Summary of the content on the page No. 1
360101-XTG-B-0508
DESCRIPTION
TECHNICAL GUIDE
These packaged cooling air conditioners are designed for
outdoor installation. Only utility and duct connections are
required at the point of installation.
AFFINITY™ SERIES
Field-installed electric heater accessories are available to
provide electric heat combined with electric cooling.
SINGLE PACKAGE
STANDARD FEATURES / BENEFITS
COOLING UNITS
OPERATING EFFICIENCY - All units provide high operating
D2EB030 THRU 060
efficiencies and have a min
Summary of the content on the page No. 2
360101-XTG-B-0508 TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 LIST OF TABLES STANDARD FEATURES / BENEFITS . . . . . . . . . . . . . . . . .1 Tbl. # Pg. # FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . .3 1 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . .16 2 RATINGS - ARI . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Summary of the content on the page No. 3
360101-XTG-B-0508 CONDENSER COIL GRILLE - A multi-piece totally enclosed, STANDARD FEATURES/BENEFITS (CONT.) rigidly mounted condenser coil grille provides protection from objects and personal after installation and provides protection UTILITY CONNECTIONS MADE EASY - Electrical utility during transit and installation. knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a LOW OPERATING SOUND LEVEL - The upward air flow
Summary of the content on the page No. 4
360101-XTG-B-0508 operation. Independent blade design insures proper control and MOTORIZED FRESH AIR DAMPER - Designed for duct less than 1% leak rate. Includes hood and mesh bird screen mounted side return and unit mounted down shot return filter integrated into the hood, dry bulb sensor and relief applications. Damper capable of providing 0% thru 50% of damper. Separate field accessories of single enthalpy and dual outdoor air (field supplied). Closes on power loss, includes enthalpy are
Summary of the content on the page No. 5
360101-XTG-B-0508 TABLE 1: PHYSICAL DATA DEB MODELS 030 036 042 048 060 EVAPORATOR CENTRIFUGAL BLOWER (Dia. x Wd. in.) 10 X 8 10 x 8 11 X 10 11 x 10 11 x 10 3 3 3 BLOWER FAN MOTOR HP ½ 4 4 4 1 ROWS DEEP 22 22 3 EVAPORATOR FINS PER INCH 15 15 15 13 16 COIL FACE AREA (Sq. Ft.) 4.38 4.38 4.38 5.62 5.26 PROPELLER DIA. (in.) 22 22 22 22 22 CONDENSER FAN MOTOR HP 1/4 1/4 1/4 1/4 1/4 FAN NOM. CFM TOTAL 2,400 2,400 2,400 2,800 2,800 ROWS DEEP 11 11 1 CONDENSER FINS PER INCH 20 18 16 13 20 COIL FACE AREA
Summary of the content on the page No. 6
360101-XTG-B-0508 TABLE 3: COOLING CAPACITIES - 2-1/2 TON (DEB030) AIR ON INDOOR COIL TEMPERATURE 750 CFM 875 CFM 1,000 CFM 1,125 CFM 1,250 CFM OF AIR ON WB °F WB °F WB °F WB °F WB °F OUTDOOR COIL 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 Net Cap 32.3 29.8 27.5 28.1 32.6 30.1 27.8 28.4 33.0 30.4 28.1 28.7 33.5 30.9 28.4 29.1 33.9 31.3 28.8 29.5 MBH Total Power 2.94 2.92 2.83 2.81 3.02 3.00 2.90 2.88 3.10 3.08 2.98 2.96 3.20 3.18 3.08 3.06 3.31 3.28 3.18 3.16 Input kW 86 18.2 23
Summary of the content on the page No. 7
