Summary of the content on the page No. 1
254599-YTG-C-0807
DESCRIPTION
®
YORK Sunline Plus™ units are convertible single package
air conditioners. The units were designed for light commercial
TECHNICAL GUIDE
and commercial applications. They can easily be installed on
a roof curb, slab, roof jack or frame.
SINGLE PACKAGE GAS/ELECTRIC UNITS
All units include:
AND SINGLE PACKAGE
• Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
AIR CONDITIONERS
• Permanently lubricated motors
DF 072
• Bottom or side air d
Summary of the content on the page No. 2
254599-YTG-C-0807 TABLE OF CONTENTS DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 LIST OF TABLES PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 Tbl. # Pg. # FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . . 8 2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . . 8 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5 3 GAS HEAT RATINGS . . . . . . . . . . . . .
Summary of the content on the page No. 3
254599-YTG-C-0807 PRODUCT NOMENCLATURE 6 Ton Sunline Model Number Nomenclature D F 072 N04 A 2 A AA 1 0 1 2 4 A Product Category Product Style D = A/C, Single Pkg., R-22 A = Style A Product Identifier Configuration Options (not required for all units) These four digits will not be assigned until a quote is requested, or an order placed. F = 10.4 EER A/C SS Drain Pan CPC Controller, DFS, APS Nominal Cooling Capacity Johnson Controller, DFS, APS Honeywell Controller, DFS, APS 072 = 6.0 Ton Novar C
Summary of the content on the page No. 4
254599-YTG-C-0807 gas valve, if applicable, and the temperature limit FEATURES switch on gas heat units. The unit control board will All models are available with a wide variety of factory- alarm on ignition failures, compressor lockouts and mounted options such as stainless steel heat exchangers, repeated limit switch trips. electric heaters, phase monitor, convenience outlet, dirty filter • Nuisance Trip Protection- To prevent nuisance switch, disconnect switch, smoke detectors, and coil
Summary of the content on the page No. 5
254599-YTG-C-0807 FIGURE 1 - UNIT CUTAWAY • ELECTRIC HEATERS - Wired for single point power FACTORY-INSTALLED OPTIONS supply. These nickel chromium heater elements are pro- • SINGLE INPUT ELECTRONIC ENTHALPY ECONO- vided with limit and automatic reset capability to prevent MIZERS - Includes a slide-in / plug-in damper assembly operation at excessive temperatures. with fully modulating spring-return motor actuator capa- • FILTER OPTIONS - Standard units are shipped with 1” ble of introducing u
Summary of the content on the page No. 6
254599-YTG-C-0807 scheduling is built-in. Two different modes of demand power to the control board if smoke is detected within the ventilation are achieved through the INTELLI-Comfort™ air compartment. using CO2 sensors. It uses an inside CO2 sensor to per- form Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to pro- vide comfortable ventilation air temperature. The pat- Factory installed S
Summary of the content on the page No. 7
254599-YTG-C-0807 tudes up to 6,000 feet. This accessory supplements the FIELD-INSTALLED ACCESSORIES basic propane conversion kit. • SINGLE INPUT ELECTRONIC ENTHALPY ECONO- • LOW NOX KIT- Required to reduce the emission of MIZERS - Includes a slide-in / plug-in damper assembly nitrogen oxides below 40 nanograms per joule. with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal • POWER EXHAUST - Our single input economizer 1% leakage ty
Summary of the content on the page No. 8
254599-YTG-C-0807 1 TABLE 1: SOUND POWER RATING -12 SOUND POWER (db 10 Watts) ESP BLOWER UNIT Octave Band Centerline Frequency (Hz) dB(A) CFM SWL SIZE @ dB(A) IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000 2 10Ft. 072 2,200 0.3 HIGH 1.35 87877770726560557744 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system d
Summary of the content on the page No. 9
254599-YTG-C-0807 TABLE 5: DF072 COOLING CAPACITIES (6 TON) Temperature of Air on Condenser Coil Return Air 2 Gross Sensible Capacity (MBh) Gross Sensible Capacity (MBh) Gross Power Gross Power Capacity Input Return Air Dry Bulb (°F) Capacity Input Return Air Dry Bulb (°F) WB CFM 1 (MBh) (kW) (MBh) (kW) (°F) 86 83 80 77 74 71 68 90 85 80 75 70 65 68 85°F 95°F 72 83.1 5.24 54.6 46.4 38.2 30.0 21.8 - - 80.2 5.92 53.1 44.9 36.7 28.5 20.3 - - 67 79.5 5.15 67.8 59.6 51.4 43.2 35.0 26.8 18.6 75.3 5.8
Summary of the content on the page No. 10
254599-YTG-C-0807 TABLE 6: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION 1 Available External Static Pressure - IWG Unit Air Flow 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Tonnage (CFM) RPMWatts RPMWatts RPMWatts RPMWatts RPMWatts RPMWatts RPMWatts 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160
Summary of the content on the page No. 11
254599-YTG-C-0807 TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION 1 Available External Static Pressure - IWG Unit Motor 0.2 0.3 0.4 0.5 0.6 Tonnage Speed CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts Hi 2256 883 2258 931 2247 950 2223 964 2182 979 Med/Hi 2145 771 2127 784 2119 808 2089 826 2051 844 2 6 Med 2020 637 1999 656 1985 675 1947 696 1910 715 Med/Low --- - ---- -- Low --- - ---- -- 1 Available External Static Pressure - IWG Unit Motor 0.7 0.8 0.9 1
Summary of the content on the page No. 12
254599-YTG-C-0807 TABLE 11: ELECTRICAL DATA - DF072 BELT DRIVE W/O POWERED CONV. OUTLET COMPRESSORS ID MIN. MAX. FUSE/ OD FAN CONV 1 MODEL BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR VOLTAGE MOTOR OUTLET RLA LRA TONNAGE MOTOR MODEL NO. KW AMPS AMPACITY SIZE FLA FLA EACH EACH FLA (AMPS) (AMPS) None - - 33.4 45 2 2CE04510525 4 11.1 33.4 45 2 2CE04510725 5.6 15.5 33.4 45 208-3-60 20.7 156.0 2.3 5.2 0.0 2CE04511025 8 22.2 34.3 45 2CE04511525 11.9 33.0 47.8 50 2CE04512025 15.9 44.1 61.7 70 2CE0
Summary of the content on the page No. 13
254599-YTG-C-0807 TABLE 13: ELECTRICAL DATA - DF072 BELT DRIVE W/POWERED CONV. OUTLET COMPRESSORS ID MIN. MAX. FUSE/ OD FAN CONV 1 MODEL BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR VOLTAGE MOTOR OUTLET RLA LRA TONNAGE MOTOR MODEL NO. KW AMPS AMPACITY SIZE FLA FLA EACH EACH FLA (AMPS) (AMPS) None - - 43.4 60 2 2CE04510525 4 11.1 43.4 60 2 2CE04510725 5.6 15.5 43.4 60 208-3-60 20.7 156.0 2.3 5.2 10.0 2CE04511025 8 22.2 46.8 60 2CE04511525 11.9 33.0 60.3 70 2CE04512025 15.9 44.1 74.2 80 2CE04
Summary of the content on the page No. 14
254599-YTG-C-0807 TABLE 15: DF PHYSICAL DATA DF MODELS 072 Centrifugal Blower (Dia. x Wd. in.) 12 X 10 EVAPORATOR Fan Motor HP (Direct Drive) 1 BLOWER Fan Motor HP (Belt Drive) 1 1/2 Rows Deep 4 EVAPORATOR Fins Per Inch 13 COIL Face Area (Sq. Ft.) 5.1 Propeller Dia. (in.) 24 CONDENSER Fan Motor Hp 1/2 FANS Nom. CFM 4200 Rows Deep 2 CONDENSER Fins Per Inch 18 COILS Face Area (Sq. Ft.) 17.1 COMPRESSOR Recip Type 1 (Qty. Per Unit) Quantity Per Unit (15” X 20” X 1” or 2“) 2 AIR Quantity Per Unit (14
Summary of the content on the page No. 15
254599-YTG-C-0807 TYPICAL POWER WIRING REFER TO THE ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, OVERCURRENT PROTEC- TION AND WIRING. TYPICAL CONTROL WIRING COOLING / HEATING (24 VOLT THERMOSTAT) COOLING ONLY (24 VOLT THERMOSTAT) 1 THERMOSTAT 1 TERMINALS THERMOSTAT UNIT TERMINAL TERMINALS STRIP TB1 UNIT TERMINAL RH STRIP TB1 ADD RV R JUMPER RC R 24 VOLT Y Y1 YC Y1 24 VOLT TRANSFORMER TRANSFORMER Y2 Y2 W W1 GF G W2 C G G C 1 24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER ON SE
Summary of the content on the page No. 16
254599-YTG-C-0807 FIGURE 3 - UNIT DIMENSIONS (6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW FIGURE 4 - UNIT DIMENSIONS (6 TON COOLING/GAS HEAT) FRONT VIEW 16 Unitary Products Group
Summary of the content on the page No. 17
254599-YTG-C-0807 DETAIL “A” FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD DETAIL “B” FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD Unitary Products Group 17
Summary of the content on the page No. 18
254599-YTG-C-0807 FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) TABLE 18: UTILITIES ENTRY FILTER ACCESS HOLE OPENING SIZE (DIA.) USED FOR BLOWER MOTOR Side 1 2 ACCESS A 7/8” KO Control Wiring Bottom DOT PLUGS Side 1 B Power Wiring 2” KO FIELD-SUPPLIED Bottom DISCONNECT SWITCH LOCATION C 1-5/8” KO Gas Piping (Front) MOUNTING BRACKET FOR DICONNECT SWITCH D 1-1/2” KO Gas Piping (Bottom) (Shipped attached to the blower housing inside A,B the blower compartment) 1. Opening in the bottom to the unit can be
Summary of the content on the page No. 19
254599-YTG-C-0807 FIGURE 9 - TYPICAL APPLICATIONS Unitary Products Group 19
Summary of the content on the page No. 20
254599-YTG-C-0807 BACK OF UNIT BACK OF UNIT A 7 A 7 44 / 44 / 8 8 1 1 82 / 82 / 4 4 B D F X X B C E APPROXIMATE APPROXIMATE CENTER OF GRAVITY CENTER OF GRAVITY CONDENSER COIL CONDENSER COIL C D END OF UNIT END OF UNIT FRONT OF UNIT Y FRONT OF UNIT Y FIGURE 10 - FOUR AND SIX POINT LOADING TABLE 20: DF 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION 4-Point Loading (lb) 6-Point Loading (lb) UNIT TOTAL AB CDABCD E F DF072 Cooling/ Electric 660 147 144 183 186 98 97 96 122 123 125 DF072D06 710 158 155 197