Streszczenie treści zawartej na stronie nr. 1
Serial Number
1.6L
20/25/30 kW
Models
STANDBY GENERATOR
OWNER'S MANUAL
A new standard of reliability
Not intended for use in critical life support applications.
—CAUTION—
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION!
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
This manual should remain with the unit.
Catalog Number OMASPEA025-2
Cover113 Rev. B 09/07 Part No. 0G5244
Streszczenie treści zawartej na stronie nr. 2
Standby Generator Sets Table of Contents OPERATION ...........................................................9-1 SECTION PAGE SAFETY RULES ................................................ 1-1 Generator Control and Operation ................................9-1 INTRODUCTION .....................................................1-3 Operating Unit with Manual Transfer Switch ...............9-1 Read this Manual Thoroughly ...................................1-3 Engine Start-up and Transfer .........
Streszczenie treści zawartej na stronie nr. 3
Standby Generator Sets Important Safety Instructions SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment. GENERAL HAZARDS WARNING: The engine exhaust from this product � For safety reasons, the manufacturer recommends contains chemicals known to the state that this equipment be
Streszczenie treści zawartej na stronie nr. 4
Standby Generator Sets Important Safety Instructions � Before performing any maintenance on the gen- � Generators installed with an automatic transfer erator, disconnect its battery cables to prevent switch will crank and start automatically when accidental start-up. Disconnect the cable from the normal (utility) source voltage is removed or is battery post indicated by a NEGATIVE, NEG or (–) below an acceptable preset level. To prevent such first. Reconnect that cable last. automatic start-
Streszczenie treści zawartej na stronie nr. 5
Standby Generator Sets Important Safety Instructions INTRODUCTION This symbol points out potential explosion Thank you for purchasing this model of the standby hazard. generator set product line. This symbol points out potential fire hazard. Every effort was expended to make sure that the information and instructions in this manual were This symbol points out potential electrical shock both accurate and current at the time the manual was hazard. written. However, the manufacture
Streszczenie treści zawartej na stronie nr. 6
Standby Generator Sets General Information NOTE: IDENTIFICATION RECORD For actual information related to this particular DATA LABEL model, please refer to the Manual Drawing Listing located at the end of this manual, or to the data Every generator set has a DATA LABEL that contains label affixed to the unit. important information pertinent to the generator. The data label, which can be found attached to the gen- Generator Model and Serial Number erator’s lower connection box, lists the un
Streszczenie treści zawartej na stronie nr. 7
Standby Generator Sets Equipment Description EQUIPMENT DESCRIPTION COOLANT RECOMMENDATIONS This equipment is a revolving field, alternating cur- Use a mixture of half low silicate ethylene glycol rent generator set. It is powered by a gaseous fueled base anti-freeze and deionized water. Cooling system engine operating at 1800 rpm for 4-pole direct drive capacity is listed in the specifications. Use only deion- units, 3600 rpm for 2-pole direct drive units and ized water and only low silicate a
Streszczenie treści zawartej na stronie nr. 8
Standby Generator Sets Engine Protective Devices OVERCRANK SHUTDOWN ENGINE PROTECTIVE DEVICES The standby generator may be required to operate for After a prespecified duration of cranking, this func- long periods of time without an operator on hand to tion ends the cranking if the engine has failed to monitor such engine conditions as coolant tempera- start. The overcrank LED will turn ON. Turn OFF the ture, oil pressure or rpm. For that reason, the engine AUTO/OFF/MANUAL switch, then tur
Streszczenie treści zawartej na stronie nr. 9
Standby Generator Sets Fuel Systems PROPANE VAPOR WITHDRAWAL FUEL SYSTEM FUEL SYSTEM This type of system utilizes the vapors formed above FUEL REQUIREMENTS the liquid fuel in the supply tank. Approximately 10 to 20 percent of the tank capacity is needed for fuel The standby generator may be equipped with one of expansion from the liquid to the vapor state. The the following fuel systems: vapor withdrawal system is generally best suited for � Natural gas fuel system smaller engines that r
Streszczenie treści zawartej na stronie nr. 10
Standby Generator Sets Specifications Engine Lubrication System SPECIFICATIONS Type of Oil Pump ...................................................................... Gear Oil Filter .............................................................Full Flow, Cartridge GENERATOR Crankcase Oil Capacity ....................................................4 U.S. qts. Type ............................................................................. Synchronous Rotor Insulation .........................
