Uninterruptible Power Supply
SANUPS
E11A102A
Instruction Manual
M0007084E
Streszczenie treści zawartej na stronie nr. 2
Streszczenie treści zawartej na stronie nr. 3
Introduction Thank you for choosing the SANUPS (E11A102A). SAVE THESE INSTRUCTIONS This manual contains important instructions for E11A102U001 that should be followed during installation and maintenance of the UPS and batteries.To use the UPS correctly and safely, read this manual before using the UPS. After reading, please keep it handy for convenient reference. This UPS is intended for installation in a temperature-controlled indoor environment free of conductive contaminants. ・ Oper
Streszczenie treści zawartej na stronie nr. 4
1. Safety Precautions PRECAUTIONS (IMPORTANT SAFETY INSTRUCTIONS) Before installing, operating, performing maintenance or inspecting the UPS, be sure to read this manual and accompanying documents carefully to obtain a clear understanding of the information related to its operation, safety and important precautions. This manual described two warning levels, DANGER and CAUTION, as described below. :Denotes immediate hazards which WILL probably cause severe bodily injury or death,
Streszczenie treści zawartej na stronie nr. 5
1. Installation Precautions CAUTION ! • The UPS should be installed only by technically qualified personnel. Improper installation can result in electric shock, bodily injury, and/or fire. • Never operate or store the UPS in the following environmental conditions. Doing so may cause the UPS to malfunction, sustain damage or deteriorate, which could result in a fire. a. In ambient environmental conditions other than those specified in the product brochure and instruction manual (tempera
Streszczenie treści zawartej na stronie nr. 6
3. Operating Precautions ! DANGER • Immediately shut the UPS off if it malfunctions, or if an unusual odor or noise is observed. Failure to do so may result in a fire. • To avoid electric shock, do not open the cover of the UPS. CAUTION ! • Risk of electric shock, do not remove cover, No user serviceable part inside. Refer serviving to qualified personnel. • The space around the UPS must be well ventilated. Otherwise, gas produced by battery charging could result in rupture or exp
Streszczenie treści zawartej na stronie nr. 7
4. Radio Frequency Interference CAUTION ! • This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and. if not installed and used in accordance with the instruction manual, may cause harmful i
Streszczenie treści zawartej na stronie nr. 8
7. Battery Handling Precautions CAUTION ! • Risk of explosion if battery is replaced by an incorrect type • Dispose of used batteries according to the instructions. • Battery servicing should be performed by technically qualified personnel. Keep unqualified personnel away from batteries. • Replace batteries only with the same model and brand: HRL1234WF2FR manufactured by CSB BATTERY Co., LTD. • Customers should not dispose of used batteries themselves. Contact your nearest sales re
Streszczenie treści zawartej na stronie nr. 9
2. For Proper Operation 2.1 Input Power Requirements (1) Make certain that the AC input voltage and frequency correspond to the specified equipment rating (100V, 110V, 115V, 120V, within -20% and +15%, and 50 or 60 Hz ±5%: Active Filter and Economy Mode*). * The frequency variation range is set to ±3% when the UPS is shipped from the factory. If the frequency variation range of input power supply is ±5%, select ±5% as described in item ③ “Frequency sync range” of 10.1 “Setup Menu I
Streszczenie treści zawartej na stronie nr. 10
(5) Insulation testing Before testing indoor wiring insulation, shut down the UPS and disconnect the input and output cables. Conducting an insulation test with the UPS connected may damage electronic components such as the built-in arrester. (6) Rack support rails (not supplied) are required to mount the UPS on a rack. For details, contact your supplier or Sanyo Denki representative. 2.4 Dealing with Errors Contact your supplier or Sanyo Denki representative if any of the following
Streszczenie treści zawartej na stronie nr. 11
Filter Charger Filter 4. Overview The SANUPS E11A is a stationary-type uninterruptible power supply designed to provide high-quality, stable AC power to critical equipment that requires continuous, uninterrupted power. The UPS is comprised of rectifier, charger, inverter, battery, and utility power transfer (bypass) circuits. In the event of failure of the AC utility power source, AC output to the load is sustained by the inverter converting DC power from the batteries. When th
