGS . . . . . . . . . . .
Streszczenie treści zawartej na stronie nr. 3
254597-YTG-B-0507 PRODUCT NOMENCLATURE 3-5 Ton Sunline Ultra Model Number Nomenclature D H 048 N04 A 2 A AA 1 0 1 2 4 A Product Category Product Style D = A/C, Single Pkg., R-22 A = Style A Product Identifier Configuration Options (not required for all units) These four digits will not be assigned until a quote is requested, or an order placed. H = 12.0 SEER A/C SS Drain Pan CPC Controller, DFS, APS Johnson Controller, DFS, APS Nominal Cooling Capacity Honeywell Controller, DFS, APS 036 = 3.0 To
Streszczenie treści zawartej na stronie nr. 4
254597-YTG-B-0507 gas valve, if applicable, and the temperature limit FEATURES switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and All models are available with a wide variety of factory- repeated limit switch trips. mounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter • Nuisance Trip Protection- To prevent nuisance switch, disconnect switch, smoke detectors, and coil
Streszczenie treści zawartej na stronie nr. 5
254597-YTG-B-0507 FIGURE 1 - UNIT CUTAWAY • BAS Controls - York’s Sunline™ series units offer factory • PHENOLIC COATED EVAPORATOR AND CON- ® mounted BAS controls such as Simplicity INTELLI-Com- DENSER COILS - Special coating process that utilizes TM fort™, Novar, Honeywell, Johnson, and CPC. Technicoat 10-1 processes. Coating is applied by total immersion of the complete coil for maximum protection. FACTORY-INSTALLED OPTIONS • ELECTRIC HEATERS - Wired for single point power • SINGLE INPUT EL
Streszczenie treści zawartej na stronie nr. 6
254597-YTG-B-0507 installed dirty filter indicator switch, an air-proving switch, • SMOKE DETECTORS - (supply air & return air) The an Outside Air Humidity sensor, a Return Air Humidity smoke detectors stop operation of the unit by interrupting sensor, an Inside IAQ sensor, and an Outside Air IAQ power to the control board if smoke is detected within the sensor. Construction mode operation, 365-day real time air compartment. clock with 7 day programming plus holiday scheduling is built-in.
Streszczenie treści zawartej na stronie nr. 7
254597-YTG-B-0507 tudes up to 6,000 feet. This accessory supplements the FIELD-INSTALLED ACCESSORIES basic propane conversion kit. • SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper assembly • LOW NOX KIT - Required to reduce the emission of with fully modulating spring-return motor actuator capa- nitrogen oxides below 40 nano grams per joule. ble of introducing up to 100% outdoor air with nominal • POWER EXHAUST - Our single input economizer 1% leakage
Streszczenie treści zawartej na stronie nr. 8
254597-YTG-B-0507 1 TABLE 1: SOUND POWER RATING -12 SOUND POWER (db 10 Watts) ESP BLOWER UNIT Octave Band Centerline Frequency (Hz) dB(A) CFM SWL SIZE @ dB(A) IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000 2 10Ft. 036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41 048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42 060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free fi
Streszczenie treści zawartej na stronie nr. 9
254597-YTG-B-0507 TABLE 5: DH036 COOLING CAPACITIES (3 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F 95°F EVAPORATOR 1 1 TOTAL SENSIBLE CAPACITY TOTAL SENSIBLE CAPACITY COIL POWER POWER 1 1 ENTERING DRY BULB, °F ENTERING DRY BULB, °F CAP. CAP. 2 2 INPUT kW INPUT kW MBH MBH CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 55.2 3.18 35.2 30.7 26.2 21.8 17.3 - - 51.5 3.44 34.1 29.7 25.2 20.7 16.2 - - 67 49.1 3.13 41.7 37.2 32.8 28.3 23.8 19.4 14.9 45.8 3.35 40.2 35.7 31.3 26.8 22.3 1
Streszczenie treści zawartej na stronie nr. 10
254597-YTG-B-0507 TABLE 6: DH048 COOLING CAPACITIES (4 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F 95°F EVAPORATOR 1 1 TOTAL SENSIBLE CAPACITY TOTAL SENSIBLE CAPACITY COIL POWER POWER 1 1 ENTERING DRY BULB, °F ENTERING DRY BULB, °F CAP. CAP. 2 2 INPUT kW INPUT kW MBH MBH CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 59 3.3 46 40 34 28 23 - - 55 3.5 43 37 32 26 20 - - 67 53 3.2 53 49 43 38 32 26 21 49 3.4 49 47 41 35 30 24 2000 62 47 3.2 47 47 47 42 36 30 25 44 3.4 44 44 44 38
Streszczenie treści zawartej na stronie nr. 11
254597-YTG-B-0507 TABLE 7: DH060 COOLING CAPACITIES (5 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F 95°F EVAPORATOR 1 1 TOTAL SENSIBLE CAPACITY TOTAL SENSIBLE CAPACITY COIL POWER POWER 1 1 ENTERING DRY BULB, °F ENTERING DRY BULB, °F CAP. CAP. 2 2 INPUT kW INPUT kW MBH MBH CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 82 4.3 56 50 43 37 30 - - 76 4.6 54 48 41 34 28 - - 67 70 4.2 67 61 54 48 41 34 28 65 4.5 65 58 51 45 38 31 25 2500 62 67 4.0 67 67 66 59 52 46 39 62 4.5 62 62 62
