UPStation GXT™
6 & 10 kVA
230V
USER MANUAL
English
Streszczenie treści zawartej na stronie nr. 2
IMPORTANT SAFETY INSTRUCTIONS 1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT SAFETY INSTRUCTIONS. Read all safety and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individuals without previous training. 2. This product is designed for Commercial/Industrial use only. It is not intended for use with life sup
Streszczenie treści zawartej na stronie nr. 3
10. Storing magnetic media on top of the UPS may result in data loss or corruption. 11. Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol cleaners. GLOSSARY OF SYMBOLS Indicates AC Input Indicates AC Output Indicates Caution: Note the accompanying instruction Indicates the position of a fuse Requests the user to consult the manual for additional information Indicates that the unit contains a valve regulated lead aci
Streszczenie treści zawartej na stronie nr. 4
INTRODUCTION AND SYSTEM DESCRIPTION Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure, which may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT protec
Streszczenie treści zawartej na stronie nr. 5
RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to regulated DC power for use by the inverter, while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives: the mains power is used as efficiently as possible by the UPS, and the amount of distortion reflected on the mains is reduced. This results in clean
Streszczenie treści zawartej na stronie nr. 6
CONTROLS AND INDICATORS Fault Indicator UPS ON / BYPASS Alarm Silence / Manual Battery Test UPS ON BATTERY Output OFF / Bypass AC INPUT Load / Battery Level Indicators Fault Indicator (Red) The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to Troubleshooting Guide). BYPASS Indicator (Amber) The BYPASS indicator is illuminated when the UPS is operating from BYPASS power.
Streszczenie treści zawartej na stronie nr. 7
The UPStation GXT is equipped with automatic and remote battery test features. The automatic test occurs every 14 days if a manual battery test has not been performed or if mains has not been interrupted (14 day timer resets if unit goes to battery). Should the battery fail this test, the fault indicator along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to Troubleshooting Guide). The remote test feature functions with either SiteNet® 2 or SiteNet® SNM
Streszczenie treści zawartej na stronie nr. 8
TM DB-9 Intellislot GXT 6 & 10 kVA Communications Communications Component Diagram Port Port 230 & 230X Models Shown Output Voltage Selector Switches TM Intellislot DB-9 Communications Communications Port Port Breakers Output Voltage Selector Switches Battery Input Output Breaker Input Output Battery Breaker Breaker Breaker Hardwire Terminal Blocks Hardwire Terminal Blocks Adjustable levels 6
Streszczenie treści zawartej na stronie nr. 9
OPERATING MODES NORMAL MODE OPERATION- UPS mode During normal operation, mains power provides energy to the UPS. The filters, the power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green LED’s indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate an
Streszczenie treści zawartej na stronie nr. 10
BYPASS MODE OPERATION During BYPASS operation, mains power provides energy to your load and maintains the batteries in a fully charged state. The four green LED’s indicate an approximate level of load in 25% increments. If the BYPASS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate Bypass Mode Operation at and sound an alarm. 51-75% loading The display template indicates the percentage of load on the output. CAUTION: The BYPASS power path does n
Streszczenie treści zawartej na stronie nr. 11
STARTING THE UPS 1. Ensure the load equipment is turned off, and all loads are properly connected to the UPS output. 2. Check that the mains wall isolator is ON. Turn On (Close) the Battery circuit breaker, the Input and Output circuit breakers in that order. The UPS will now automatically start up and default to BYPASS mode once the UPS is connected to an active AC mains supply and the Battery and Input circuit breakers are closed. At the end of the startup sequence the BYPASS LED sho
Streszczenie treści zawartej na stronie nr. 12
SWITCHING FROM OUTPUT OFF TO UPS or UPS to BYPASS to OFF 1. If the UPS is in OUTPUT OFF condition, with all rear mounted breakers in the ON position, and the AC input LED and the bottom LED of the BATTERY/LOAD array lit. To go to UPS mode, press the UPS ON/ALARM /BATTERY TEST button until a “Beep” is heard. The UPS will then go through its start-up routine ending up after approximately 10 seconds with the UPS LED lit. 2. If the UPS is operating in UPS mode and there is a need to go to
Streszczenie treści zawartej na stronie nr. 13
TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the UPStation GXT develops a problem. Use this information to determine whether external factors cause the problem and how to remedy the situation. 1. The fault indicator will illuminate indicating the UPS detected a problem. 2. An alarm will sound, alerting that the UPS requires attention. 3. One or more additional load/battery level LED indicators will be illuminated to provide a
Streszczenie treści zawartej na stronie nr. 14
AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds Low battery Two short beeps every five seconds Output overload (bypass) One short beep every half second Over temperature (bypass) One second beep every four seconds DC Bus over voltage (bypass) One second beep every four seconds PFC failure (bypass) One second beep every four seconds Inverter failure One second beep every four seconds Battery Test failure Two second beep every mi
Streszczenie treści zawartej na stronie nr. 15
TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION Fault and Bypass UPS overloaded or load Check load level display and indicators and all load equipment is faulty remove non-essential loads. level LED's are Recalculate load VA and illuminated reduce number of loads connected to UPS. Check load equipment for faults. Fault and Bypass UPS internal fan has a Press Alarm silence button. indicators and problem or UPS Once the temperature is diagnostic LED A are shutdown due to reduced, the UPS
Streszczenie treści zawartej na stronie nr. 16
UPS MONITORING The UPStation GXT UPS has the capability of being monitored with stand alone computers, network workstations, network servers, or UNIX hosts via the DB-9 socket located on the rear of the UPS. This capability is used in applications requiring the UPS to provide status and power monitoring information to the computer system. For example, during a mains power failure, the information can be used by the computer’s operating system or application program to automatically sav
Streszczenie treści zawartej na stronie nr. 17
MAINTENANCE The UPStation GXT UPS requires very little maintenance. The batteries are valve regulated, non-spillable, lead acid, and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to the mains supply. When storing the UPS for any length of time, it is recommended to apply power to the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries. In no case should the unit be stored in exces
Streszczenie treści zawartej na stronie nr. 18
INSTALLATION INSTRUCTIONS These instructions are for use by competent personnel only. INSTALLATION CONSIDERATIONS Detailed instructions to help you install the UPS are provided in the following pages; however, you should give some consideration to the proposed environment in which the UPS is to be installed, and carry out some preparatory work. INSPECTION Before you install the UPS, give it a thorough visual examination to ensure it has not been subjected to shipping damage. If it is
Streszczenie treści zawartej na stronie nr. 19
OUTPUT INPUT CURRENT AIRFLOW DISSIPATION RATING Amps max 3 Including mains Cfm m h Watts K Btu/hr VA Watts variation/battery charge 130 221 504 1.7 6000 4200 GXT6000 = 33 amps 270 459 840 2.8 10000 7000 GXT10000= 54 amps ELECTRICAL INSTALLATION CONSIDERATIONS This UPS must be installed by competent electrical personnel and wired in accordance with local/national electrical codes. The following information is provided for your guidance. WARNING HIGH EARTH LEAKAGE CURRENT- EARTH C
Streszczenie treści zawartej na stronie nr. 20
ELECTRICAL CONNECTIONS The UPS is supplied with an input/output/ battery terminal block assembly on the rear of the UPS within a cable box. (see outline drawing) The cable box can be removed to enable knockouts to be removed or new holes drilled, to secure the cables. The cable sizes and distribution methods used during installation are subject to local/ national electrical codes of practice , and therefore are not detailed here. However, table 1 gives details of the input current and th