Summary of the content on the page No. 1
F111 (Series 1,2)
In Ceiling Media Air Cleaner
PRODUCT DATA
FEATURES
• High Efficiency Particulate Air (HEPA) filter models are
99.97% efficient and the hospital grade particle filter
models are 95% efficient at 0.3 micron particles. Both
models are more efficient on particles smaller and
larger. There is also a 95% ASHRAE model.
• Circulates up to 1230 cfm.
• Designed to overcome the increase in air flow
resistance normally caused by filter loading.
• White or black color cover to compleme
Summary of the content on the page No. 2
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER SPECIFICATIONS IMPORTANT Models: Refer to Table 1 for model descriptions. The specifications given in this publication do not include normal manufacturing tolerances. Therefore, Color: White or black cabinet and cover. this unit may not exactly match the listed specifica- tions. Also, this product is tested and calibrated Blower/Motor: Single speed direct drive forward curve. under closely controlled conditions, and some minor differences in per
Summary of the content on the page No. 3
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER Approvals: 2. When Cutting Or Drilling Into The Wall Or Ceiling, Do Underwriters Laboratories Inc.: Listed. Not Damage Electrical Wiring And Other Hidden Utili- Canadian Standards Association: Listed. ties. 3. Never Place A Switch Where It Can Be Reached From Accessory: 32000234 Variable Speed Switch. A Tub Or Shower. 4. Use This Unit Only In The Manner Intended By The Replacement Parts See Parts List, Table 4. Manufacturer. If You have Questions
Summary of the content on the page No. 4
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER 1. Locate the prepunched hole in the side of the cabinet. INSTALLATION 2. Remove the air cleaner lid. 3. Remove the connection box cover plate in the center cavity of the air cleaner. 4. Refer to Fig. 3 and 4 for typical wiring diagrams. WARNING Explosion Hazard Possible. Can cause personal injury or equipment damage. Do not install or use the F111 (series 1,2) air cleaner WARNING where there is any danger of gas, vapor or dust Risk of Fire or Ele
Summary of the content on the page No. 5
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER • Never rest the air cleaner on the T-bar. 11. For Series 1 only. Be sure the fastener tabs are facing downward and fasten them. 5. Level the air cleaner. 12. For Series 2 only. Be sure both catches are turned 6. Turn the air cleaner power on and check for proper down and filter rests firmly on catches. operation for 2 to 3 minutes. There should be a smooth, 13. Install the prefilter in the air cleaner lid. Position the powerful blower sound and
Summary of the content on the page No. 6
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER To remove the lid, swing it into the open position. Move the lid at least 20% of a specified ventilation rate or code must be to the side to disengage the hinge pins. Reverse the derived from outdoor air. The F111 (series 1,2) air cleaner procedure to replace the lid. filtered and recirculated air can be the remaining 80%. OPERATION SERVICE The F111 (series 1,2) in Ceiling Media Air Cleaner has been engineered to improve indoor air quality for co
Summary of the content on the page No. 7
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER IMPORTANT 3. For Series 2 only.Support the adsorbent module with Do not touch the pleated filter media. Handle only the one hand and turn open the catches filter frame to prevent damage to the filter media. 4. Use two hands and slide the filter from the housing. 7. Close and latch the lid. IMPORTANT The module weighs about 26 lb (12 kg) and can be hard to handle. CPZ™ Adsorbent Module The CPZ™ adsorbent module is used to collect gases, 5. Place th
Summary of the content on the page No. 8
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER PARTS LIST Refer to Fig. 8 and Table 4 for replacement part information. Table 4. Replacement Parts. Fig. Reference No. Description Pack Qty Order Number Reference No. 1 CPZ™ sorbent module (requires 2)—used with only 1 32004078-001 31005 95% HEPA or 95% ASHRAE particle filters Charcoal sorbent module (requires 2)—used with only 1 32004078-002 — 95% HEPA or 95% ASHRAE particle filters Zeolite sorbent module (requires 2)—used with only 1 32004078-00
Summary of the content on the page No. 9
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER CABINET ASSEMBLY SORBENT MEDIA MODULE 1 (2 REQUIRED) 2 BLOWER WHEEL 3 MOTOR CAPACITOR 4 MOTOR MEDIA FILTER 5 PREFILTER 6 LID ASSEMBLY WITH 7 HINGES AND LATCHES M11995E Fig. 8. Exploded view of F111 (series 1,2) in Ceiling Media Air Cleaner components. 9 68-0198EF-4 Rev. 11-07
Summary of the content on the page No. 10
LIMITED TWO-YEAR WARRANTY Air-Pure Systems warrants its air cleaner products to be free from defects in workmanship or materials under normal use and service, for a period of two (2) years from the date of purchase by the original end-user. If at anytime during the warranty period the product is defective or malfunc- tions, Air-Pure Systems, through the distributor or dealer, from which the product was purchased, or through an authorized warranty repair station, shall at Air-Pure Systems optio