User's Manual
Streszczenie treści zawartej na stronie nr. 2
SmartSine User's Manual 1. Introduction 2 2. Controls and Indicators 4 3. Installation 6 4. Operation 9 5. Troubleshooting 11 6. Replacing the Battery 12 7. Obtaining Service 15 8. Specifications 16 9. Configurable Parameters & Settings 17 10. Limited Product Warranty 19 11. Declaration of Conformity 21 © Copyright Para Systems, Inc., 2002 1 English
Streszczenie treści zawartej na stronie nr. 3
English Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS ! Please read the manual before installing your SmartSine UPS. It provides the information that should be followed during installation and maintenance of the UPS and the batteries allowing you to correctly set up your system for the maximum safety and performance. Included is information
Streszczenie treści zawartej na stronie nr. 4
! Re-orient the receiving antenna ! Relocate the computer with respect to the receiver ! Move the computer away from the receiver ! Plug the computer into a different outlet so that the computer and receiver are on different branch circuits. ! Shielded communications interface cables must be used with this product. WARNING: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Receiving Insp
Streszczenie treści zawartej na stronie nr. 5
English Para Systems Life Support Policy As a general policy, Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or malfunction of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. Para Systems does not recommend the use of any of its products in direct patient care. Para Systems will not knowingly sell its products for
Streszczenie treści zawartej na stronie nr. 6
FRONT PANEL INDICATORS On-Line/On-Battery/Boost/Buck LED Fault LED Overload LED Weak/Bad Battery LED Site Wiring Fault LED On/Off/Test Button Press and release the ON/OFF/Test Button after 1 beep to turn the UPS ON or OFF (see section 4). On-Line On-Battery Buck Boost The On-Line/On-Battery/Boost and Buck (green) LED illuminates in a steady state when the UPS is on and supplying AC power to the load. The LED blinks and the audible alarm sounds, when supplying battery power to the load. T
Streszczenie treści zawartej na stronie nr. 7
English REAR PANEL 4 5 6 3 2 1 7 9 8 1. The RJ-45/RJ-11 modular connectors are used for 10 Base-T network/single line telephone surge protection. (see section 3) 2. The communications port is for UPS monitoring and control. (see section 4) 3. The output receptacles are NEMA 5-15R type. 4. Rating/Serial number label. 5. The Smart Slot is for MINUTEMAN option cards. 6. The output circuit breakers will trip in the event the individual banks of the output receptacles exceed the rating of the circui
Streszczenie treści zawartej na stronie nr. 8
Install the UPS in a temperature controlled environment that is free of conductive contaminants. Select a location which will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged. Operating Temperature: 0 to 40 degrees C (+32 to 104 degrees F) Operating Elevation: 0 to 3,000m (0 to 10,000 ft) Operating and Storage Relative
Streszczenie treści zawartej na stronie nr. 9
English CONNECTING THE UPS TO AN AC SOURCE Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use extension cords, adapter plugs, power strips or surge strips. CHECKING THE SITE WIRING FAULT After plugging in the UPS, check the Site Wiring Fault (SWF) LED on the front panel of the UPS. If the LED is illuminated, the UPS is plugged into an improperly wired AC outlet. If the UPS indicates a Site Wiring Fault, have a Qualified CAUTION! Electrician correct the problem. CHAR
Streszczenie treści zawartej na stronie nr. 10
English TURNING THE UNIT ON/OFF ON / OFF / Test Button Press and release the ON/OFF/Test Button after one beep to turn the UPS ON and supply power to the load. The load is immediately powered while the UPS runs a five-second self test. Press and release the ON/OFF/Test Button after one beep to turn the UPS OFF. The UPS will continue to charge the batteries whenever it is plugged into an AC outlet and there is AC present. SELF TEST The self test feature is useful to verify the correct operatio
Streszczenie treści zawartej na stronie nr. 11