Streszczenie treści zawartej na stronie nr. 11
Standby Generator Sets Specifications Figure 6.1 — Interconnections Utility In Transfer Switch CONTROL PANEL NEUTRAL TO ALTERNATOR Gen N1 NEUTRAL N1 N2 N2 23 23 GENERATOR 194 194 Load 4- # 14 GA 186 CONNECTION CIRCUIT BREAKER WIRES TO 178 183 BOX Out 178 GENERATOR CONNECTION Battery BOX Charger Input GROUND TO GENERATOR 120 Volt + Neutral CONNECTION BOX Grd To Generator Control Panel FRAME RAIL CIRCUIT BREAKER SIZE KW VOLTS / AMPS LUG SIZE 25 240 1
Streszczenie treści zawartej na stronie nr. 12
Standby Generator Sets General Information GENERATOR AC LEAD CONNECTIONS ALTERNATOR POWER WINDING See “Voltage Codes”. This generator may be rated CONNECTIONS at any one of three voltages, either single-phase or three-phase. The electrical wires in the unit’s AC con- 3-PHASE ALTERNATORS nection (lower) panel should be installed according to the number of leads and the voltage/phase required The generator is designed to supply 3-phase electri- for the application. If there are any questions
Streszczenie treści zawartej na stronie nr. 13
Standby Generator Sets Installation PRIOR TO INITIAL START-UP INSTALLATION Refer to the separate “Installation Guide” supplied with the unit. Prior to initially starting the generator, it must PREPARATION BEFORE START-UP be properly prepared for use. Any attempt to The instructions in this section assume that the crank or start the engine before it has been standby generator has been properly installed, ser- properly serviced with the recommended types viced, tested, adjusted and othe
Streszczenie treści zawartej na stronie nr. 14
Standby Generator Sets Installation � Battery charger connection to 120 VAC. � Open the valve to the engine fuel line. � Bleed the fuel system of air. (necessary for long fuel � Communication wires connected between transfer lines). switch and generator (HTS only). � Unit secured to pad. � Open the generator main line circuit breaker. � Connect a manometer to the gas line and record the static pressure. It must be as listed in the START-UP CHECKLIST Specifications. � Insert the fuse into the
Streszczenie treści zawartej na stronie nr. 15
Standby Generator Sets Operation GENERATOR CONTROL AND OPERATION Do not crank the engine continuously for longer Refer to the appropriate control panel operator’s than 30 seconds, or the heat may manual for this unit. damage the starter motor. � Let engine stabilize and warm up. OPERATING UNIT WITH MANUAL � Check all applicable instrument and gauge read- ings. When certain that all readings are correct, TRANSFER SWITCH move the transfer switch manual handle to its If the generator was
Streszczenie treści zawartej na stronie nr. 16
Standby Generator Sets Maintenance MAINTENANCE PERFORMED BY COOLING SYSTEM Air intake and outlet openings in the generator com- SERVICE FACILITIES partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow. Before working on the generator, ensure the fol- Without sufficient cooling and ventilating air flow, the lowing: engine/generator quickly overheats, which causes it � The AUTO/OFF/MANUAL switc
Streszczenie treści zawartej na stronie nr. 17
Standby Generator Sets Maintenance Figure 10.1 - Oil Dipstick and Oil Fill Cap EXERCISE SYSTEM Start the generator engine at least once every seven OIL FILL CAP days and let it run at least 20 minutes. For more detailed exercise information, see the respective sec- tions in the Control Panel Technical Manual that is supplied with the unit. INSPECT COOLING SYSTEM � Inspect engine cooling system. See “Maintenance Schedule”. � Check hoses for damage, deterioration, leaks, etc. Correct any di
Streszczenie treści zawartej na stronie nr. 18
Standby Generator Sets Maintenance Figure 10.3 – Engine Air Cleaner CHANGING ENGINE OIL Refer to maintenance performed by service facilities Air Cleaner for engine oil and filter change frequencies. Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows: 1. Remove OIL DRAIN HOSE from its retaining clip. 2. Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container. 3. When all oil has
Streszczenie treści zawartej na stronie nr. 19
Standby Generator Sets Maintenance 3. Have the state of charge and condition checked. MISCELLANEOUS MAINTENANCE This should be done with an automotive-type bat- tery hydrometer. CLEANING THE GENERATOR Keep the generator as clean and as dry as possible. DANGER Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation Storage batteries give off explosive hydrogen resistance. gas. This gas can form an explosive mixture around the battery for
Streszczenie treści zawartej na stronie nr. 20
Standby Generator Sets Service Schedule SERVICE SCHEDULE The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe applica- tion. Use calendar time or accumulated run time, from the previous maintenance interval to determine the next r