Summary of the content on the page No. 1
036-21216-003-A-0204
FLEXIBLE LIGHT COMMERCIAL UNIT
TECHNICAL GUIDE
SUNLINE ULTRA™
GENERAL
SINGLE PACKAGE AIR-COOLED
YORK’s Sunline Ultra package units are designed to han-
dle applications ranging from residential to light commer-
AIR CONDITIONERS
cial and any in between. The Sunline Ultra is a unit that
gives you the flexibility and choices you need in today’s
3, 4 AND 5 NOMINAL TON
market.
D1HE/D1HG036, 048 and D2HE/D2HG060
FEATURING
12.2 THROUGH 13.2 SEER
• COOLING ONLY UNITS
• COOL
Summary of the content on the page No. 2
036-21216-003-A-0204 TABLE OF CONTENTS DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 LIST OF TABLES FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Tbl. Pg. FACTORY-INSTALLED OPTION . . . . . . . . . . . . . . . 4 FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 4 1 CAPACITY RATING - COOLING / ELECTRIC HEAT . . 5 MECHANICAL SPECIFICATIONS . . . . . . . . . . . . . 24 2 CAPACITY RATINGS - COOLING / GAS HEATING . . . 6 3 SOUND POWER RATINGS
Summary of the content on the page No. 3
036-21216-003-A-0204 damper and economizers simply slide in, and electrical con- DESCRIPTION nections are made by modular plugs. Electric heaters mount easily, and knockouts are provided in the internal partitions to YORK Sunline Ultra units are high efficiency, convertible, sin- connect the elements to the control box single point kit. gle package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were The motorized air damper includes a sl
Summary of the content on the page No. 4
036-21216-003-A-0204 troubleshooting without affecting the normal system operat- MANUAL OUTDOOR DAMPER - Provides 0% through 35% ing pressures. or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return AIR FILTERS - Units are shipped with 1" throwaway filters. applications. Includes rain hood assembly and filter. The unit filter racks can accommodate 1" or 2" filters without any modifications ELECTRIC HEATERS - Include nickel chromiu
Summary of the content on the page No. 5
036-21216-003-A-0204 WALL THERMOSTAT - The units are designed to operate All units can operate with single stage heat / single stage cool with 24-volt electronic and electro-mechanical thermostats. thermostats - with or without the economizer. .
Summary of the content on the page No. 6
036-21216-003-A-0204 TABLE 2: CAPACITY RATINGS - COOLING / GAS HEATING 1 GAS HEAT CAPACITY ARI RATINGS COOLING CAPACITY SOUND DOE GAS MODEL 3 4 5 INPUT TEMP. RISE AFUE S.S.E. S.E. 80 / 67-95°F 2 OUTPUT LINE SIZE RATING (MBH) (°F) (%) (%) (%) 6 7 (MBH) (in. O.D.) MBH (dBels) SEER EER DHG036N040 42.5 12.25 11.1 86 50 40 80.0 81.6 77.3 15-45 1/2 DHG036N079 42.5 12.25 11.1 86 100 79 80.5 80.8 77.9 40-70 1/2 DHG048N060 75 59 80.9 81.6 77.3 25-55 1/2 46.5 13.20 11.40 87 DHG048N099 125 99 80.3 80.6 77.