English ALARMS ON BATTERY When the UPS is operating on the batteries, the On-Line LED will blink and the audible alarm will sound once every 10 seconds. The alarm will stop once the UPS returns to the On-Line operation. UPS FAULT When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will emit a sustained tone. The fault condition, in some instances, may be reset by turning the UPS OFF and then ON. (see section 5 Troubleshooting) OVERLOAD When the amount of load attache
Streszczenie treści zawartej na stronie nr. 12
Possible Cause What To Do Symptom UPS will not turn on On/Off/Test button not Press and release the On/Off/ pushed Test button to start UPS UPS operates in Input AC circuit breaker is Reset circuit breaker by battery mode only, tripped pressing the plunger back in. even though there is If the AC circuit breaker trips normal AC present after UPS starts up, reduce the load on the UPS Fault LED is UPS has detected an Call for service illuminated internal fault Have a Qualified Electrician Site Wir
Streszczenie treści zawartej na stronie nr. 13
English REPLACING THE BATTERY (AUTHORIZED SERVICE PERSONNEL ONLY) The SmartSine UPS has an easy to replace hot-swappable batteries. Please read all of the Warnings and Cautions before attempting to service the batteries. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. This Uninterruptible Power Supply contains potentially hazardous WARNING! voltages. Do not attempt to disassemble the UPS beyond battery replacem
Streszczenie treści zawartej na stronie nr. 14
CAUTION: Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressure operated vents. These UPSs contain sealed non-spillable lead acid batteries. SmartSine S 700 S 1000 S 1400 S 2000 Model # Battery 2-12V7Ah 2-12V17Ah 2-12V17Ah 2-12V12Ah Model # BP7-12 B.B. Part # BP12-12 BP12-17 BP12-17 CSB Part # GP1272 F2 GP12120 F2 GP12170 B1 GP12170 B1 Yuasa Part # NP 7-12 NP 12-12 NP 17-12 NP 17-12 BATTERY REPLACEMENT PROCEDURE PLEASE READ THE C
Streszczenie treści zawartej na stronie nr. 15
English 8. Disconnect the positive (red) wire from the battery positve terminal. 9. Using the pull tab, pull the batteries out far enough to get to the battery negative (black) wire. DO NOT pull the batteries out by pulling the battery jumper wires. 10. Disconnect the battery negative (black) wire from the battery negative terminal. 11. Using the pull tab, pull the batteries out completely. DO NOT pull the batteries out by pulling the battery jumper wires. 12. Remove the
Streszczenie treści zawartej na stronie nr. 16
IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.Verify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3.Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax MINUTEMAN Technical Support at the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or visit our Web site at www.minutemanups.com the "Discussion Board". Please
Streszczenie treści zawartej na stronie nr. 17
English MODEL NUMBER S 700 S 1000 S 1400 S 2000 Acceptable input voltage 0 - 165 VAC Input voltage (on-line 80 - 150 VAC operation) Output voltage (AC Mode) 110/120V Settings: 104-130 VAC, 127V Setting: 104-134 VAC Nominal input frequency 50 or 60 Hz, autosensing Resettable circuit breaker Input protection Frequency limits (AC Mode) 50 or 60 Hz, +/-6Hz 2-6 mS typical Transfer time Maximum load 700VA 1000VA 1400VA 2000VA 500W 700W 1000W 1400W On-battery output voltage Default 120VAC / User select
Streszczenie treści zawartej na stronie nr. 18
English (These items may require optional software or hardware) User Choices Description Function Factory Default UPS ID SmartSine Up to 64 Use this function to uniquely identify the UPS in your network characters configuration to define the UPS Date of Date of battery Enter the current date when Battery manufacture replacement - replacing batteries install day/month/year date XX/XX/XXXX Up to 5 At first battery replacement, reset Battery 1826 characters life in to reflect actual number of days
Streszczenie treści zawartej na stronie nr. 19
English Customized Output Receptacle Panels The SmartSine UPS has a removable receptacle panel. The receptacle panel can be configured with one locking receptacle and two duplex receptacles. This will allow the user to customize the output receptacles for their specific applications. MINUTEMAN will only use UL or CE approved receptacles. Here is one example that could be used: one L5-20R, two 5-15/20R duplexes. To customize your MINUTEMAN UPS for your specific application, contact your local
Streszczenie treści zawartej na stronie nr. 20
English LIMITED PRODUCT WARRANTY Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty