Streszczenie treści zawartej na stronie nr. 1
™
Belkin OmniGuard
Rackmount UPS
Ensure clean and stable power to your
enterprise systems
F6C110-RKM-2U
F6C150-RKM-2U
F6C230-RKM-2U
F6C320-RKM-3U
User Manual
P74264
Streszczenie treści zawartej na stronie nr. 2
TABLE OF CONTENTS INTRODUCTION Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Congratulations and thank you for purchasing the new OmniGuard‘ Rackmount UPS from Belkin. This exciting new series offers enterprise users an excellent Product Highlights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8 high-capacity, space-saving Uninterruptible Power Supply (UPS) solution. The OmniGuard Rackmount UPS comes in a 2U or 3U version offer
Streszczenie treści zawartej na stronie nr. 3
WARNING WARNING NOTICE: This equipment has been tested and found to CAUTION! TO REDUCE THE RISK OF ELECTRICAL SHOCK IN comply with the limits for a Class B computing device in CONDITIONS WHERE LOAD EQUIPMENT GROUNDING CANNOT BE accordance with the specifications in Subpart J of Part 15 of VERIFIED, DISCONNECT THE UPS FROM THE AC POWER OUTLET FCC Rules and the Class B limits for radio noise emissions from BEFORE INSTALLING A COMPUTER INTERFACE CABLE. RECONNECT digital apparatus set out in the Rad
Streszczenie treści zawartej na stronie nr. 4
OVERVIEW HIGHLIGHTS The Belkin OmniGuard Rackmount UPS (Figure 1) offers a 2U or 3U design with a • Enterprise Design capacity range of 1100VA/660 watts to 3200VA/1920 watts of true sine-wave Adapts to your power protection needs for virtually any size environment. output. •Lower Cost of Ownership Lengthens the life of your properly attached components through proactive energy regulation; protects your valuable hardware and information from being lost to abrupt power failures. • Enhanced System
Streszczenie treści zawartej na stronie nr. 5
HIGHLIGHTS PACKAGE CONTENTS Please review the contents of the box to ensure you have all the correct parts The Battery (Red) LED illuminates when the UPS has detected needed to correctly install and use the system. that the batteries are weak/bad. Battery replacement might be •OmniGuard Rackmount UPS required. (See section 5) •6 ft. RS232 communication cable •Pair of standard black brackets for 19" The Site Wiring Fault (Red) LED illuminates when the UPS •Installation manual detects an improperl
Streszczenie treści zawartej na stronie nr. 6
QUICK START PRODUCT INSTALLATION To install the OmniGuard Rackmount UPS, the following steps should be followed: CAUTION! Install the UPS in a temperature-controlled environment that is free of conductive contaminants. Select a location that will provide good air circulation for the UPS at all 1. Find a proper location for the UPS device. times. Avoid locations near heating devices, water, or excessive 2. Mount the device into an appropriate rack or alternative configuration. humidity, or where
Streszczenie treści zawartej na stronie nr. 7
PRODUCT INSTALLATION PRODUCT INSTALLATION Mounting the UPS within the Rack CAUTION! Use two or more people when installing the UPS into The OmniGuard Rackmount UPS includes a mounting kit, which includes two the rack. Use caution, the UPS is extremely heavy. Do not move mounting brackets for a standard 19-inch (48.3cm) rack and eight retaining the rack after the units have been installed. The rack may be screws for mounting the brackets to the UPS device. Note that the screws and unstable due to
Streszczenie treści zawartej na stronie nr. 8
PRODUCT INSTALLATION PRODUCT DIAGNOSTICS Connecting your Equipment (2U Rack, 120VAC models shown) (2U Rack, 230VAC models shown) Plug the equipment into the output receptacles on the back panel of the unit. If UPS Output Surge Only UPS Output Surge Only your UPS is a 3U rack, there are a total of eight outlets, with seven outlets Circuit Circuit Breaker Breaker Protect Protect Caution: Use only Caution: 26 AWG Use only Phone Line 26 AWG Phone Line providing backup plus surge protecti
Streszczenie treści zawartej na stronie nr. 9
PRODUCT DIAGNOSTICS PRODUCT DIAGNOSTICS Turning the Unit On/Off DIP Switch Settings Press and release the “ON/OFF/TEST” switch. After one beep the The DIP-switch setting may be changed by the user to set the desired inverter unit will turn on and supply power to the load. The load is (on-battery) output voltage. The DIP switch must be set to the desired output immediately powered while the UPS runs a five-second self- voltage and then the unit must be turned OFF and restarted to reconfigure the
