Streszczenie treści zawartej na stronie nr. 1
A Sierra Monitor Company
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-122
X30 Profibus DP Master
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version: 1.01
Document Revision: 3
Streszczenie treści zawartej na stronie nr. 2
FS-8700-122 X30 Profibus DP Master Manual Table of Contents TABLE OF CONTENTS 1. X30 PROFIBUS DP MASTER DESCRIPTION..................................................................3 2. DRIVER SCOPE OF SUPPLY...........................................................................................4 2.1. Supplied by FieldServer Technologies for this driver ...................................................4 rd 2.2. Provided by the Supplier of 3 Party Equipment.....................
Streszczenie treści zawartej na stronie nr. 3
FS-8700-122 X30 Profibus DP Master Manual Page 3 of 16 1. X30 Profibus DP Master Description The FieldServer Profibus X30 DP Master driver can be used to transfer I/O data with up to 125 Profibus DP Slave devices. The FieldServer is programmed with an embedded database using rd the required 3 party configuration tool. The embedded database contains information on the number of slaves and I/O modules to be transferred with each slave. The tool requires the input of GSD/E files
Streszczenie treści zawartej na stronie nr. 4
FS-8700-122 X30 Profibus DP Master Manual Page 4 of 16 2. Driver Scope of Supply 2.1. Supplied by FieldServer Technologies for this driver FieldServer Technologies Description PART # FS-8700-122 Driver Manual. X30-Profibus DP Master Profibus X30 DP Master Card rd 2.2. Provided by the Supplier of 3 Party Equipment rd 2.2.1. Required 3 Party Software HMS Anybus NetTool for Profibus rd 2.2.2. Required 3 Party Configuration Connection to a correctly terminated Profibus netwo
Streszczenie treści zawartej na stronie nr. 5
FS-8700-122 X30 Profibus DP Master Manual Page 5 of 16 3. Hardware Connections The FieldServer is connected to the Profibus network as shown in the connection drawing below. 3.1. Hardware Connection Tips / Hints Use the recommended network cable and terminators as specified by the Profibus network organization and/or the manufacturer of your network equipment. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299
Streszczenie treści zawartej na stronie nr. 6
FS-8700-122 X30 Profibus DP Master Manual Page 6 of 16 4. Configuring the FieldServer as a X30 Profibus DP Master Client For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameter
Streszczenie treści zawartej na stronie nr. 7
FS-8700-122 X30 Profibus DP Master Manual Page 7 of 16 Example // Data Arrays Data_Arrays Data_Array_Name, Data_Array_Format, Data_Array_Length Byte_Output, Byte, 10 Byte_Input, Byte, 10 Word_Output, Uint16, 10 Word_Input, Uint16, 10 Float_Output, Float, 10 Float_Input, Float, 10 4.3. Client Side Connection Descriptions Section Title Connections Column Title Function Legal Values Adapter Adapter Name Prof_DP Example // Client Side Connections
Streszczenie treści zawartej na stronie nr. 8
FS-8700-122 X30 Profibus DP Master Manual Page 8 of 16 4.5. Client Side Map Descriptors 4.5.1. FieldServer Related Map Descriptor Parameters Column Title Function Legal Values Name of this Map Up to 32 alphanumeric Map_Descriptor_Name Descriptor characters Name of Data Array One of the Data Array where data is to be Data_Array_Name names from “Data Array” stored in the section above FieldServer Starting location in Data 0 to maximum specified in Data_Array_Offset Array “
Streszczenie treści zawartej na stronie nr. 9
FS-8700-122 X30 Profibus DP Master Manual Page 9 of 16 4.6. Map Descriptor Example. This example demonstrates the transfer of I/O data with Remote Profibus DP Slaves using Station Addresses of 1 and 125. Map Descriptor Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Profibus_Data_Type, Address, Length, Scan_Interval Word_In_003, Word_Input, 0, RDBC, PDP_SLV003, WORD 0, 50, 1s Word_Out_003, Word_Output, 0, WRBC, PDP_SLV003, WORD 0
Streszczenie treści zawartej na stronie nr. 10
FS-8700-122 X30 Profibus DP Master Manual Page 10 of 16 4.7. Configuring the Embedded Profibus Database The X30 Profibus Master has to be configured with an embedded database that contains information about the Profibus Network data rate and remote Slave devices to access. The HMS Anybus NetTool for Profibus software must be installed and used for this purpose. Connect a serial RS-232 cable from the PC with the tool installed to the serial connector on the X30 as shown below:
Streszczenie treści zawartej na stronie nr. 11
FS-8700-122 X30 Profibus DP Master Manual Page 11 of 16 3) Expand the Profibus DP tree and drag the Slave Device you want to connect to onto the Bus Configuration window. Note: If your device does not show up, import the device’s GSD file by right clicking on Profibus DP and selecting Install new GS*-file. The ANYBUS-S PDP Slave device is shown here for illustration purposes. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA We
Streszczenie treści zawartej na stronie nr. 12
FS-8700-122 X30 Profibus DP Master Manual Page 12 of 16 4) Right-click on the Profibus Slave and assign its Profibus address. 5) Continue adding all other Slaves and setting their Profibus addresses. 6) Right click on the ABM-DPV Master device and select Object Properties. Set the Master Station Address to the same as the System_Station_Address used in the FieldServer’s config.csv file. Also set the desired Profibus Network Baud rate. FieldServer Technologies 1991 Tar
Streszczenie treści zawartej na stronie nr. 13
FS-8700-122 X30 Profibus DP Master Manual Page 13 of 16 7) Select the first slave device, right-click on the Slot 1 line and choose Module selection. Now you have to add I/O modules up to the total number of bytes or words that will be transferred with this slave as set up in the config.csv file. For Example, for the Map Descriptor for Slave1 using 50 Words In and Out, you would choose the following modules: 8) Continue selecting other Slaves and adding modules for them as
Streszczenie treści zawartej na stronie nr. 14
FS-8700-122 X30 Profibus DP Master Manual Page 14 of 16 Important Note: Note that the X30 must be running with a valid configuration file before it will allow download of a new database. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Streszczenie treści zawartej na stronie nr. 15
FS-8700-122 X30 Profibus DP Master Manual Page 15 of 16 Appendix A. Troubleshooting tips Appendix A.1. Connection Tips & Hints An error message displays when trying to download the Profibus database? • Ensure you have selected the correct serial port in the configure path setting. • Ensure that the X30 is powered up with a valid configuration file declaring all the slaves to be communicated with. • Confirm that the Run Led is flashing. • The following message on the E screen of
Streszczenie treści zawartej na stronie nr. 16
FS-8700-122 X30 Profibus DP Master Manual Page 16 of 16 THIS PAGE INTENTIONALLY LEFT BLANK FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com