360101-XTG-B-0508 TABLE 4: COOLING CAPACITIES - 3 TON (DEB036) AIR ON INDOOR COIL TEMPERATURE 900 CFM 1,050 1,200 1,350 1,500 OF AIR ON WB °F WB °F WB °F WB °F WB °F OUTDOOR COIL 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 Net Cap 34.7 32.3 28.5 28.4 36.9 34.3 30.3 30.1 39.0 36.4 32.1 31.9 39.9 37.1 32.7 32.6 40.7 37.9 33.4 33.2 MBH Total Power 3.61 3.52 3.46 3.46 3.62 3.53 3.47 3.47 3.63 3.55 3.48 3.48 3.70 3.61 3.55 3.55 3.77 3.68 3.61 3.61 Input kW 86 19.7 25.4 28.5 28.4 22.2
Summary of the content on the page No. 8
360101-XTG-B-0508 TABLE 5: COOLING CAPACITIES - 3-1/2 TON (DEB042) AIR ON INDOOR COIL TEMPERATURE 1,050 CFM 1,225 1,400 1,575 1,750 OF AIR ON WB °F WB °F WB °F WB °F WB °F OUTDOOR COIL 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 Net Cap 40.7 39.0 36.5 34.1 42.0 40.3 37.7 35.2 43.3 41.6 38.8 36.3 43.9 42.1 39.3 36.8 44.4 42.6 39.8 37.2 MBH Total Power 4.09 3.82 3.77 3.75 4.16 3.89 3.83 3.81 4.23 3.95 3.90 3.88 4.38 4.10 4.04 4.02 4.54 4.25 4.18 4.16 Input kW 86 23.8 31.3 36.5 34.1
Summary of the content on the page No. 9
360101-XTG-B-0508 TABLE 6: COOLING CAPACITIES - 4 TON (DEB048) AIR ON INDOOR COIL TEMPERATURE 1200 CFM 1400 CFM 1600 CFM 1800 CFM 2000 CFM OF AIR ON WB °F WB °F WB °F WB °F WB °F OUTDOOR COIL 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 Net Cap 49.2 46.1 41.6 41.3 50.6 47.4 42.9 42.5 52.1 48.8 44.1 43.7 52.8 49.4 44.7 44.2 53.4 50.1 45.2 44.8 MBH Total Power 4.47 4.44 4.35 4.33 4.59 4.57 4.47 4.45 4.72 4.69 4.59 4.57 4.78 4.76 4.66 4.63 4.85 4.83 4.72 4.70 Input kW 86 28.3 35.7 41
Summary of the content on the page No. 10
360101-XTG-B-0508 TABLE 7: COOLING CAPACITIES - 5 TON (DEB060) AIR ON INDOOR COIL TEMPERATURE 1200 CFM 1400 CFM 1600 CFM 1800 CFM 2000 CFM OF AIR ON WB °F WB °F WB °F WB °F WB °F OUTDOOR COIL 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 Net Cap 65.2 59.2 52.9 53.4 67.2 61.1 54.5 55.1 69.2 62.9 56.2 56.7 70.3 63.9 57.1 57.6 71.4 64.9 58.0 58.6 MBH Total Power 5.68 5.60 4.45 5.41 5.87 5.79 5.63 5.59 6.06 5.98 5.82 5.77 6.25 6.16 6.00 5.95 6.43 6.35 6.18 6.13 Input kW 86 37.9 46.9 52
Summary of the content on the page No. 11
360101-XTG-B-0508 TABLE 8: SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE Blower External Static Pressure (Inches Water Gauge) Model No. Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 DEB Setting CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W High - ----- -- 11715041080486990468888456786444 - - - - 030 Medium 1080 351 1021 341 961 331 902 321 841 305 781 290 - - - - - ---- - (2.5) Low 810261765240 -- ----- ---- - - ---- - High - - - - 1440 605 1361 581 1273 555 1185 530 1097
Summary of the content on the page No. 12
360101-XTG-B-0508 TABLE 10: ELECTRICAL DATA VOLTAGE SUPPLY MAX. COND. MAX. COMPRESSOR 1 AIR MINIMUM HACR UNIT LIMITATIONS 2 MODEL POWER FAN FUSE TRANSFORMER BLOWER CIRCUIT BREAKER POWER DEB SUPPLY MOTOR, SIZE, SIZE (VA) MOTOR AMPACITY SIZE, FACTOR MIN. MAX. RLA LRA FLA AMPS FLA AMPS 30 208/230-1-60 187 253 14.7 73 1.1 2.6 22.1 30 30 0.96 40 36 208/230-1-60 187 253 17.3 94 1.1 3.5 26.2 35 35 0.96 40 42 208/230-1-60 187 253 15.5 86 1.1 3.5 23.9 30 30 0.96 40 48 208/230-1-60 187 253 24.4 140 1.3 4.
