Streszczenie treści zawartej na stronie nr. 1
F111 (Series 1,2,3)
In Ceiling Media Air Cleaner
PRODUCT DATA
FEATURES
• High Efficiency Particulate Air (HEPA) filter models are
99.97% efficient and the hospital grade particle filter
models are 95% efficient at 0.3 micron particles. Both
models are more efficient on particles smaller and
larger. There is also a 95% ASHRAE model.
• Circulates up to 1250 cfm.
• Designed to overcome the increase in air flow
resistance normally caused by filter loading.
• White or black color cover to comple
Streszczenie treści zawartej na stronie nr. 2
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER SPECIFICATIONS IMPORTANT Models: Refer to Table 1 for model descriptions. The specifications given in this publication do not include normal manufacturing tolerances. Therefore, Grill Color: White (standard) or Black (add ‘B’ to end of this unit may not exactly match the listed specifica- model number). tions. Also, this product is tested and calibrated under closely controlled conditions, and some minor Blower/Motor: Single speed (standard)
Streszczenie treści zawartej na stronie nr. 3
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER Table 2. F111 Air Volume Specifications for 3 Speed Models (Series 3). a High Medium Low Particulates at Gas, V.O.C. and in cfm in cfm in cfm 0.3 Micron Odor Control 3 3 3 Model Voltage (DOP Test) Modules (2) (m /hr) (m /hr) (m /hr) F111A1253W-3S 120 Vac, 60 Hz, 8.5A 95% ASHRAE N/A 1250 (2120) 800 (1360) 450 (760) F111A1063W-3S 120 Vac, 60 Hz, 7.2A 99.97% HEPA N/A 950 (1610) 775 (1310) 450 (760) F111C1073W-3S 120 Vac, 60 Hz, 7.5A 95% ASHRAE
Streszczenie treści zawartej na stronie nr. 4
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER Space Volume Minimum CEILING (L x W x H) in Cubic Number of Number of Air CLEANING FOOTPRINT Feet (Cubic Meter) Persons Present Cleaners F111 1 (SERIES 35001 to 51000 91 to 120 3 11000) (1050 to 1530) FLOOR 2 51001 to 65000 121 to 180 4 (1530 to 1950) CORRECT INCORRECT 65001 to 80000 181 to 240 5 (1950 to 2400) 80001 to 95000 241 to 300 6 (2400 to 2850) M12652A IMPORTANT WARNING Never hang the air cleaner higher than 16 ft (5m) TO REDUCE THE
Streszczenie treści zawartej na stronie nr. 5
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER • latches (2) • 3-speed switch module ( 3 Series only) FACTORY WIRING BLACK BLACK Make Opening (if Mounting in a Drop Ceiling) RED BROWN 1. Size the opening to fit the air cleaner cabinet as closely EXTERNAL BLUE WIRING BY MOTOR as possible. INSTALLER VIOLET 2. Frame the opening to provide adequate support for the WHITE cabinet. The cabinet must fit snugly in the opening; GREEN allow no more than 1/4 in. (6 mm) from the opening to each
Streszczenie treści zawartej na stronie nr. 6
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER HEX BOLT TOP OF METAL CABINET CAUTION THREADED LOCK ROD WASHER • This installation to be performed only by a qualified JAM installer. NUT • All wiring to comply with local electrical codes. • Disconnect power to air cleaner at fuse or breaker before beginning work. Failure to do so can result in CHAIN shock hazard endangering equipment and personal EYEBOLT safety of installer. JAM NUT • Only one air cleaner can be connected to a remote 3/8
Streszczenie treści zawartej na stronie nr. 7
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER 14. Connect one wire on air cleaner to power supply wire Removing /Replacing the Lid with a wire nut following color code used at remote switch. (White) IMPORTANT 15. Connect the ground wire from the remote switch to a The lid is heavy. Make sure that it is supported ground stud of the wiring compartment cover.(Green) before removing. 16. Fold wires into wiring compartment. Replace wiring compartment cover. To remove the lid, swing it into
Streszczenie treści zawartej na stronie nr. 8
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER Local, Federal and professional ventilation engineering 3. Place spent filter in a plastic trash bag and dispose of standards and codes prescribe minimum ventilation rates to properly. dilute air contamination in specific applications. The 4. Inspect the motor brackets for loose fasteners and ventilation rates usually assume the injection of outdoor air tighten as necessary. measured as air exchange rate. The use of the F111 (series 5. Install t
Streszczenie treści zawartej na stronie nr. 9
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER PARTS LIST Refer to Fig. 9 and Table 5 for replacement part information. Table 5. Replacement Parts. Fig. Reference No. Description Pack Qty Order Number 1 CPZ™ sorbent module (requires 2)—used with only 1 32004078-001 95% HEPA or 95% ASHRAE particle filters Charcoal sorbent module (requires 2)—used with only 1 32004078-002 95% HEPA or 95% ASHRAE particle filters Zeolite sorbent module (requires 2)—used with only 1 32004078-003 95% HEPA or 95% AS
Streszczenie treści zawartej na stronie nr. 10
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER CABINET ASSEMBLY SORBENT MEDIA MODULE 1 (2 REQUIRED) BLOWER WHEEL 2 3 MOTOR CAPACITOR 4 MOTOR 5 MEDIA FILTER PREFILTER 6 LID ASSEMBLY WITH 7 HINGES AND LATCHES M11995E Fig. 9. Exploded view of F111 (series 1,2,3) in Ceiling Media Air Cleaner components. 68-0198-2 Revised 5-09 10
Streszczenie treści zawartej na stronie nr. 11
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER NOTES 11 68-0198-2
Streszczenie treści zawartej na stronie nr. 12
LIMITED TWO-YEAR WARRANTY Air-Pure Systems warrants its air cleaner products to be free from defects in workmanship or materials under normal use and service, for a period of two (2) years from the date of purchase by the original end-user. If at anytime during the warranty period the product is defective or malfunc- tions, Air-Pure Systems, through the distributor or dealer, from which the product was purchased, or through an authorized warranty repair station, shall at Air-Pure Systems optio