Bryant 591B user manual

User manual for the device Bryant 591B

Device: Bryant 591B
Category: Air Conditioner
Manufacturer: Bryant
Size: 0.1 MB
Added : 10/27/2013
Number of pages: 12
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Bryant 591B. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Bryant 591B.

For your convenience

If looking through the Bryant 591B user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Bryant 591B on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Bryant 591B to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Bryant 591B User manual - Online PDF
Advertisement
« Page 1 of 12 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Bryant 591B but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Bryant 591B. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

installation and
591B, 550A
start-up instructions
552A, 556A
11, 12, 13, 14 SEER
SPLIT-SYSTEM AIR CONDITIONERS
WITH PURON® REFRIGERANT
Cancels: II 550A-18-3 II 550A-18-4
11-03
NOTE: Read the entire instruction manual before starting the
installation.
This symbol → indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal

Summary of the content on the page No. 2

NOTE: Avoid contact between tubing and structure OUTDOOR WALL INDOOR WALL CAULK LIQUID TUBE A C L B VAPOR TUBE INSULATION THROUGH THE WALL 3 8 ⁄16″ JOIST 3 ⁄8 IN. DIA TIEDOWN KNOCKOUTS HANGER STRAP (2) PLACES (AROUND VAPOR INSULATION IN BASEPAN TUBE ONLY) A97375 VAPOR TUBE DIMENSIONS (IN.) TIEDOWN KNOCKOUT UNIT BASE PAN LOCATIONS DIMENSIONS AB 22-1/2 X 27-1/2 2-13/16 6-15/16 30X33 5-1/16 9-11/16 1″ MIN. Fig. 3—Clearance Requirements LIQUID TUBE clearance on 1 side of unit and 12 in. on all remai

Summary of the content on the page No. 3

INSTALLING TXV IN PLACE OF PISTON 10 O'CLOCK 2 O'CLOCK 1. Pump system down to 2 psig and recover refrigerant. SENSING BULB 2. Remove hex nut from piston body. Use backup wrench on fan coils. STRAP 3. Remove and discard factory-installed piston. Be sure teflon seal is in place. 4. Reinstall hex nut. Finger tighten nut plus 1/2 turn. SUCTION TUBE NOTE: If the piston is not removed from the body, TXV will not function properly. 8 O'CLOCK 4 O'CLOCK 7 7 CAUTION: To prevent damage to the unit, u

Summary of the content on the page No. 4

TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.) LIQUID VAPOR VAPOR (LONG LINE) UNIT SIZE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018, 024 3/8 3/8 5/8 5/8 5/8 3/4 030, 036 3/8 3/8 3/4 3/4 3/4 7/8 042, 048 3/8 3/8 7/8 7/8 7/8 1-1/8 060 3/8 3/8 7/8 1-1/8 7/8 1-1/8 NOTES: 1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service

Summary of the content on the page No. 5

R - 4 1 0 C. REFRIGERANT TUBING 5000 Connect vapor tube to fitting on outdoor unit vapor service valves. 4500 Connect liquid tube to filter drier. (See Fig. 6 and Table 1.) Use 4000 refrigerant grade tubing. LEAK IN 3500 SYSTEM LIQUID-LINE 3000 FILTER-DRIER 2500 LIQUID 2000 SERVICE VALVE VACUUM TIGHT 1500 TOO WET 1000 TIGHT 500 DRY SYSTEM CONNECTOR TUBE A95424 0 1 23 4 5 67 MINUTES A95424 Fig. 7—Deep Vacuum Graph 5. Repeat this procedure as indicated in Fig. 8. System will then be free of any co

Summary of the content on the page No. 6

A. ROUTE GROUND AND POWER WIRES XI. START-UP Remove access panel to gain access to unit wiring. Extend wires CAUTION: To prevent compressor damage or personal from disconnect through power wiring hole provided and into unit injury, observe the following: control box.  Do not overcharge system with refrigerant.  Do not operate unit in a vacuum or at negative pressure. WARNING: The unit cabinet must have an uninter-  Do not disable low-pressure switch. rupted or unbroken ground to minimize pers

Summary of the content on the page No. 7

TABLE 3—REQUIRED LIQUID-LINE TEMPERATURE (°F) REQUIRED SUBCOOLING LIQUID TEMPERATURE PRESSURE AT (°F) SERVICE VALVE (PSIG) 8 1012141618 189 58 56 54 52 50 48 195 60 58 56 54 52 50 202 62 60 58 56 54 52 208 64 62 60 58 56 54 215 66 64 62 60 58 56 222 68 66 64 62 60 58 229 70 68 66 64 62 60 236 72 70 68 66 64 62 243 74 72 70 68 66 64 251 76 74 72 70 68 66 259 78 76 74 72 70 68 266 80 78 76 74 72 70 274 82 80 78 76 74 72 283 84 82 80 78 76 74 291 86 84 82 80 78 76 299 88 86 84 82 80 78 308 90 88 86