Summary of the content on the page No. 13
360101-XTG-B-0508 TABLE 11: ELECTRICAL DATA (COOLING / ELECTRIC HEAT) (CONTINUED) SUPPLY COND. FAN AIR MAX FUSE/ 2 COMPRESSOR ELECTRIC HEAT ACCESSORY MODEL POWER MCA MAX HACR 1 MOTORS BLOWER SIZE DEB SUPPLY (AMPS) BREAKER SIZE MOTOR (AMPS) RLA LRA FLA FLA MODEL NO. STAGE KW TOTAL AMPS 2NH04501025 1 7.5/10.0* 20.8/24.1 30.4/34.4 35/35 35/35 042 208/230-3-60 11.5 88.0 1.1 3.5 2NH04501525 1 11.3/15.0* 31.3/36.1 43.5/49.5 45/50 45/50 2NP04501025 1 7.5/10.0* 20.8/24.1 31.1/35/1 35/40 35/40 2NP0450152
Summary of the content on the page No. 14
360101-XTG-B-0508 HIGH VOLTAGE CONN. FRONT COMPRESSOR " DIA. KNOCKOUT SERVICE ACCESS HIGH VOLTAGE CONN. COMPARTMENT PANEL " DIA. KNOCKOUT DIMENSION LOW VOLTAGE CONN. “A” UNIT SIZE “A” “ DIA. KNOCKOUT (OVERALL) 2 030 - 042 33 048 - 060 41 SIDE SUPPLY AIR OPENING REFRIGERANT SIDE RETURN CONNECTIONS AIR OPENING ELECTRICAL/FILTER SERVICE ACCESS COMPARTMENT PANEL HIGH VOLTAGE CONN. " DIA. KNOCKOUT (OVERALL) 2 (OVERALL) 1 LOW VOLTAGE CONN. “ DIA. KNOCKOUT UNIT CONDENSATE 4 CONNECTION “ NPTI FRONT (TRA
Summary of the content on the page No. 15
360101-XTG-B-0508 TABLE 12: UNIT WEIGHTS Corner Weights Shipping Operating Economizer Roof Curb Unit Size Weight Weight (lbs.) (lbs.) AB C D 030 333 328 85 81 82 86 036 338 333 91 80 78 88 8" - 70 042 347 342 94 83 80 91 40 14" - 75 048 368 363 92 88 92 97 060 376 371 105 100 84 87 CENTER OF GRAVITY D C FRONT A OF UNIT B 26 FIGURE 4 - CENTER OF GRAVITY Johnson Controls Unitary Products 15
Summary of the content on the page No. 16
360101-XTG-B-0508 TYPICAL APPLICATIONS SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT FIGURE 5 - TYPICAL SLAB ON GROUND INSTALLATION FIELD SUPPLIED DISCONNECT SWITCH MOUNTED ON UNIT TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT SUPPLY AIR DUCT ROOF CURB INSTALLATION RETURN AIR ROOF CURB REAR DUCT DUCT INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION FIGURE 6 - TYPICAL ROOF CURB INSTALLATION 16
Summary of the content on the page No. 17
360101-XTG-B-0508 1 4 OPENING FOR RETURN AIR DUCT 22 OPENING FOR 1 SUPPLY AIR DUCT 14 FRONT WOOD NAILER INSULATED PANELS RECOMMENDED DUCT SIZE SUPPLY AIR DUCT " x " RETURN AIR DUCT " x " FIGURE 7 - ROOF CURB DIMENSIONS (8” Roof curb also available) 1" " x 1" WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES UNIT BASE RAIL COUNTERFLASHING UNIT BASE WOOD NAILER CANT STRIP 8" MIN. ABOVE FINISHED ROOF 14" INSULATION AND ROOFING MATERIAL CURB FRAME INSULATION ROOF DECK AND ROOFING MATERIAL
Summary of the content on the page No. 18
360101-XTG-B-0508 SEE OPTIONAL CCH DETAIL "A" S / P CONFIGURATION CCH BLK L1 BLK T1 D / P CONFIGURATION CCH BLK L1 BLK L 2 M1 - 2 2 T2 L DETAIL "A" 15695BASH0301 FIGURE 9 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY) DEB MODELS 18 Johnson Controls Unitary Products
Summary of the content on the page No. 19
360101-XTG-B-0508 TYPICAL WIRING DIAGRAM NOTES TYPICAL WIRING DIAGRAM LEGEND - F 9 - 6 (N O T U SED ) - 2 - M 3 , 230V C O IL -- -- FIGURE 10 -TYPICAL WIRING DIAGRAM (208/230-3-60 POWER SUPPLY) DEB MODELS Johnson Controls Unitary Products 19
Summary of the content on the page No. 20
360101-XTG-B-0508 2 FIGURE 11 -TYPICAL WIRING DIAGRAM (460-3-60 AND 575-3-60 POWER SUPPLY) DEB MODELS 20 Johnson Controls Unitary Products