Streszczenie treści zawartej na stronie nr. 12
5. External Dimensions and Part Names 5.1 Front and Back Panels (Inside cover) ③ 440 17.32 ② (Inside cover) ① ⑤ ⑦ ⑨ MAIN SW EXT. BATT ⑫ ⑥ ④ ⑧ ⑩ ⑪ Length: 1.8 m Depth: 408 mm (16.06 inch) (70.9 inch) Weight: 16 kg (35.27 lbs) No. Name Label Function Control panel for control operations, UPS status ① - Control panel and indicators display, and function settings ② Forced bypass switch Forced Bypass Switch
Streszczenie treści zawartej na stronie nr. 13
5.2 Control Panel and Indicators LED11 LED5 LED6 LED10 LED7 LED8 ① LED12 LED4 ② LED9 ③ LED0 LED1 LED2 LED3 Functions No. Label Fast Status display Lit Not lit Slow blink blink LED0 INPUT Input power status Normal input - Input error - LED1 OUTPUT UPS output power status Inverter operation OFF Bypass operation - Economy mode - LED2 ECONOMY Operation mode OFF (*3) - operation (*1) DOUBLE Double conversion LED3 Operation mode OFF
Streszczenie treści zawartej na stronie nr. 14
5.3 External Interfaces ① UPS back panel MAIN SW EXT. BATT ② No. Name Function Allows you to control the UPS from a computer (PC or workstation) by using the ① PC I/F supplied power management software. Install the power management software (*2) (PC interface) on the computer, and connect the computer to the UPS with the supplied network (RS-232C) cable. Interface mode (*1): Workstation mode (*1): Use the controls on the front panel to set the int
Streszczenie treści zawartej na stronie nr. 15
6. Installation ・ When installing the UPS, carefully follow the instructions in this Instruction Manual. ・ Install the UPS on a stable surface that can bear the weight (16 kg, 35.27 lbs). This surface should be flat, so the UPS cannot fall and cause bodily injury. ・ The possibility of vibration and shock should be minimized at the installation location. ・ All work that involves lifting the UPS, such as mounting it in a rack or attaching the ! stand, should be carried out by at lea
Streszczenie treści zawartej na stronie nr. 16
6.4 Preparation Before Installation ・ Wear insulated gloves and take other precautions when connecting the batteries. Otherwise electric shock can result. ・ There is a constant voltage (max. approx. 24V: approx. 12V × 2) at the battery terminals. ! Do not touch them with your hands or short circuit them. Bodily injury can result. ・ The battery connector cannot be inserted in the wrong orientation. If it does not go in, CAUTION do not try to force it. Doing so can damage the con
Streszczenie treści zawartej na stronie nr. 17
6.5 Attaching the Stand ・ Unless the UPS is secured solidly in place, it can shift or fall during seismic events (earthquakes) or when it is subjected to shock or vibration, possibly ! causing bodily injury. CAUTION ・ Be careful not to get your hands caught when installing the stand. Proceed as follows to attach the supplied stands. ① Prepare two supplied stands. ② Place the UPS in the stand. Always place with the left side of the UPS on the bottom, and the cont
Streszczenie treści zawartej na stronie nr. 18
6.6 Mounting a Rack Mount Type UPS ・ Be careful to avoid straining your lower back when moving and installing the UPS. ・ The UPS weighs about 16 kg (35.27 lbs). Always get at least one other person to help you install it. Bodily injury can result if the UPS falls. ・ The UPS can fall when it is moved or installed, resulting in bodily injury or ! damage to the UPS. Hold the bottom side of the UPS firmly with both hands when CAUTION installing it. ・ For safety, use L-type rails
Streszczenie treści zawartej na stronie nr. 19
7. Wiring ・ Check that input and output power plugs are firmly seated. Do not exceed the rated capacity when connecting loads to the output terminals. Check that plugs and cards are firmly seated in the external interfaces. Failure to observe ! these precautions can result in electric shock, fire, or bodily injury. CAUTION ・ The input power plug must be grounded. Failure to ground it can result in electric shock. 7.1 UPS Wiring ① Check that MAIN SW is in the “OFF”
Streszczenie treści zawartej na stronie nr. 20
③ Connect the input power plugs of the load devices to the output terminals. Terminal rated capacity AC125V 15A MAIN SW The total load connected to the 6 output terminals must not exceed 10A. EXT. BATT Output terminal capacity Note If you must make a single-wire 125V 15A grounded connection, always U terminal × 6 connect the ground phase to the E V terminal (phase) side. V Note The total output from all output terminals must not exceed 10A. 7