Streszczenie treści zawartej na stronie nr. 1
DO NOT
DISCARD
Para obtener un ejemplar en Español de este Pour demander un exemplaire en français de ce Manuel
Manual del propietario, visite www.heatnglo.com. du propriétaire, visitez www.heatnglo.com.
Owner’s Manual
Installation and Operation
Models:
6000G
6000G-LP
6000G-IPI
6000G-IPILP
CAUTION
DO NOT DISCARD THIS MANUAL
• Important operating • Read, understand and follow • Leave this manual with
and maintenance these instructions for safe
party responsible for use
instructions included.
Streszczenie treści zawartej na stronie nr. 2
Read this manual before installing or operating this appliance. Please retain this owner’s manual for future reference. Congratulations Congratulations on selecting a Heat & Glo gas appliance This Owner’s Manual should be retained for future —an elegant and clean alternative to wood burning reference. We suggest that you keep it with your other important documents and product manuals. appliances. The Heat & Glo gas appliance you have selected is designed to provide the utmost in safety, The
Streszczenie treści zawartej na stronie nr. 3
Table of Contents 1 Listing and Code Approvals 9 Gas Information A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 A. Fuel Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 B. Glass Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 B. Gas Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 C. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 C. G
Streszczenie treści zawartej na stronie nr. 4
Listing and Code Approvals 1 1 A. Appliance Certifi cation D. High Altitude Installations U.L. Listed gas appliances are tested and approved with- MODELS: 6000G, 6000G-IPI out requiring changes for elevations from 0 to 2000 feet in LABORATORY: Underwriters Laboratories, Inc. (UL) the U.S.A. and Canada. TYPE: Direct Vent Gas Appliance Heater When installing this appliance at an elevation above 2000 STANDARD: ANSI Z21.88-2000 • CSA2.33-M98 • UL307B feet, it may be necessary to decrease the in
Streszczenie treści zawartej na stronie nr. 5
Inspection Note: The following requirements reference various The state or local gas inspector of the side wall horizon- Massachusetts and national codes not contained in this tally vented gas fueled equipment shall not approve the document. installation unless, upon inspection, the inspector ob- serves carbon monoxide detectors and signage installed H. Requirements for the Commonwealth of in accordance with the provisions of 248 CMR 5.08(2)(a)1 Massachusetts through 4. For all side wall
Streszczenie treści zawartej na stronie nr. 6
Getting Started 2 2 A. Design and Installation Considerations C. Inspect Appliance and Components Heat & Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of WARNING the building and all exhaust gases expelled to the outside. Inspect appliance and components for damage. No additional outside air source is required. Damaged parts may impair safe operation. • Do NOT install damaged components. • Do NOT install incomplete components. CAUTION
Streszczenie treści zawartej na stronie nr. 7
Framing and Clearances 3 3 Note: WARNING • Illustrations reflect typical installations and are FOR Fire Risk DESIGN PURPOSES ONLY. Provide adequate clearance: • Illustrations/diagrams are not drawn to scale. • Around air openings • Actual installation may vary due to individual design preference. • To combustibles • For service access A. Selecting Appliance Location Locate appliance away from traffi c areas. When selecting a location for your appliance it is important to Note: For actual