Summary of the content on the page No. 8

TABLE 4—SUPERHEAT CHARGING EVAPORATOR ENTERING AIR TEMPERATURE (°F WB) OUTDOOR TEMP (°F) 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12141720232629323537404245 60 7 10121518212427303335384043 65 — 6 10 13 16 19 21 24 27 30 33 36 38 41 70 — — 7 1013161921242730333639 75 — — — 6 9 12 15 18 21 24 28 31 34 37 80 ———— 5 8 12 15 18 21 25 28 31 35 85 —————— 8 11 15 19 22 26 30 33 90 —————— 5 9 13 16 20 24 27 31 95 ——————— 6 10 14 18 22 25 29 100 ———————— 8 12 15 20 23 27 105 ———————— 5 9 13 17 22 26

Summary of the content on the page No. 9

BRYANT BRYANT FA, FB, FC, NON-PROGRAMMABLE NON-PROGRAMMABLE FD, FF AIR SINGLE-STAGE AIR THERMOSTAT THERMOSTAT FAN COIL CONDITIONER MODEL AC FURNACE CONDITIONER MODEL AC 24 VAC HOT 24 VAC HOT R R R R 24 VAC COM 24 VAC COM C C C C SEE SEE HEAT STAGE 1 W/W1 W C C NOTE 2 NOTE 2 HEAT STAGE 1 W/W1 W2 COOL STAGE 1 Y/Y2 Y COOL STAGE 1 Y/Y2 INDOOR FAN G G G INDOOR FAN G A97359 A97360 BRYANT BRYANT PROGRAMMABLE PROGRAMMABLE FA, FB, THERMOSTAT SINGLE-STAGE AIR THERMOSTAT FC, FD, FF AIR MODEL AC FURNACE

Summary of the content on the page No. 10

BRYANT BRYANT NON-PROGRAMMABLE PROGRAMMABLE AIR THERMOSTAT FK4C AIR THERMOSTAT FK4C CONDITIONER MODEL AC FAN COIL CONDITIONER MODEL AC FAN COIL J1 JUMPER DH DH 24 VAC HOT R 24 VAC HOT R R R C INDOOR FAN G 24 VAC COM J1 JUMPER C G J2 JUMPER W/W1 W/W1 HEAT STAGE 1 HEAT STAGE 1 J2 JUMPER W1 SEE W1 C NOTE 2 Y/Y2 Y/Y2 COOL STAGE 1 COOL STAGE 1 W2 W2 Y/Y2 G NOT USED O/W2 INDOOR FAN Y/Y2 G NOT USED Y1/W2 SEE C NOTE 2 O Y1 C 24 VAC COM C Y1 B A97363 NOT USED OTHER O L NOT USED NON-PROGRAMMABLE FK4C A

Summary of the content on the page No. 11

PURON® (R–410A) QUICK REFERENCE GUIDE  Puron® refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron®  Puron® refrigerant cylinders are rose colored.  Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.  Puron® systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with

Summary of the content on the page No. 12

© 2003 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. 550a184 Catalog No. 5355-020 —12—


Alternative user manuals
# User manual Category Download
1 Bryant 113A User manual Air Conditioner 365
2 Bryant 24B User manual Air Conditioner 61
3 Bryant 187B User manual Air Conditioner 39
4 Bryant 342S User manual Air Conditioner 17
5 Bryant 39479D8 User manual Air Conditioner 31
6 Bryant 342 User manual Air Conditioner 15
7 Bryant 165A User manual Air Conditioner 22
8 Bryant 450D User manual Air Conditioner 21
9 Bryant 451P User manual Air Conditioner 7
10 Bryant 451 User manual Air Conditioner 7
11 Bryant 36-453 User manual Air Conditioner 10
12 Bryant 452W User manual Air Conditioner 6
13 Bryant 452 User manual Air Conditioner 3
14 Bryant 454 User manual Air Conditioner 112
15 Bryant 463AAC008BA User manual Air Conditioner 17
16 Sony SU-PW2 User manual Air Conditioner 12
17 Sony CV-P12PX User manual Air Conditioner 3
18 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
19 Sony VGN-BX500 User manual Air Conditioner 1
20 Philips 190S5 User manual Air Conditioner 21