Summary of the content on the page No. 7
036-21216-003-A-0204 TABLE 5: COOLING CAPACITIES - MODELS DHE/DHG 036 - 85°F - 95ºF TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F EVAPORATOR 3 SENSIBLE CAPACITY COIL TOTAL POWER ENTERING DRY BULB, °F 1 CAP. 2 INPUT WB MBH CFM 86 83 80 77 74 71 68 °F 72 55.2 3.18 35.2 30.7 26.2 21.8 17.3 #N/A #N/A 67 49.1 3.13 41.7 37.2 32.8 28.3 23.8 19.4 14.9 1500 62 44.7 3.05 44.7 43.6 39.1 34.6 30.1 25.7 21.2 57 42.4 3.05 42.4 42.4 42.4 37.9 33.4 29.0 24.5 72 55.2 3.18 35.2 30.7 26.2 21.8 17.3 #N/A #N/A 6
Summary of the content on the page No. 8
036-21216-003-A-0204 TABLE 6: COOLING CAPACITIES - MODELS DHE/DHG 036 - 105°F - 115ºF TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 105°F EVAPORATOR 3 SENSIBLE CAPACITY COIL TOTAL POWER ENTERING DRY BULB, °F 1 CAP. 2 INPUT WB MBH CFM 86 83 80 77 74 71 68 °F 1500 72 47.6 3.65 32.3 27.8 23.3 18.9 14.4 #N/A #N/A 67 42.5 3.56 39.0 34.5 30.0 25.6 21.1 16.6 12.1 62 38.0 3.49 38.0 38.0 36.6 32.1 27.6 23.1 18.7 57 37.4 3.54 37.4 37.4 37.4 32.9 28.5 24.0 19.5 1350 72 46.5 3.62 29.7 25.8 21.8 17.8 13.8 #N
Summary of the content on the page No. 9
036-21216-003-A-0204 TABLE 7: COOLING CAPACITIES - MODELS DHE/DHG048 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F 95°F EVAPORATOR 3 3 SENSIBLE CAPACITY SENSIBLE CAPACITY COIL TOTAL TOTAL POWER POWER ENTERING DRY BULB, °F ENTERING DRY BULB, °F 1 1 CAP. CAP. 2 2 INPUT INPUT WB MBH MBH CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 °F 72 59 3.3 46 40 34 28 23 - - 55 3.5 43 37 32 26 20 - 67 53 3.2 53 49 43 38 32 26 21 49 3.4 49 47 41 35 30 24 2000 62 47 3.2 47 47 47 42 36 30 25 44 3.4 44 44 44 38
Summary of the content on the page No. 10
036-21216-003-A-0204 TABLE 8: COOLING CAPACITIES - MODELS DHE/DHG060 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F 95°F EVAPORATOR 3 3 SENSIBLE CAPACITY SENSIBLE CAPACITY COIL TOTAL TOTAL POWER POWER ENTERING DRY BULB, °F ENTERING DRY BULB, °F 1 1 CAP. CAP. 2 2 INPUT INPUT WB MBH MBH CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 °F 72 82 4.3 56 50 43 37 30 - - 76 4.6 54 48 41 34 28 - - 67 70 4.2 67 61 54 48 41 34 28 65 4.5 65 58 51 45 38 31 25 2500 62 67 4.0 67 67 66 59 52 46 39 62 4
Summary of the content on the page No. 11
036-21216-003-A-0204 1 TABLE 9: SUPPLY AIR BLOWER PERFORMANCE -DHE/DHG036 2 AVAILABLE EXTERNAL STATIC PRESSURE - IWG AIR MODEL FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 DHE/DHG CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 881 815 920 900 961
Summary of the content on the page No. 12
036-21216-003-A-0204 1 TABLE 10: SUPPLY AIR BLOWER PERFORMANCE DHE/DHG048 (4 TON GAS HEAT MODELS) 2 AVAILABLE EXTERNAL STATIC PRESSURE - IWG UNIT AIR SIZE FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 (MBH CFM RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 88
Summary of the content on the page No. 13
036-21216-003-A-0204 1 TABLE 11: SUPPLY AIR BLOWER PERFORMANCE DHE/DHG060 (5 TON GAS HEAT MODELS) 2 AVAILABLE EXTERNAL STATIC PRESSURE - IWG UNIT AIR FLOW SIZE 0.20 0.30 0.40 0.50 0.60 0.70 0.80 CFM (MBH) RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535
Summary of the content on the page No. 14
036-21216-003-A-0204 TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER ADJUSTABLE FIXED 1 BELT MOTOR MOTOR PULLEY BLOWER PULLEY BLOWER MODEL RANGE PITCH PITCH PITCH FRAME SERVICE BORE BORE DESIG- (RPM) HP RPM DIA. DIA. LENGHT SIZE FACTOR (in.) (in.) NATION (in.) (in.) (in.) 7/ 1/ DHE/DHG 036 780 - 1120 1 1,725 56 1.15 2.4 - 3.4 5.7 1 37.3 A36 2 8 1/ 7/ DHE/DHG048 790 - 1,120 1 1,725 56 1.15 2.4 - 3.4 5.7 1 37.3 A36 2 8 1/ 7/ DHE/DHG060 850 - 1,220 1 1,725 56 1.15 2.4 - 3.4 5.2 1 37.3 A36 2 8 1.
