Streszczenie treści zawartej na stronie nr. 1
DEH40206 Installation Instructions
GE Total Lighting Control
ProSys Lighting Control System
Catalog Number RSxPS-x
ProSys™ Softwired Switches, 1-, 2-, 4- and 8-button
RS1SWS-x RS2SWS-x
RS4PS-x RS8PS-x
DESCRIPTION
The ProSys Lighting Control System is a small network of enabled override function. The switch will be disabled
relay panels and occupant control switches linked by a 4-wire except when a key is used to activate a 5 minute
dataline. Together, these devices form a reconfigurable override
Streszczenie treści zawartej na stronie nr. 2
DEH40206 Installation Instructions If you have purchased the ProSys Lighting Control System (the stand-alone system), the devices (panels, switches and clock) will be in self-install mode. This means that as soon as they are connected to the network, they are operational and can communicate with each other. If you have purchased the ProSys LM Lighting Control System along with the ProSys LM software, the devices will be in software-install mode. This means that you must use your network manageme
Streszczenie treści zawartej na stronie nr. 3
DEH40206 Installation Instructions DATALINE SWITCH INSTALLATION AND TESTING The 1-, 2- and 4-button dataline switches mount in standard Low-Resistance Red/Black Data Path single-gang switch boxes. The 8-button unit mounts in a After wiring the last switch on the local dataline, disconnect standard 2-gang box. The dataline is typically connected in a the red and black wires from the Local Dataline terminals in “daisy-chain” from switch to switch, eliminating expensive the relay panel and wire nut
Streszczenie treści zawartej na stronie nr. 4
NUMBER AND DOCUMENT DATALINE SWITCHES As shown in Figure 1 below, dataline switches are numbered A separate ProSys SWITCH DOCUMENTATION form sequentially beginning with 01-01 (Panel 01-Switch 01). A should be used for each relay panel to record the number of single switch unit may have 1, 2, 4 or 8 buttons. Switch units the switch and its number of buttons. Allow one line for each should be identified on the reflected ceiling plan showing the button as shown on the form in Figure 2 below. For ex
Streszczenie treści zawartej na stronie nr. 5
SOFTWIRING A DATALINE SWITCH TO A GROUP OF RELAYS Dataline switches are typically wired to a single relay or group of relays within a panel (See Figure 3, right). Wiring to Figure 3 – Softwiring a Dataline Switch a channel is a shortcut — it provides a simple way of With the wallplate removed and the switch’s master manually overriding all of the relays which are grouped to an button flipped open… automation channel (A-H) within a panel. 1 Press the SOFTWIRE tab. The LED next to the tab will tur
Streszczenie treści zawartej na stronie nr. 6
DEH40206 Installation Instructions SWITCH BUTTON LABELING 3 1 The individual switch buttons provide space for ⁄8" wide x 1 ⁄16" long (9mm x 30mm) label directories. The directory labels can be attached simply by removing the clear lenses, positioning the labels and replacing the lenses as shown at right. If desired, the buttons may be completely removed from the base plate and labeled separately. You may find this method easier to achieve better alignment of the labels. To remove a button from a
Streszczenie treści zawartej na stronie nr. 7
DEH40206 Installation Instructions SPECIAL FUNCTIONS ProSys is designed to provide flexibility without compromising simplicity in installation and operation. The Special Functions Figure 5 described here may be used to enhance the operation of your system, but they are not required in most installations. 01-01 Patterns 01-02 A Pattern is a combination of ONs and OFFs for a group of relays which creates a scene. Any button on a dataline switch 01-03 may be softwired to create such a scene. Simpli
Streszczenie treści zawartej na stronie nr. 8
DEH40206 Installation Instructions SPECIAL FUNCTIONS (CONTINUED) Master Button Alternate Scenarios Figure 8 OFF/RESTORE — The Default Setting The Master Button on the 2-, 4- and 8-button switch is pre- configured to provide an OFF/Restore scenario. If several individual switch buttons are ON, hitting the Master turns all of those buttons OFF. Hitting the Master again would turn those same switches back ON. 1 Example (Figure 8): Assume that in the previous office ⁄3 Lighting plus wall wash exampl
Streszczenie treści zawartej na stronie nr. 9
DEH40206 Installation Instructions SPECIAL FUNCTIONS (CONTINUED) Figure 9 Cleaning Switch Combining the Cleaning Scenario with Pattern operation can provide an elegant solution to control of cleaning lights (see The third DIP switch, when set in Figures 9 and 10). Let’s assume that switch 01-01 has been the OFF position as shown, changes configured as a cleaning switch with button 1 controlling a the operation of the entire switch Pattern in which the north half of the floor is ON and south unit
Streszczenie treści zawartej na stronie nr. 10