F114 and F115 Ceiling Surface
Mounted Media Air Cleaners
PRODUCT DATA
FEATURES
• High Efficiency Particulate AIR (HEPA) filter models are
99.97% efficient and the D.O.P. particle filter models are
95% efficient at 0.3 micron particles. Both models are
more efficient on particles smaller and larger.
• F114 two-speed, direct-drive, forward curve, motor/blower
models deliver up to 325 cfm (550 m3/hr).
F114
• F115 single speed models deliver up to 600 cfm
(1020 m3/hr) .
• Select models include CPZ™
Summary of the content on the page No. 2
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS Models: SPECIFICATIONS Refer to Table 1 for model descriptions. IMPORTANT Color: The specifications given in this publication do not F114: white cabinet and cover. include normal manufacturing tolerances. Therefore, F115: white cabinet and cover. this unit may not exactly match the listed specifications. This product is tested and calibrated Blower/Motor: under closely controlled conditions, and some minor F114: two-speed, direct-drive, fo
Summary of the content on the page No. 3
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS Dimensions: Installation Weight: See Fig. 1 and 2 for dimensions. F114: approximately 40 lbs (18 kg). F115: approximately 80 lbs (36 kg). 37-1/2 (952) 34-1/8 (867) Controls: 28-7/8 (733) F114: two speed On/Off switch. 1-1/4 (31) F115: direct wired (optional remote mounted On/Off switch). 20 (508) Sound Level at 3.3 ft (1m): F114: 59 dBA on High speed, 55 dBA on Low speed. 4-3/4 F115: 52 to 56 dBA. (120) Replacement Parts and Accessories:
Summary of the content on the page No. 4
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS MEDIA AIR CLEANER 1 AIR SPACE TO BE CLEANED 1 DISCHARGE AIR FLOW IN ANY DIRECTION IS ACCEPTABLE. M11694 Fig. 3. Choose location for air cleaners. IMPORTANT CAUTION When selecting a location, make sure the air cleaner is secured to ceiling load-bearing supports Electrical Shock Hazard. or joists. If installing on a T-grid drop ceiling, secure Power source can shock. the air cleaner to the true ceiling. • Do not connect the power source u
Summary of the content on the page No. 5
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS IMPORTANT GREEN/YELLOW BLACK (L1) When installing the air cleaner, be sure to follow all MOTOR MOTOR WHITE (N) local codes and accepted practices. 1. Decide if the air cleaner wire connections will be from WHITE (N) JUNCTION BOX BLACK (L1) from the top or the side. Make the necessary wiring GREEN/YELLOW GREEN/YELLOW provisions at the ceiling. BLACK (L1) 2. Grasp the air cleaner cover edge near the plenum WHITE (N) and remove the cover from
Summary of the content on the page No. 6
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS 1. Grasp the edge of the air cleaner cover near the plenum and remove the cover from the support CAUTION brackets. Set it aside. Electrical Shock Hazard. 2. Remove the prefilters. Power source can shock. 3. Check the prefilters and replace them if they are fully • Turn off the power to the air cleaner when cleaning coated with dust and lint (approximately every 1 to 3 or servicing. months). • Stand on a stable platform when working 4. Repl
Summary of the content on the page No. 7
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS PLENUM 1 9 2 3 11 (EARLY MODELS 4 11 AND 12 0NLY) 12 5 10 6 7 8 M12711 Fig. 6. Exploded view of F114 Ceiling Surface Mounted Media Air Cleaner components. 7 68-0201-2 Revised 11-07
Summary of the content on the page No. 8
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS Table 3. F115 Ceiling Surface Mounted Media Air Cleaner Parts List. Fn ig. Reference No.Dy escriptio Pr ack QtO. rder Numbe Reference No 1 B1 lower Wheel 3A 2000245 902515 11 20V, 60 Hz 37 2000249 90506 2 21 20-240V, 50/60 Hz motor 3- 2001839 - 3M1 id-plate 34 2000241 90020 P4 refilter (1 box) 35 2000229 3601 4 10 0 boxes 4036 200023 3601 H1 EPA filter (requires 4) 30 2000206 2150 5 D1 .O.P. Particle filter (requires 4) 30 2000217 2871 6D1
Summary of the content on the page No. 9
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS INSPECTION PLENUM PLATE 1 2 3 4 ACCESS PLATE 5 6 7 8 M12712 Fig. 7. Exploded view of F115 Ceiling Surface Mounted Media Air Cleaner components. 9 68-0201-2 Revised 11-07
Summary of the content on the page No. 10
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS LIMITED TWO-YEAR WARRANTY Air-Pure Systems warrants its air cleaner products to be free from defects in workmanship or materials under normal use and service, for a period of two (2) years from the date of purchase by the originial end-user. If at anytime during the warranty period the product is defective or malfunctions, Air-Pure Systems, through the distributor or dealer, from which the product was purchased, or through an authorized wa