Summary of the content on the page No. 15
036-21216-003-A-0204 TABLE 15: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE036 & 048 SUPPLY ELECTRIC HEATERS MAX. MAX. HEATER TOTAL AIR FUSE SIZE MODEL POWER ACCESSORY UNIT BLOWER TOTAL 1 2 DHE SUPPLY MODEL AMPACITY kW STAGES SIZE HACR MOTOR AMPS NUMBER AMPS AMPS AMPS FLA 3 4.0 1 11.0 25.2 35 35 2CE04500525 4 5.6 1 15.6 26.2 35 35 2CE04500725 208-3-60 5.3 2CE04501025 8.0 1 22.1 34.2 35 35 2CE04501525 11.9 2 33.1 48.1 50 50 2CE04502025 15.9 2 44.2 61.9 70 70 4 5.3 1 12.7 25.2 35 35 2CE04500525 4 7
Summary of the content on the page No. 16
036-21216-003-A-0204 TABLE 18: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE060 SUPPLY ELECTRIC HEATERS MAX. MAX. HEATER TOTAL AIR FUSE SIZE MODEL POWER ACCESSORY UNIT BLOWER TOTAL 1 2 DHE SUPPLY MODEL AMPACITY kW STAGES SIZE HACR MOTOR AMPS NUMBER AMPS AMPS AMPS FLA 3 4.0 1 11.0 26.0 40 40 2CE04500525 4 5.6 1 15.6 26.9 40 40 2CE04500725 2CE04501025 8.0 1 22.1 35.1 40 40 208-3-60 6.0 2CE04501525 11.9 2 33.1 48.9 50 50 2CE04502025 15.9 2 44.2 62.7 70 70 2CE04503025 22.2 2 61.7 84.6 90 90 4 5.3 1 12
Summary of the content on the page No. 17
036-21216-003-A-0204 #
$
Summary of the content on the page No. 18
036-21216-003-A-0204
All dimensions are in inches. They are subject to change without notice. Certi- fied dimensions will be provided upon request. FIGURE 7 - DHE UNIT DIMENSIONS TABLE 19: UTILITIES ENTRY DATA KNOCKOUT HOLE USED FOR SIZE (DIA.) Control Wiring (Side or 1 A 7/8” 2 Bottom) Power Wiring (Side or B 2” Bottom) C 1-5/8” Gas Piping (Front) D 1-1/2” Gas Piping (Bottom) 1. Kn
Summary of the content on the page No. 19
036-21216-003-A-0204
All dimensions are in inches. They are subject to change without notice. Certi- fied dimensions will be provided upon request. FIGURE 9 - UNIT DIMENSIONS DHG UNIT NOTE: DHG modes must be provided a 1” clearance TABLE 20: CLEARANCES between any combustible material and the supply DHE UNITS 24” air ductwork for a distance of 2 feet from the unit. FRONT DHG UNITS 32
Summary of the content on the page No. 20
036-21216-003-A-0204 FIGURE 10 - REAR DIMENSIONS OF DHE AND DHG UNITS 3, 4 & 5 TON UNITS Duct covers - units are shipped with all air duct openings cov- For bottom duct applications: ered. • remove the side supply air duct cover to gain access to For side duct applications: the bottom supply air knockout panel. • Remove and discard the bottom knockout panel. • Remove and discard the supply and return air duct • Replace the side duct cover.