Streszczenie treści zawartej na stronie nr. 8
insulation. If the appliance is being installed on a cement B. Constructing the Appliance Chase slab, a layer of plywood may be placed underneath to pre- A chase is a vertical boxlike structure built to enclose the vent conducting cold up into the room. gas appliance and/or its vent system. Vertical vents that run on the outside of a building may be, but are not re- C. Clearances quired to be, installed inside a chase. Construction of the chase may vary with the type of build- WARNING ing. Th
Streszczenie treści zawartej na stronie nr. 9
D. Mantel Projections TO CEILING 18 IN T E R IO R W A L L 12 Top V iew 11 10 32 9 8 25 7 19 6 A 18 B 5 17 4 16 3 15 FIREPLACE 14 OPENING 13 12 M A N T E L LE G O R W A LL P R O J EC TIO N S 2-1/2 11 10 If A minimum is ____, then B maximum is_____. 5 Inches 2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16 A Millimeters 62 87 113 138 164 189 Inches 1234 5 ∞ MEASUREMENTS FROM B Millimeters TOP EDGE OF THE OPENING ∞ 25 51 76 102 127 Note: All measurements in inches. Figure 3.4 Clearances to Mantel Legs or
Streszczenie treści zawartej na stronie nr. 10
Termination Locations 4 4 HORIZONTAL A. Vent Termination Minimum Clearances OVERHANG 2 FT. 20 INCHES MIN. VERTICAL MIN. WARNING WALL LOWEST DISCHARGE OPENING Fire Risk. GAS DIRECT VENT Explosion Risk. TERMINATION CAP Inspect external vent cap regularly. X • Ensure no debris blocks cap. 12 • Combustible materials blocking cap may ROOF PITCH ignite. IS X/ 12 • Restricted air fl ow affects burner operation. H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING WARNING Roof Pitch H (
Streszczenie treści zawartej na stronie nr. 11
M N P R Q (See Note 2) V T S S Electrical V V Service D* V = VENT TERMINAL X V = AIR SUPPLY INLET = AREA WHERE TERMINAL IS NOT PERMITTED A = 12 inches.................clearances above grade, veranda, L** = 7 ft. ......................... clearance above paved (See Note 1) (See Note 1) porch, deck or balcony sidewalk or a paved driveway located on public property B = 12 inches.................clearances to window or door M*** = 18 inches................ clearance under veranda, porch, that
Streszczenie treści zawartej na stronie nr. 12
Vent Information and Diagrams 5 5 A. Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams. Symbol Description Vertical First section (closest to appliance) of vertical length V1 Second section of vertical length V2 First section (closest to appliance) of horizontal length H1 8-1/2 in. Second section of horizontal length H2 WARNING Horizontal Fire Hazard. Explosion Risk. Figure 5.1 Asphyxiation Risk. Do NOT connect this gas appliance to a chimney fl ue
Streszczenie treści zawartej na stronie nr. 13
D. Vent Diagrams WARNING Fire Risk. Explosion Risk. Note: The 6000 series fi replaces can adapt to Do NOT pack insulation or other combustibles SLP series vent pipe, if desired. between ceiling fi restops. When venting off the top of the unit, use a DVP-2SL adapter and • ALWAYS maintain specifi ed clearances around a minimum 48 inch vertical section of SLP series vent pipe. venting and fi restop systems. • Install wall shield and ceiling fi restops as speci- After the 48 inch vertical sectio
Streszczenie treści zawartej na stronie nr. 14