Streszczenie treści zawartej na stronie nr. 12
254597-YTG-B-0507 TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION 2 AVAILABLE EXTERNAL STATIC PRESSURE-IWG AIR UNIT FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 TONNAGE CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 881
Streszczenie treści zawartej na stronie nr. 13
254597-YTG-B-0507 TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION 2 AVAILABLE EXTERNAL STATIC PRESSURE-IWG AIR UNIT FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 TONNAGE CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2
Streszczenie treści zawartej na stronie nr. 14
254597-YTG-B-0507 TABLE 12: BELT DRIVE BLOWER MOTOR AND DRIVE DATA BELT 1 ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY MOTOR (NOTCHED) BLOWER MODEL RANGE OUTSIDE PITCH OUTSIDE PITCH PITCH SIZE DESIG- BORE DESIG- BORE DESIG- (RPM) HP FRAME DIA. DIA. DIA. DIA. LENGTH QTY. NATION (IN.) NATION (IN.) NATION (IN.) (IN.) (IN.) (IN.) (IN.) 3 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 4 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 5 TON 850/1220
Streszczenie treści zawartej na stronie nr. 15
254597-YTG-B-0507 TABLE 15: ELECTRICAL DATA - DH036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET COMPRESSORS ID MIN. MAX. FUSE/ OD FAN CONV 1 MODEL BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR VOLTAGE MOTOR OUTLET RLA LRA TONNAGE MOTOR MODEL NO. KW AMPS AMPACITY SIZE FLA FLA EACH EACH FLA (AMPS) (AMPS) None -- -- 26.7 35 2 2CE04510525 4.0 11.1 26.7 35 2 2CE04510725 5.6 15.5 29.4 35 208-3-60 13.1 110.0 2.3 8.0 0.0 2CE04511025 8.0 22.2 37.8 40 2CE04511525 11.9 33.0 51.3 60 2CE045120
Streszczenie treści zawartej na stronie nr. 16
254597-YTG-B-0507 TABLE 16: ELECTRICAL DATA - DH036-060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET COMPRESSORS ID MIN. MAX. FUSE/ OD FAN CONV 1 MODEL BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR VOLTAGE RLA LRA MOTOR OUTLET TONNAGE MOTOR MODEL NO. KW AMPS AMPACITY SIZE EACH EACH FLA FLA FLA (AMPS) (AMPS) None -- -- 23.9 30 2 2CE04510525 4.0 11.1 23.9 30 2 2CE04510725 5.6 15.5 25.9 35 208-3-60 13.1 110.0 2.3 5.2 0.0 2CE04511025 8.0 22.2 34.3 35 2CE04511525 11.9 33.0 47.8 50 2CE04512025 15.9 4
Streszczenie treści zawartej na stronie nr. 17
254597-YTG-B-0507 TABLE 17: ELECTRICAL DATA - DH036, 048 & 060 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET COMPRESSORS ID MIN. MAX. FUSE/ OD FAN CONV 1 MODEL BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR VOLTAGE MOTOR OUTLET RLA LRA TONNAGE MOTOR MODEL NO. KW AMPS AMPACITY SIZE FLA FLA EACH EACH FLA (AMPS) (AMPS) None -- -- 36.7 45 2 2CE04510525 4.0 11.1 36.7 45 2 2CE04510725 5.6 15.5 41.9 45 208-3-60 13.1 110.0 2.3 8.0 10.0 2CE04511025 8.0 22.2 50.3 60 2CE04511525 11.9 33.0 63.8 70 2CE0451202
Streszczenie treści zawartej na stronie nr. 18
254597-YTG-B-0507 TABLE 18: ELECTRICAL DATA - DH036-060 BELT DRIVE W/POWERED CONVENIENCE OUTLET COMPRESSORS ID MIN. MAX. FUSE/ OD FAN CONV 1 MODEL BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR VOLTAGE MOTOR OUTLET RLA LRA TONNAGE MOTOR MODEL NO. KW AMPS AMPACITY SIZE FLA FLA EACH EACH FLA (AMPS) (AMPS) None -- -- 33.9 45 2 2CE04510525 4.0 11.1 33.9 45 2 2CE04510725 5.6 15.5 38.4 45 208-3-60 13.1 110.0 2.3 5.2 10.0 2CE04511025 8.0 22.2 46.8 50 2CE04511525 11.9 33.0 60.3 70 2CE04512025 15.9 44
Streszczenie treści zawartej na stronie nr. 19
254597-YTG-B-0507 TABLE 19: PHYSICAL DATA DH MODELS 036 048 060 Centrifugal Blower (Dia. x Wd. in.) 12 X 10 12 X 10 12 X 10 EVAPORATOR Fan Motor HP (Direct Drive) 3/4 1 1 BLOWER Fan Motor HP (Belt Drive) 1 1/2 1 1/2 1 1/2 Rows Deep 4 4 4 EVAPORATOR Fins Per Inch 13 13 13 COIL Face Area (Sq. Ft.) 4.3 5.1 5.1 Propeller Dia. (in.) 24 24 24 CONDENSER Fan Motor Hp 1/2 1/2 1/2 FANS Nom. CFM 4500 4200 4200 Rows Deep 2 2 2 CONDENSER Fins Per Inch 18 18 18 COILS Face Area (Sq. Ft.) 17.1 17.1 17.1 COMPRES
Streszczenie treści zawartej na stronie nr. 20
254597-YTG-B-0507 TYPICAL POWER WIRING TYPICAL CONTROL WIRING COOLING ONLY (24 VOLT THERMOSTAT) COOLING / HEATING (24 VOLT THERMOSTAT) 1 1 THERMOSTAT UNIT TERMINAL THERMOSTAT TERMINALS STRIP TB1 TERMINALS UNIT TERMINAL RV R RH STRIP TB1 ADD 24 VOLT JUMPER YC Y1 RC R TRANSFORMER Y Y1 Y2 24 VOLT TRANSFORMER Y2 GF G W W1 C W2 1 24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224. G G C COOLING / HEATING (ELECTRONIC THERMOSTAT) 1 MULTI STA