Streszczenie treści zawartej na stronie nr. 10
PRODUCT DIAGNOSTICS PRODUCT DIAGNOSTICS Alarms Communications Port ON-BATTERY The communications port is a standard DB9 female with both RS232 and When the UPS is operating on the batteries, the On-Line LED will blink and the simulated contact closure capability. The OmniGuard units will poll the port and audible alarm will sound every 10 seconds. The alarm will stop once the UPS activate it for RS232 or contact closure in accordance with the type of cable it returns to On-Line operation. finds
Streszczenie treści zawartej na stronie nr. 11
SOFTWARE FEATURES & INSTALLATION SOFTWARE FEATURES & INSTALLATION 1. Open your Windows Communications Port Connection 2000 Control Panel by Setting Up OmniGuard Power Management Software and The Interface Cable clicking on “Start”, Power Management software and interface cable kits can be used with the UPS. “Setting”, “Control Use only approved interface cables with this UPS. Connect the interface cable to Panel”. the 9-pin communication port on the rear panel of the UPS. Secure the connector t
Streszczenie treści zawartej na stronie nr. 12
SOFTWARE FEATURES & INSTALLATION SOFTWARE FEATURES & INSTALLATION 4. Double-click on the 7. Select the UPS page, Uninterruptible Power and then click on Supply service “Select…” 5. Select the “Log On As: 8. Choose “Generic” This Account” button, from the “Select input the appropriate manufacturer” pull- account information, down list, choose the and then click “OK”. correct COM port, and then click on “Next”. 6. Double-click on the 9. Click on the boxes, as Control Panel’s “Power shown, and the
Streszczenie treści zawartej na stronie nr. 13
FAQS MAINTENANCE Battery Replacement Symptom Possible Cause What To Do The OmniGuard Rackmount series has easy-to-replace hot-swappable batteries. UPS will not turn on On/Off/Test button not pushed Press the On button Please read the following warning statements before attempting to service the momentarily (one beep to battery(s). NOTE: If there is a power interruption while replacing the hot- start UPS) swappable batteries, with the UPS on, the load will not be backed up. UPS operates in batte
Streszczenie treści zawartej na stronie nr. 14
MAINTENANCE OBTAINING SERVICE OmniGuard TM Rackmount UPS Battery Replacement Instructions Important Please Read The Warnings And Instructions Before Attempting To Replace The Batteries: 1. Turn off all connected equipment that is plugged into the UPS 1. Use the TROUBLESHOOTING section to eliminate obvious causes. 2. Press and release, after one beep, the ON/OFF button of the front panel 2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the 3. Remove the front Bezel o
Streszczenie treści zawartej na stronie nr. 15
TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS SPECIFICATIONS (120VAC models) SPECIFICATIONS (230VAC models) Model F6C110-RKM-2U F6C150-RKM-2U F6C230-RKM-2U F6C320-RKM-3U Model F6C110-RKM-2U-230v F6C150-RKM-2U-230v F6C230-RKM-2U-230v F6C320-RKM-3U-230v VA 1100 1500 2300 3200 VA 1100 1500 2300 3200 Watts 660 900 1380 1920 Watts 660 900 1380 1920 Type Rack-Mount Model Type Rack-Mount Model Agency Approvals UL, cUL Agency Approvals CE EMC & Safety Warranty 3 yr. Warranty 3 yr. Input (non-battery
Streszczenie treści zawartej na stronie nr. 16
NOTICE NOTICE The information in this publication is subject to change without notice and is ©2003 Belkin Corporation. All rights reserved. Printed in the U.S.A. provided “as is” without warranty of any kind. The entire risk arising out of the Belkin is a registered trademark with the United Sates Patent and use of this information remains with recipient. In no event shall Belkin be liable Trademark Office. for any direct, consequential, incidental, special, punitive, or other damages Other pr
Streszczenie treści zawartej na stronie nr. 17
belkin.com Belkin Corporation 501 West Walnut Street Compton • CA • 90220 • USA Tel: 310.898.1100 Fax: 310.898.1111 Belkin Components, Ltd. Express Business Park Shipton Way • Rushden • NN10 6GL United Kingdom Tel: +44 (0) 1933 35 2000 Fax: +44 (0) 1933 31 2000 Belkin Components B.V. Starparc Building • Boeing Avenue 333 1119 PH Schiphol-Rijk • The Netherlands Tel: +31 (0) 20 654 7300 Fax: +31 (0) 20 654 7349 Belkin, Ltd. 7 Bowen Crescent • West Gosford NSW 2250 • Australia Tel: +61 (0) 2 4372