1. Top Vent - Horizontal Termination - (continued) Three Elbows V Min. H Max. V Min. H Max. 1 1 2 2 Elbow only 2 ft. 610 mm 0 in. 0 mm 1 ft. 305 mm 6 in. 152 mm 3 ft 914 mm 6 in. 152 mm 2 ft. 610 mm 1 ft. 305 mm 6 ft. 1.8 m 1 ft. 305 mm 6 ft. 1.8 m 2 ft. 610 mm 11 ft.* 3.4 m* 2 ft. 610 mm 10 ft.* 3.1 m* 3 ft. 914 mm 16 ft * 4.9 m* 3 ft. 914 mm 14 ft.* 4.3 m* *H + H = 20 ft. (6.1 m) Maximum V + V + H + H = 40 ft. (12.2 m) Maximum 1 2 1 2 1 2 WARNING Fire Risk. • When using DVP-HRC
Streszczenie treści zawartej na stronie nr. 15
2. Top Vent - Vertical Termination Flue Restrictor Instructions 1. Remove Exhaust Shield using a 1/4 inch nut driver by removing the four screws securing it in place (see Figure 5.7). V = 40 ft. Max. (12.4 m) 1 V = 3 ft. Min. (914 mm) 1 Note: If installing a vertical vent/ termination off the top of the appli- ance, the optional vertical termina- tion baffl e should be used. EXHAUST SHIELD FLUE RESTRICTOR No Elbow Figure 5.7 2. Break the Flue Restrictor into two pieces. Do this by bending the
Streszczenie treści zawartej na stronie nr. 16
4. Center the Flue Restrictor on vent and secure in place 3. Match the amount of vertical you have in the sys- by using two self-tapping screws (see Figure 5.10). tem with the chart to fi nd the appropriate position 5. Reinstall the Exhaust Shield. to set the Flue Restrictor (see Figure 5.9 ). TOP VENT REAR VENT Vertical NG LP NG LP No No No 4 ft. 1-1 1 2 3 4 5 Restrictor Restrictor Restrictor No 8 ft. 2-2 1-2 1-1 Restrictor 15 ft. 3-3 3-2 2-2 1-2 SETTINGS 20 ft. 3-4 3-3 3-3 2-3 2
Streszczenie treści zawartej na stronie nr. 17
2. Top Vent - Vertical Termination - (continued) V H + H V V + V Minimum H + H Maximum 1 1 2 2 1 2 1 2 Three Elbows Elbow only 1 ft. 305 mm * * * 1 ft. 305 mm 6 in. 152 mm 2 ft. 610 mm * * * 2 ft. 610 mm 1 ft. 305 mm 2 ft. 610 mm * * * 2 ft. 610 mm 2 ft. 610 mm 4 ft. 1.2 m * * * 4 ft. 1.2 m 3 ft. 914 mm 9 ft. 2.7 m * * * 9 ft. 2.7 m 4 ft. 1.2 m 18 ft. 5.5 m * * * 18 ft. 5.5 m H + H = 20 ft (6.1 m) Maximum V + V + H + H = 40 ft (12.2 m) Maximum 1 2 1 2 1 2 INSTALLED HORIZONTALLY
Streszczenie treści zawartej na stronie nr. 18
3. Rear Vent - Horizontal Termination H = 16 in. (406 mm) Maximum No Elbow 1 Figure 5.13 One 45º Elbow 0 Do not use a 45 elbow in corner installations. 0 Use two 90 elbows instead. Figure 5.14 18 Heat & Glo • 6000G, 6000G-IPI • 2103-900 Rev. M • 9/08
Streszczenie treści zawartej na stronie nr. 19
3. Rear Vent - Horizontal Termination - (continued) H Maximum V Minimum H H + H Maximum 1 1 2 1 2 Two Elbows Back to Back 1 ft. 305 mm 1 ft. 305 mm 2 ft. 610 mm 90º Elbows 2 ft. 610 mm 6 in. 152 mm 2 ft. 610 mm 4 ft. 1.2 m 3 ft. 914 mm 1 ft. 305 mm 2 ft. 610 mm 5 ft. 1.5 m 3 ft. 914 mm 2 ft. 610 mm 4 ft. 1.2 m 7 ft. 2.1 m 3 ft. 914 mm 3 ft. 914 mm 9 ft. 2.7 m 12 ft. 3.7 m 3 ft. 914 mm 4 ft 1.2 m 18 ft. 5.5 m 20 ft.* 6.1 m* V + H + H = 40 ft (12.2 m) Maximum H = 3 ft (914 mm) Maximum 1 1
Streszczenie treści zawartej na stronie nr. 20
4. Rear Vent - Vertical Termination V Minimum H Maximum 1 1 One Elbow 6 in. 152 mm 2 ft. 610 mm 1 ft. 305 mm 3 ft. 914 mm 2 ft. 610 mm 5 ft. 1.5 m 3 ft. 914 mm 7 ft. 2.1 m 4 ft. 1.2 m 8 ft 2.4 m 5 ft. 1.5 m 8 ft 2.4 m V + H = 40 ft (12.2 m) Maximum 1 1 H = 8 ft (2.4 m) Maximum 1 Figure 5.17 H + H Maximum V Minimum 1 2 1 Two Elbows Back to Back 90° Elbows 3 ft. 914 mm 2 ft 610 mm 6 ft. 1.8 m 4 ft 1.2 m 9 ft. 2.7 m 6 ft. 1.8 m 12 ft. 3.7 m 8 ft. 2.4 m 15 ft. 4.6 m V